Approved Consent Files - Architectural Plans - DL20007 Queen Street Waimate RFI Plan Set - R1
Approved Consent Files - Architectural Plans - DL20007 Queen Street Waimate RFI Plan Set - R1
Approved Consent Files - Architectural Plans - DL20007 Queen Street Waimate RFI Plan Set - R1
01 28/07/2020
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Laundry Laundry
Lobby Lobby
WC WC
Living Living Living Living
Courtyard Courtyard
Kitchen Kitchen
Hall Hall
Store Room Store Room
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
Stairwell Stairwell
Kitchen Kitchen
Store Room Store Room
16G x 280 mm
16G x 280 mm
17R x 241 mm
17R x 241 mm
5 5
4 4
3 3
2 2
DOWN DOWN
1 1
Passage Passage UP UP
WC WC
Foyer Foyer
Existing Ramp
Existing Ramp
Stairwell Stairwell
07
Existing Ground
Existing
FloorGround
Plan Floor Plan 1:100 1:100
Firm Name Notes Job Title Design Pat Coll Client Name Scale
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
10
HW
9
11
8
12
7
13
6
Stairwell
16G x 280 mm
17R x 241 mm
14
Sunroom 5
15
Living
DOWN
UP
WC Bed 4
Store
Bathroom
Store
Hall
Bed 2 Bed 1
Bed 3
Firm Name Notes Job Title Design Pat Coll Client Name Scale
A301
A2
-All lights to be L.E.D and IC-F rated. 4.12.08 Safety Glass
- All door handles to be lever action between 3.01.04 Internal Walls 3.0m max 25 RFI 25 - Accessible Counter
900-1200mm returned towards door. Opening
pressure as per NZS4121:2011 Non Loadbearing generally construct with 90x45 SG8 H1.2
36 RFI 34 - Fire Alarm Panel Location
150
framing with studs @ 400mm crs to NZS3604:2011 Table. 02 5/08/2020
Bottom Plate Fixing For Timber Walls: Dwang at 800crs. Dwang for all fittings, fixtures, linings, 38 RFI 37 - Wall Finishes
Concrete Floor - All bottom plates to be fixed in Access WC
accordance with NZS3604:2011 Clause 7.5.12.2 - bracing panels & trims. DPC (malthoid) between bottom
Proprietary anchors shall be within 150mm of plate and conc. slab. A1 B1
each end of the plate and be spaced at a
2,110
maximum of 600mm centres.
External walls & internal wall bracing elements - C1
2/100x3.75mm hand driven nails or 3/90x3.15
power driven nails @ 600mm centres. 4 Enclosure Eatery
90
Internal walls - 1/100x3.75mm hand driven nail or Lobby
1/90x3.15 power driven nail @ 600crs
Bracing walls - All bracing element fixings as per 4.12.08 Safety Glass 5.01.12 Preperation Benchs
manufactures specifications. Grade A safety glass to all showers & overhead glazing, All WC
Smoke/Security: glazing to comply with N.Z.S 422301:2016. Refer to window 36
Alarms complying with and door schedule for glass selections. 3.01.04 Internal Walls 3.0m max
AS 3786, BS 5446, Part F7/AS1
Back up battery powered
90
Gib Aqualine Linings 5 Interior
890
Selected Carpet
5.01.12 Preperation Benchs Store
316 Stainless Stell benctops to have seamless sink welded
Courtyard
90
into. All benchs are to be on SS adjustable legs which allow Kitchen
Panel Location
Selected Branz Appraised Vinyl
A302
Fire Alarm
A3
benchs to be moved to allow cleaning of the floor and 5.01.12 Preperation Benchs
1,740
walls. 5.01.16 Wall Surface Finishes
Indicates Insulated Wall
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
200
5.01.16 Wall Surface Finishes 38
Indicates un-insulated Wall 2.7mm Standard Seratone to be applied to all entire wall
surface in Passage
Store
Fridges
1,360
hygeine areas including handwashing, kitchen, servery. Passage
90
F (400) F (400) G (600)
Range hood
1,919
5.01.12 Preperation Benchs
Kitchen 5.01.16 Wall Surface Finishes
WC
90
Stair Well
5.01.12 Preperation Benchs
560
Servery
5.01.16 Wall Surface Finishes
90
90 2,100 90
5.01.16 Wall Surface Finishes
22G x 280 mm
23R x 180 mm
7
3 DOWN
Accessible Counter
2
1 Bakery
Existing Ramp
A4 UP A4
1,496 A302 A302
723 723
Entry
A1 A1
A301 A301
glass washer
2,200
2,155
D01
Finishings Architrave
Glazing Safety Glass to Doors & Below 800mm
A302
A301
A3
A2
as per NZS4223
Double
Frame Aluminium
Firm Name Notes Job Title Design Pat Coll Client Name Scale
3 Structure
3.03.15 Concrete Block Wall
Concrete Block as per attached engineers documents.
4 Enclosure
4.09.06 Mesh Gate
Mesh lockable gate for entrance to compound
7 Services
150 15,230 150
7.02.24 Gas Bottles
4/45l gas bottles on concrete or tile pad secured to wall. 150 9,480 150 5,600 150
Gas systems to be installed as exempt work by an
150
approved installer and required certificates to be provided
150
at installation time. Gas bottle valves to be protected from
weather by suitable permanent Weather proof cover.
Compound
3,350
30
Solid Waste Storage
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
150
3.03.15 Concrete Block Wall
4.09.06 Mesh Gate 7.02.24 Gas Bottles
14,210
8,460
Yard
2,250
150
Firm Name Notes Job Title Design Pat Coll Client Name Scale
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
4 Enclosure
3.01.01 External Walls 90mm
4.12.08 Safety Glass
Grade A safety glass to all showers & overhead glazing, All
glazing to comply with N.Z.S 422301:2016. Refer to window 15 4.12.08 Safety Glass
Kitchen
and door schedule for glass selections. Dining
140
10
F
14
12 15
11 16
10 17
9 18 WC
8 19
Linen 3.01.04 Internal Walls 3.0m max
01
22G x 280 mm
23R x 180 mm
7
Bathroom
1,200
20
6
583 583
21
6,465
Laundry Store Wardrobe
W
HW
DOWN
Hall
1,321
1,000 UP
1,200
1,000 W/r
3,600
90
Bed 2 Bed 1
2,550
Bed 3
2,279
900
10
1,550
1,350
W/r
650
Frame Aluminium Frame Aluminium Frame Aluminium 246 439 1,000 495 200
18 W01
Opening restrictor as per F4/AS1 Opening restrictor as per F4/AS1 Opening restrictor as per F4/AS1
Glazing Double Glazing Double Glazing Double
Firm Name Notes Job Title Design Pat Coll Client Name Scale
NOTES
26 IP IP
ALL FOUL WATER MAINS 100MM Ø 1:60 FALL MIN
100MM DIA WASTE TO TOILET PANS WITH MIN 1 IN 60 GRADIENT FALL 7.02.23 Gas Califont
BATHROOM WASTE 40MM DIA TO BASINS, 50MM DIA TO SHOWER, ALL 7.02.02 100mm dia uPVC Sewer Line
WITH MIN 1 IN 40 GRADIENT
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
KITCHEN WASTE PROVIDE 50MM DIA TO SINKS AND DISHWASHER ALL
WITH MIN 1 IN 40 GRADIENT 50mm vent 50mm vent
LAUNDRY WASTE PROVIDE 50MM DIA TO WASHING MACHINE, AND TUB
ALL WITH MIN 1 IN 40 GRADIENT
Notes
Notes
WATER TRAP REQUIREMENTS: DISCHARGE POINTS FROM SANITARY 28 ORG*
FIXTURES AND SANITARY APPLIANCES SHALL HAVE A WATER TRAP TO 7 7 Services
Services
PREVENT FOUL AIR FROM THE PLUMBING SYSTEM ENTERING THE
BUILDING. WATER TRAPS SHALL BE REMOVABLE, ABLE TO BE 7.02.02
7.02.02100mm
100mm dia dia
uPVCuPVC
Sewer
Sewer
LineLine TV*
DISMANTLED, OR FITTED WITH A CLEANING EYE Existing
Existing
100mm
100mmdia dia
uPVCuPVC
sewer
sewer
lineline
connecting
connecting
intointo
mainmain IP
IP
line.line.
PVC PIPES TO BE DENSO TAPE WRAPED WHEN PASSING THROUGH
CONCRETE SLAB AND CONCRETE FOUNDATION WALL. FELT WRAPPED 7.02.13
7.02.13 Grease
GreaseTrapTrap
WHEN UNDERSLAB IN CONTACT WITH AP40 500L
500L polytrap
polytrapto to
be be
install
install
as as
perper
attached
attachedsuppliers
suppliers
specification.
specification.
Seating
Seating
provided
providedfor for
88 88
people,
people,
therfore
therfore
at at
PROVIDE INSPECTION POINTS IMMEDIATELY INSIDE BOUNDARY, AT 5L each
5L eachthe the
required
required
sizesize
of the
of the
grease
grease
traptrap
is 440L
is 440L
min.min.
EVERY HORIZONTAL CHANGE IN DIRECTION MORE THAN 45 DEGREE, AT Install
Install
withwith
heatheat
trace
trace
system
systemto piping
to piping
to prevent
to preventgrease
grease
AVERY JUNCTION THAT SERVES A SOIL FIXTURE OR ANY BRANCH
blockages.
blockages.
DRAIN LONGER THAN 2M AND AT BOTH ENDS WHERE A DRAIN PASSES
UNDER THE BUILDING 7.02.23
7.02.23GasGas
Califont
Califont
Rinnai
RinnaiINFINITY®
INFINITY®EF26EF26External
Externalinstalled
installedas asperper
PLUMBING PLANS INDICATIVE ONLY AND SUBJECT TO DRAINAGE AS
manufactures
manufacturesinstructions.
instructions.
BUILT PLANS BY PLUMBER. AS BUILT DRAINAGE PLANS TO BE
SUBMITED TO COUNCIL. HAND DRAWN PLANS WILL NOT BE ACCEPTED. 7.02.24
7.02.24GasGas
Bottles
Bottles
4/45l
4/45l
gasgas
bottles
bottles
on concrete
on concreteor tile
or tile
padpad
secured
secured
to wall.
to wall.
PLUMBING TO AS/NZS 3500 GasGassystems
systemsto tobe be
installed
installedas as
exempt
exempt workwork
by byan an
approved
approved
installer
installer
andand
required
required
certificates
certificates
to be
to provided
be provided
WATER SUPPLY at installation
at installation
time.
time.
GasGas
bottle
bottle
valves
valves
to be
to protected
be protectedfromfrom
weather
weather
by suitable
by suitable
permanent
permanentWeather
Weatherproof
proof
cover.
cover.
20MM Ø MDPE COLD WATER PIPE REQUIREMENTS FOR PROTECTION FROM 7.08.01
7.08.01Water
Water
Supply
Supply
FREEZING To be
To connected
be connected
to existing
to existing
water
water
services
services
on site.
on site.
Where
Where
HOT WATER (10MM MIN. PIPE TO ALL FIXTURES) PIPES TO BE LAGGED TO Potable
Potable
Water
Water
supply
supply
is not
is not
fromfrom
municipal
municipal
system
system(ie Well
(ie Well
PREVENT FREEZING water)
water)
a potable
a potable
water
water
testtest
certificate
certificate
willwill
be be
provided
provided
prior
prior
to Code
to Code
of Compliance
of Compliance
Certificate
Certificate
application.
application.
7.2 PROTECTION FROM FREEZING
7.2.1 Where there is the likelyhood of freezing, hot and
cold water supply systems shall be protected in the
following manner:
(a) Piping outisde of the building's thermal envelope
shall be insulated.
(b) Piping buried in the ground shall be insulated or
installed below a affected by freezing.
(c) Storage water heater vent pipes shall be insulated
Ground Floor Plumbing Plan 1:100
WATER SUPPLIES TO GS12/AS1
Firm Name Notes Job Title Design Pat Coll Client Name Scale
NOTES
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
KITCHEN WASTE PROVIDE 50MM DIA TO SINKS AND DISHWASHER ALL
WITH MIN 1 IN 40 GRADIENT
40w/AAV
LAUNDRY WASTE PROVIDE 50MM DIA TO WASHING MACHINE, AND TUB
ALL WITH MIN 1 IN 40 GRADIENT 28
WATER SUPPLY
20MM Ø MDPE COLD WATER PIPE REQUIREMENTS FOR PROTECTION FROM FREEZING
HOT WATER (10MM MIN. PIPE TO ALL FIXTURES) PIPES TO BE LAGGED TO PREVENT FREEZING
Firm Name Notes Job Title Design Pat Coll Client Name Scale
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
Existing Roof Plan 1:100
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Notes
4 Enclosure
4.02.04 Metal Roofing
Metalcraft corrugated (or simular equal product confirm
with designer at time of construction) Colorsteel roofing
system on Thermakraft 215 building paper.
13
7 Services
7.10.07 Vents
Ventilation system as per Thompson refrigeration
documents. Level under soaker corrugate flashings as 15°
detailed. 4.02.04 Metal Roofing
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
7.10.08 Ducting
Contractor to provide suitability structural / weather tight
compliant bracing system of ducting above roof line. PS3
to be provided upon completion.
Gutter
31
7.10.07 Vents
Chase Apron
7.10.08 Ducting
Apron
Chase Apron
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Pitch: 5/15o
Cladding: As indicated by keynotes.
Roof Underlay: Thermakraft 215, breather type roof underlay.
Purlins: 75x45 SG8 H1.2 purlins at 900mm crs.
(Ensure 600mm to ends)
Framing: Approved Truss at 900crs by others.
Refer to manufacturer's specifications.
Downpipes: 2 x 80mmØ downpipes added
Catchment Area: 20m2 new
Notes
3 Structure
3.02.01 Rafters
190x45mm Rafters as per attached engineers design.
4 Enclosure
4.02.04 Metal Roofing
Metalcraft corrugated (or simular equal product confirm
with designer at time of construction) Colorsteel roofing
system on Thermakraft 215 building paper.
4.03.10 Downpipes
Ø80mm paintined PVC downpipes with brackets @800mm
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
ctrs. Bend Downpipe to return to required set-off from
wall to match existing Downpipes.
4.03.10 Downpipes
3.02.01 Rafters
3.02.01 Rafters
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Bathroom
Eatery
1 4-1 Heat Vent light
Lobby
Bed 1
WC
2 Interior Surface LED Light 7.10.03 Extract Fan
Bed 2
1 Interior Surface LED Light
Bed 3
1 Interior Surface LED Light
Store
Dining Courtyard
Kitchen
1 Interior Surface LED Light
Eatery
8 Interior Surface LED Light
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
Hall
4 Interior Surface LED Light Store Passage
Passage
Kitchen 7.10.06 Light
6 Interior Surface LED Light
Extraction
Laundry 7.02.22 Rangehood
Make Up
1 4-1 Heat Vent light
Linen WC Kitchen
Stair Well
1 Interior Surface LED Light
7.10.03 Extract Fan
Living
2 Interior Surface LED Light
Lobby Notes
2 Interior Surface LED Light
7 Services
Passage
3 Interior Surface LED Light 7.02.22 Rangehood
Rangehood as per Thompson Refrigeration's attached
Stair Well documentation. Bakery
Firm Name Notes Job Title Design Pat Coll Client Name Scale
7 Services
1 Fire Alarm Panel 7.10.03 Extract Fan
Access WC Provide in-line extraction fans to all Cooking extract,
bathrooms, ensuites and WC's. Fans to be switched when
1 4-1 Heat Vent light
light is activated. Install as manrose 150mm mechcanical
Bakery ventilation. to be vented to external of building as shown on
11 Interior Surface LED Light plans.
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
Hall
4 Interior Surface LED Light
7.10.07 Vents
Kitchen
Kitchen
6 Interior Surface LED Light Dining
Laundry Living
1 4-1 Heat Vent light
Linen
7.10.03 Extract Fan
1 Interior Surface LED Light
7.10.03 Extract Fan
Living
2 Interior Surface LED Light
WC
Lobby
Linen
2 Interior Surface LED Light 22 Bathroom
Passage
Laundry Store Wardrobe
3 Interior Surface LED Light 7.10.06 Light
Stair Well Hall
2 Interior Surface LED Light
Store 7.10.03 Extract Fan
W/r
Firm Name Notes Job Title Design Pat Coll Client Name Scale
3 Structure
3.01.21 Fire Rated Ceiling
-/60/60 rated firewall. Installed as GBUC60. Detail
included in drawing set. Area shown by red fill. As specifed
by attached engineers documents.
3.04.01 Existing concrete slab
Existing concrete slab achieves 60min fire rating.
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
3.04.01 Existing concrete slab
Firm Name Notes Job Title Design Pat Coll Client Name Scale
3 Structure
3.01.19 Firewall
60/60/60 rated firewall. Installed as JHETGR60-N. Detail
included in drawing set. Specifed as per attached
engineers documents.
3.01.20 Fire Rated Ceiling
60/-/- ceiling (structural fire rating only) to support
Boundary Firewall (2-layer of 13 mm GIB Fyreline fixed in
accordance with GIB GBUC60 specification)
3.01.22 Fyreline GIB
2/13mm layers of Fyreline GIB fixed to cavity battons
against existing double brick wall. To act as GBUW GIB
firewall. as specified by attached engineers documents.
5 Interior
5.01.05 Timber Strapping
45x20mm H1.2 strapping on DPC to existing brick wall.
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
3.01.19 Firewall
3.01.19 Firewall
Firm Name Notes Job Title Design Pat Coll Client Name Scale
3.02.30 Ramp
ACCESSIBLE SIGNAGE TO BE
CLEARLY DISPLAYED AS PER
NZS4142:2001 FIG 3 & FIG 5
90 1,300 90
90
90 1,200
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
1,200
ACCESSIBLE SIGNAGE TO BE
CLEARLY DISPLAYED AS PER
NZS4142:2001 FIG 3 & FIG 5
Site Image Accessible Layout 1:250 Accessible Ground Floor Plan 1:150
Firm Name Notes Job Title Design Pat Coll Client Name Scale
3,000
3.03.10 Structural Elements Stairwell Bed 3 W/R Bed 2 Bed 1
4 Enclosure
4.09.02 Aluminium Joinery
Powder coated aluminium joinery, with paint finished
Bakery
planted timber reveals and timber architraves. Double
glazing to joinery throughout except single glazing to
garage area. Refer to window and door schedule for types.
4.10.03 R3.6 Ceiling Insulation
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
R3.6 Pink Batts ceiling insulation (180mm) installed as per
manufacturers specification.
Existing Foundation
4.12.07 Glazing
All glazing to comply with NZBC F2/AS1 inconjunction with
NZS 4223: Part 3 2016 Cross Section A 1:100
5 Interior
5.01.01 10mm Gib Wall Lining 7.10.07 Vents 3.01.04 Internal Walls 3.0m max
10mm Gib wall lining vertically fixed & stopped to level 4
finish for selected paint system - square stop to ceiling
junction.
5.01.03 13mm Gib Ceiling Lining
13mm Gib board ceiling lining fixed to rondo ceiling battens 5.01.01 10mm Gib Wall Lining
@600crs and stopped to Level 4 paint finish. To be sealed 5.01.03 13mm Gib Ceiling Lining
and coated with two layers of waterproof enamel paint. Bedroom 2 Hall Linen Kitchen
7 Services
7.10.07 Vents
Ventilation system as per Thompson refrigeration
Existing floor structure to be upgraded as per engineers drawings
documents. Level under soaker corrugate flashings as
detailed. Suspended Ceiling Suspended Ceiling
Range
Hood
Bakery Eatery
Servery Store Kitchen
Compound
Existing Foundation
Firm Name Notes Job Title Design Pat Coll Client Name Scale
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
3.02.21 Rondo Ceiling @600 crs 4.10.07 R3.2 Skillion Batts
GIB Rondo 310 ceiling batten system at 600mm ctrs 3.01.01 External Walls 90mm
maximum. Instealled as per manufacture instructions. 3.01.22 Fyreline GIB
970 2,475 3,020
5.01.05 Timber Strapping
Restraints as per truss design when using Rondo systems.
10
3.03.22 Floor Joists
140x45 SG8 H1.2 joists @ 400mm crs as per attached
engineers documents. 3.01.02 External Walls 140mm
3.03.22 Floor Joists
3.03.24 Stairs
Main private stairway as per D1/AS1. Max rise of 190mm
and tread. measurements as show on plan. Stair 3.03.22 Floor Joists
construction desribed by attached engineers documents
280
4 Enclosure
180
4.02.04 Metal Roofing
1,802
1,000 max
4,145
planted timber reveals and timber architraves. Double 280
glazing to joinery throughout except single glazing to
180
2,343
R3.2 skillion roof Pink Batt insulation (115mm) installed as
per manufacturers specification.
4.11.02 Roof Underlay
Thermakraft 215, breather type building wrap. Self-
supporting when run horizontally at pitches 3° and
greater. Up to Very high wind only (for higher wind zones 33°
use Thermakraft 401)
970 3,360 2,007
Existing Foundation
4.12.07 Glazing
Existing Foundation
All glazing to comply with NZBC F2/AS1 inconjunction with
NZS 4223: Part 3 2016 Stair Cross Section 1:50 Stair Cross Section 1:50
Firm Name Notes Job Title Design Pat Coll Client Name Scale
1:100
Number of storeys High risk 2
Roof/wall intersection design High risk 3
Eaves width Very high risk 5
Envelope complexity Medium risk 1
Deck design Low risk 0
Total Risk Score: 11
Notes
4.09.02
4 Enclosure 4.12.07
North Elevation
Metalcraft corrugated (or simular equal product confirm Existing Building
with designer at time of construction) Colorsteel roofing
system on Thermakraft 215 building paper.
4.03.10 Downpipes
Ø80mm paintined PVC downpipes with brackets @800mm
ctrs. Bend Downpipe to return to required set-off from
wall to match existing Downpipes.
4.08.25 Hardieflex
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
James Hardie Hardieflex sheet cavity fixed to timber
framing. External and internal corners to have
09 Colorsteel 09
MAXX flashing behind, refer details.
4.09.02 Aluminium Joinery
Powder coated aluminium joinery, with paint finished
planted timber reveals and timber architraves. Double
glazing to joinery throughout except single glazing to
garage area. Refer to window and door schedule for types.
4.12.07 Glazing
All glazing to comply with NZBC F2/AS1 inconjunction with
NZS 4223: Part 3 2016
7 Services
1:100
7.02.23 Gas Califont
Rinnai INFINITY® EF250 External installed as per
manufactures instructions.
7.10.07 Vents
Ventilation system as per Thompson refrigeration
documents. Level under soaker corrugate flashings as 4.08.25
detailed.
09
7.10.07
East Elevation
4.02.04
4.03.10
7.02.23
Firm Name Notes Job Title Design Pat Coll Client Name Scale
1:100
Roof/wall intersection design High risk 3
Eaves width Very high risk 5
Envelope complexity Medium risk 1
Deck design Low risk 0
Total Risk Score: 11
4.02.04
Notes
4.03.10
4.09.02 4.12.08 4.08.25
4 Enclosure 4.12.07
South Elevation
Metalcraft corrugated (or simular equal product confirm
with designer at time of construction) Colorsteel roofing
system on Thermakraft 215 building paper.
4.03.10 Downpipes
Ø80mm paintined PVC downpipes with brackets @800mm
ctrs. Bend Downpipe to return to required set-off from
wall to match existing Downpipes.
4.08.25 Hardieflex 4.12.08
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
James Hardie Hardieflex sheet cavity fixed to timber 7.02.24
framing. External and internal corners to have Colorsteel 09 Compound
MAXX flashing behind, refer details.
4.09.02 Aluminium Joinery
Powder coated aluminium joinery, with paint finished
planted timber reveals and timber architraves. Double
glazing to joinery throughout except single glazing to
garage area. Refer to window and door schedule for types.
4.12.07 Glazing
All glazing to comply with NZBC F2/AS1 inconjunction with
NZS 4223: Part 3 2016
1:100
4.12.08 Safety Glass
Grade A safety glass to all showers & overhead glazing, All
glazing to comply with N.Z.S 422301:2016. Refer to window
and door schedule for glass selections.
7 Services
7.02.24 Gas Bottles
4/45l gas bottles on concrete or tile pad secured to wall.
Gas systems to be installed as exempt work by an
approved installer and required certificates to be provided
at installation time. Gas bottle valves to be protected from 09
weather by suitable permanent Weather proof cover.
West Elevation
7.10.07 Vents
Ventilation system as per Thompson refrigeration
documents. Level under soaker corrugate flashings as
detailed.
Firm Name Notes Job Title Design Pat Coll Client Name Scale
A401
Drawing Number
Scale
EAVE FLASHING REQUIRED WHEN * T-RIB
MIN. ROOF PITCH = 3°
- ROOF PITCH ≤ 10°, OR
15.00°
- SOFFIT WIDTH ≤ 100mm, OR
- WIND ZONES = VERY HIGH OR EXTRA HIGH OR
- ENGINEER SPECIFIC DESIGN mm
125
MIN.
m
50m
MIN.
D
UIRE
S REQ
OR A
METALCRAFT
Rooney Group
CORRUGATED
ROOFING
Roof Details
BUILDING PAPER SHOWN
DASHED
Drawing Title
Client Name
MIN. 35mm
OVERLAP
TIMBER PURLIN
Pat Coll
####
DL20007
28/07/2020
Tim Mayo
QUARTER ROUND GUTTER
STST OR GALV. FLAT HEAD NAIL FOR
FLASHING
QUARTER ROUND GUTTER
INTERNAL BRACKET PRE-FINISHED SELF
DRILLING/TAPPING SCREW WITH
RUBBER WASHER
PRE-FINISHED 8g WAFER-TEK
Project Number
SCREW TIMBER PACKER
Print Date
FASCIA BOARD
Checked
Design
Drawn
ROOF FRAMING
TIMBER PACKER
SPECIFIED CLADDING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLE * - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS
ROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 AND MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.
MRM CODE OF PRACTICE VERSION 2.2 /2012.
FLUSH EAVE WITH INTERNAL GUTTER BRACKET
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM code
T-Rib RESIDENTIAL ROOFING
of practice version 2.2 /2012, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the
09 / 24
responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a
m
50m
MIN.
D
UIRE
S REQ
OR A
METALCRAFT
Job Title
CORRUGATED
ROOFING
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
Copyright remains the property of Draftline Ltd unless specified in writing
MIN. 35mm
OVERLAP
TIMBER PURLIN
QUARTER ROUND GUTTER
All dimensions are in millimetres unless otherwise stated
RUBBER WASHER
PRE-FINISHED 8g WAFER-TEK
SCREW TIMBER PACKER
ROOF FRAMING
TIMBER PACKER
standards alike
SPECIFIED CLADDING
Notes
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLE * - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS
ROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 AND MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.
MRM CODE OF PRACTICE VERSION 2.2 /2012.
FLUSH EAVE WITH EXTERNAL GUTTER BRACKET
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM code
T-Rib RESIDENTIAL ROOFING
of practice version 2.2 /2012, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the
10 / 24
responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a
single line for simplicity and is indicative only. Building paper type and method of installation should comply Reference RRTRI Date 2014 Scale 1:2 Sheet
DESIGN & DRAUGHTING SERVICES
PROPERTY MANAGEMENT
PROPERTY INSPECTION
A402
Drawing Number
Scale
CATEGORY A CATEGORY B
1. NORMAL EXPOSURE 1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.
SPECIFIED CLADDING 2. ROOF PITCH >10° 2. ROOF PITCH <10°
G 25mm 25mm
BUILDING PAPER OVER N MIN. 50mm + HEM OR 75mm MIN. 75mm + HEM OR 100mm
(VERTICALLY UP FACE - SMOOTH) (VERTICALLY UP FACE - SMOOTH)
FLASHING SHOWN DASHED MIN. 75mm + HEM OR 100mm MIN. 100mm + HEM OR 125mm
(VERTICALLY UP FACE - PROFILED) (VERTICALLY UP FACE - PROFILED)
PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2/2012 FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
Rooney Group
PVC CAVITY CLOSER SITUATION 1 SITUATION 2 SITUATION 3
Roof Details
1. LOW, MEDIUM, HIGH WIND ZONES 1. VERY HIGH WIND ZONE 1. EXTRA HIGH WIND ZONE
2. ROOF PITCH ≥ 10° 2. ALL ROOF PITCHES 2. ALL ROOF PITCHES
STST OR GALV. FLAT HEAD G MIN. 35mm MIN. 35mm MIN. 35mm
N = 50mm min
NAIL FOR FLASHING
N MIN. 75mm MIN. 75mm MIN. 75mm
Drawing Title
Client Name
L MIN. 130mm MIN. 200mm MIN. 200mm
(EXCLUDDING ANY SOFT EDGE OR (EXCLUDDING ANY SOFT EDGE OR
TURN-DOWN TO ROOFING) TURN-DOWN TO ROOFING)
Pat Coll
####
DL20007
28/07/2020
Tim Mayo
L=1
50m
mm
in * T-RIB
MIN. ROOF PITCH = 3°
NOG FOR FIXING APRON
15.00°
FLASHING
Project Number
DRILLING/TAPPING SCREW WITH
RUBBER WASHER METALCRAFT T-RIB ROOFING
Print Date
Checked
PURLIN
Design
Drawn
BUILDING PAPER SHOWN DASHED
WALL FRAMING
ROOF FRAMING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLE * - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS
ROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 AND MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.
MRM CODE OF PRACTICE VERSION 2.2 /2012.
TRANSVERSE APRON
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM code
T-Rib RESIDENTIAL ROOFING
of practice version 2.2 /2012, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is the
14 / 24
responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as a
Job Title
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
Copyright remains the property of Draftline Ltd unless specified in writing
Email pat.coll@draftline.co.nz
10 Beswick Street Timaru
PATRICK COLL NZCD Arch
9.4.2.5
Sheetmetal Flashings on Corrugated Profiles
9.4.2.5A Level Over-Flashing: Corrugate
Soft edge
apron
Fall
100mm
150mm
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
Fit overflashing
continuous to
ridge
Fall
250mm
30
Do not penetrate back
of cricket with roof
fasteners
Trim sheet to form overlap each
side of the soaker
9.4
NZ Metal Roof And Wall Cladding Code Of Practice v3.0 232 © New Zealand Metal Roofing Manufacturers Inc 2019
This is a controlled document. This copy of the Code Of Practice was issued 1 June 2020, and the next issue is due 1 September 2020.
The Online version of this document is the most up-to-date and in the case of conflict the Online version prevails over any saved or printed version.
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Copyright remains the property of Draftline Ltd unless specified in writing
DESIGN & DRAUGHTING SERVICES All dimensions are in millimetres unless otherwise stated Drawn Tim Mayo Rooney Group
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
56 Queen Street Waimate
PROPERTY MANAGEMENT
PROPERTY INSPECTION
Checked #### Drawing Number
PATRICK COLL NZCD Arch standards alike Drawing Title
A403
10 Beswick Street Timaru
Refer to specifications for timber strength
Ph/Fax 03 688 8455
Cell 0274 370 280
Proposed Building Conversion Project Number DL20007
Roof Details
Email pat.coll@draftline.co.nz ALL DIMENSIONS TO BE VERIFIED ON SITE Print Date 28/07/2020
RevID ChID Revision Date
Notes 4 Enclosure 4.08.25 Hardieflex Polsulphide sealant to seal chase. 01 12 RFI 12 - Junction Detail 28/07/2020
James Hardie Hardieflex sheet cavity fixed to timber
4.02.04 Metal Roofing 4.13.03 Chase Apron flashing
3 Structure framing. External and internal corners to have Colorsteel
Metalcraft corrugated (or simular equal product confirm 2 piece pre finished chase apron flashing
MAXX flashing behind, refer details.
3.01.02 External Walls 140mm with designer at time of construction) Colorsteel roofing
Generally construct with 140x45 SG8 H1.2 framing with system on Thermakraft 215 building paper. 4.10.02 R2.8 Wall Insulation
studs @ 600mm crs to NZS3604:2011. Dwang at 800crs R2.8 Pink Batts wall insulation (90mm) installed as per 5 Interior
except for vertical cedar type claddings dwang at 480crs. 4.04.03 Apron Flashing manufacturers specification.
0.55 BMT Colorsteel apron flashing as detailed fully 5.01.01 10mm Gib Wall Lining
Dwang for all fittings, fixtures, linings, bracing panels & 10mm Gib wall lining vertically fixed & stopped to level 4
supported and installed in accordance with E2/AS1. Stop- 4.11.01 Building Wall Wrap
trims. DPC (malthoid) between bottom plate and conc. slab, finish for selected paint system - square stop to ceiling
end to all low-end terminations to direct water Thermakraft Watergate PLUS wall wrap fixed to exterior
3.02.18 Purlins mechanically out from cladding. Separate all metal from face of framing. Dressed into all openings and taped using junction.
75x45 SG8 H1.2 purlins at 900mm ctrs maximum fixed to timber with a layer of building wrap. the Thermakraft Aluband sealing system. Install to 5.01.14 Cavity Closer
rafters/truss, ensure 600mm to ends. manufacturers system and specification. Cavity Closer to suit 20mm cavity.
4.07.05 Existing Brick Walls
Existing external brick walls. 4.13.02 Selected Sealant
12
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
4.10.02 R2.8 Wall Insulation
20 20
3.01.02 External Walls 140mm
80° 80° 4.08.25 Hardieflex
4.13.02 Selected Sealant
10
10
5.01.01 10mm Gib Wall Lining
4.13.03 Chase Apron flahing 4.13.03 Chase Apron flashing
75
4.04.03 Apron Flashing
110
110
4.07.05 Existing Brick Walls 4.07.05 Existing Brick Walls 5.01.14 Cavity Closer
2 Corrugations
35
2 Corrugations
150
5
4.02.04 Metal Roofing 4.02.04 Metal Roofing 4.02.04 Metal Roofing
5
3.02.18 Purlins
Brick Chase Parallel Brick Flashing 1:5 Brick Chase Transverse Apron 1:5 Apron Hardiflex Parallel Apron Detail 1:5
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Figure 22: Cavity concrete foundation detail Figure 23: Cavity vertical uPVC joint
09
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
Figure 25: Cavity vertical sealant joint
28 HardieFlex™ Sheet Technical Specification October 2013 New Zealand HardieFlex™ Sheet Technical Specification October 2013 New Zealand 29
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Copyright remains the property of Draftline Ltd unless specified in writing
DESIGN & DRAUGHTING SERVICES All dimensions are in millimetres unless otherwise stated Drawn Tim Mayo Rooney Group
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
56 Queen Street Waimate
PROPERTY MANAGEMENT
PROPERTY INSPECTION
Checked #### Drawing Number
PATRICK COLL NZCD Arch standards alike Drawing Title
A405
10 Beswick Street Timaru
Refer to specifications for timber strength
Ph/Fax 03 688 8455
Cell 0274 370 280
Proposed Building Conversion Project Number DL20007
Hardiflex Detail
Email pat.coll@draftline.co.nz ALL DIMENSIONS TO BE VERIFIED ON SITE Print Date 28/07/2020
RevID ChID Revision Date
01 09 RFI 9 - Cladding Details 28/07/2020
Figure 26: Cavity internal uPVC corner joint Figure 33: Cavity horizontal control joint
09
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
Figure 27: Cavity external uPVC corner joint
30 HardieFlex™ Sheet Technical Specification October 2013 New Zealand 34 HardieFlex™ Sheet Technical Specification October 2013 New Zealand
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Copyright remains the property of Draftline Ltd unless specified in writing
DESIGN & DRAUGHTING SERVICES All dimensions are in millimetres unless otherwise stated Drawn Tim Mayo Rooney Group
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
56 Queen Street Waimate
PROPERTY MANAGEMENT
PROPERTY INSPECTION
Checked #### Drawing Number
PATRICK COLL NZCD Arch standards alike Drawing Title
A406
10 Beswick Street Timaru
Refer to specifications for timber strength
Ph/Fax 03 688 8455
Cell 0274 370 280
Proposed Building Conversion Project Number DL20007
Hardiflex Detail
Email pat.coll@draftline.co.nz ALL DIMENSIONS TO BE VERIFIED ON SITE Print Date 28/07/2020
RevID ChID Revision Date
01 09 RFI 9 - Cladding Details 28/07/2020
Figure 34: Cavity corner to ‘h’ mould joint Figure 36: Cavity window head
09
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
Figure 35: Cavity window sill Figure 37: Cavity window jamb
HardieFlex™ Sheet Technical Specification October 2013 New Zealand 35 36 HardieFlex™ Sheet Technical Specification October 2013 New Zealand
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Copyright remains the property of Draftline Ltd unless specified in writing
DESIGN & DRAUGHTING SERVICES All dimensions are in millimetres unless otherwise stated Drawn Tim Mayo Rooney Group
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
56 Queen Street Waimate
PROPERTY MANAGEMENT
PROPERTY INSPECTION
Checked #### Drawing Number
PATRICK COLL NZCD Arch standards alike Drawing Title
A407
10 Beswick Street Timaru
Refer to specifications for timber strength
Ph/Fax 03 688 8455
Cell 0274 370 280
Proposed Building Conversion Project Number DL20007
Hardiflex Detail
Email pat.coll@draftline.co.nz ALL DIMENSIONS TO BE VERIFIED ON SITE Print Date 28/07/2020
RevID ChID Revision Date
01 12 RFI 12 - Junction Detail 28/07/2020
12
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
Timber cavity batten as per E2/AS1
Approved sealant
Existing double brick wall
Firm Name Notes Job Title Design Pat Coll Client Name Scale
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
Amend 5
Aug 2011
Amend 5
Aug 2011
COMMENT:
Where possible, pipe penetrations, meterboxes and
Amend 5
Aug 2011 similar penetrations should be located in sheltered areas
of the building, such as a porch, or be installed behind a
weatherproof glazed panel.
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Copyright remains the property of Draftline Ltd unless specified in writing
DESIGN & DRAUGHTING SERVICES All dimensions are in millimetres unless otherwise stated Drawn Tim Mayo Rooney Group
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
56 Queen Street Waimate
PROPERTY MANAGEMENT
PROPERTY INSPECTION
Checked #### Drawing Number
PATRICK COLL NZCD Arch standards alike Drawing Title
A409
10 Beswick Street Timaru
Refer to specifications for timber strength
Ph/Fax 03 688 8455
Cell 0274 370 280
Proposed Building Conversion Project Number DL20007
Wall Penetration Detail
Email pat.coll@draftline.co.nz ALL DIMENSIONS TO BE VERIFIED ON SITE Print Date 28/07/2020
RevID ChID Revision Date
01 17 RFI 17 - Window Schedule 28/07/2020
01/2017
LINTEL FIXING OPTIONS
TYPE E TYPE F
1.4kN 4.0kN
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
1.5 4.0 E F F G G E E F F G
DEFINITIONS 5.0 F F G G H E E F G G
OR Plate Fixing Schedule.
6 x 90mm x 3.15 dia. nails 6 x 90mm x 3.15 dia. nails
6.0 F F G H H E E F G H
Lintel span dimension point 200mm Sheet Brace Lintel Lintel
2.0 E F F F G E E F F F Strap to one side Tylok 10T10
Top plate 3.0 E F F G G E E F F G 2 x 90mm x 3.15 dia. nails to one side Stud numbers
directly below lintel (typical) 6 x 30mm x 3.15 dia. nails 60mm (Two rows of teeth indicative only.
2.0 4.0 F F G G H E E F G G into understud)
each end
5.0 F F G H H E E F G H Refer Table 8.5
Lintel
drop
3.0 F F G G H E E F G G OR OR OR OR
2.4 4.0 F F G H H E E F G H
depth
Lintel
Lintel
2 x Tylok 2T4 ®
GIB HandiBrac
TM
Trimmer studs 5.0 F G G H H E F G H H 2 x 200mm Sheet to both sides 400mm Sheet Brace
Brace Strap to one
(Number of studs 6.0 F G H H - E F G H H side 3 x 30mm x
for Radiata Pine Strap to one side
2 x Strap Nail 6 x 30mm x 3.15 dia. nails to stud
indicative only) 2.0 E F F G G E E F F G Max. 100mm 3.15 dia. nails to
Jack stud (typical) each stud
to both sides
3 x 30mm x 3.15 dia. nails to
3.0 F F G H H E E F G H for Douglas Fir
bottom plate
Doubling or understud 3.0 4.0 F G G H H E F G H H
Sill or Header 5.0 F G H H - E F G H H
6.0 F G H - - E F G H - Min. 75mm 6kN Stud Anchor 3 x 30mm x 6 x 30mm x 3.15 dia. nails to timber
trimmer into concrete (CPC80) 3.15 dia. nails joist/bearer
2.0 F F G G H E E F G G floor into bottom plate Proprietary screw bolt
3.0 F F G H H E F G G H
BOWMAC Screw Bolt M10 x 140mm with 50 x 50 x 3mm square washer into concrete floor or timber joist/bearer
height
3.6 4.0 F G H H - E F G H H
Sill
5.0 F G H - - E F G H -
6.0 G H H - - E F H - -
Bottom plate Jack stud 2.0 F F G G H E E F G G
3.0 F G H H - E F G H H
4.2 4.0 F G H - - E F G H - TYPE H For fixing of jack studs
Lintel Supporting Girder Trusses 5.0 G H H - - E F H - - 13.5kN to lintel & top plate,
refer to Stud to Top
Roof Tributary Light Roof Heavy Roof 6.0 G H - - - E F H - - OR Plate Fixing Schedule.
Area 2.0 F F G H H E E F G H
Wind Zone Wind Zone 8 x 90mm x 3.15 dia. nails
3.0 F G H H - E F G H H 8 x 90mm x 3.15 dia. nails
3.4 F G H H - E F G H H Lintel Lintel
L, M, VH EH L, M, VH EH 4.5
4.0 F G H - - E F G H - 200mm Sheet Brace Tylok 10T10 to Stud numbers
H H 5.0 G H - - - E F H - - Strap to both sides 6 x 30mm x 3.15 dia. nails both sides 60mm (Two rows of teeth
each end of each strap into understud) indicative only.
8.6m2 G G H G G H 6.0 G H - - - E F H - - Refer Table 8.5
2.0 F F G H H E E F G H NZS 3604:2011
11.6m2 G H H G G H 3.0 F G H H - E F G H H
12.1m2 G H H G H H 3.2 F G H H - E F G H H OR OR OR
4.8 90mm x 3.15 dia. nails
4.0 F G H - - E F H H - @ 250mm crs. both GIB® HandiBracTM 2 x 400mm Sheet Brace
15.3m 2
H H - G H H 5.0 G H - - - E F H - - sides (typical) 6 x 30mm x 3.15 dia. nails Strap to one side
6.0 G H - - - E F H - - to each side of stud 6 x 30mm x 3.15 dia. nails
19.1m2 H - - G H - Max. 100mm 2 x Tylok 2T4 each end to stud
2.0 F F G H H E F G G H (typical) both sides
20.9m2 H - - H H - 3.0 F G H H - E F G H H 3 x 30mm x 3.15 dia. nails 3 x 30mm x 3.15 dia. nails
to each side of bottom plate to bottom plate
3.5 F G H - - E F G H -
21.8m2 H - - H - - 5.1
4.0 G G H - - E F H H -
Min. 75mm into 2 x 6kN Stud Anchor 400mm Sheet Brace 6 x 30mm x 3.15 dia. nails
34.3m2 - - - H - - 5.0 G H - - - E F H - - concrete floor (CPC80) Strap wrap around bottom each end to timber
6.0 G H - - - E G H - - (typical) plate and up the other side Proprietary screw bolt joist/bearer
NOTES: 2.0 F F G H H E F G G H
BOWMAC Screw Bolt M10 x 140mm with 50 x 50 x 3mm square washer into concrete floor or timber joist/bearer
1. Roof Tributary Area = approx. 1/2 x (Total roof area on girder and rafter 2.8 F G H H - E F G H H
trusses supported by lintel) 3.0 F G H - - E F G H -
2. Assumed girder truss is at mid-span or middle third span of lintel 5.4
4.0 G H H - - E F H - -
3. Use similar fixings for both ends of lintel 5.0 G H - - - E F H - -
4. All other cases require specific engineering design 6.0 G H - - - E G H - -
Firm Name Notes Job Title Design Pat Coll Client Name Scale
07/2011
1 BLUE SCREW
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
CPC40
FIXING DEFINITIONS
NAIL = Either 90mm x 3.15 dia. power-driven nail CT200 = LUMBERLOK Ceiling Tie CT200 bend over purlin,
or 100mm x 3.75 dia. hand-driven nail 4 x LUMBERLOK Product Nails 30mm x 3.15 dia.
each end
BLUE SCREW = 80mm x 10 gauge LUMBERLOK BLUE
SCREW CPC40 = L
UMBERLOK CPC40 with 2 x Type 17 - 14g x
35mm Hex Head Screws per flange
WIRE DOG = LUMBERLOK WIRE DOG either LH or RH
FOR
SCAN FOR
10. ROOF FRAMING
INSTALLATION
INSTALLATIONINSTALLATION
VIDEO VIDEO
VIDEO
https://vimeo.com/117353340
https://vimeo.com/117353340
https://vimeo.com/117353340
© Copyright 2017 MiTek Holdings, Inc. © Copyright 2017 MiTek Holdings, Inc.
111 All rights reserved. 112 All rights reserved.
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Copyright remains the property of Draftline Ltd unless specified in writing
DESIGN & DRAUGHTING SERVICES All dimensions are in millimetres unless otherwise stated Drawn Tim Mayo Rooney Group
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
56 Queen Street Waimate
PROPERTY MANAGEMENT
PROPERTY INSPECTION
Checked #### Drawing Number
PATRICK COLL NZCD Arch standards alike Drawing Title
A411
10 Beswick Street Timaru
Refer to specifications for timber strength
Ph/Fax 03 688 8455
Cell 0274 370 280
Proposed Building Conversion Project Number DL20007
LUMBERLOK Details
Email pat.coll@draftline.co.nz ALL DIMENSIONS TO BE VERIFIED ON SITE Print Date 28/07/2020
RevID ChID Revision Date
01 28/07/2020
11/2017
Stud Stud
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
O/H Supported Internal load bearing wall
O/H Supported Span
Span
External wall with EXTERNAL WALL External wall with
Standard truss LOADED DIMENSION = Internal load bearing wall
SUPPORTED SPAN + O/H
2 Girder truss
Jack truss
Ridge beam
Available in 2 lengths allowing for connections from stud to single top plate
(SL125) and stud to double top plates (SL170) FIXING SELECTION CHART
Applied in the factory (Suitable for walls supporting roof members at 600, 900 or 1200mm crs.)
Is a completely internal connection avoiding any clashes with wall linings Wind Zones L, M, H, VH, EH as per NZS 3604:2011
Loaded Dimension (m) Light Roof Heavy Roof
Stud Centres
300mm 400mm 600mm L
Wind Zone
M H VH EH L
Wind Zone
M H VH EH
2N = 2/ 90mm x 3.15 dia. nails
3.0 2.3 1.5 2N 2N SL SL SL 2N 2N SL SL SL
Single STUD-LOK
4.0 3.0 2.0 2N 2N SL SL SL 2N 2N SL SL SL SL = plus 2/ 90mm x 3.15 dia. nails
5.0 3.8 2.5 2N SL SL SL SL 2N 2N SL SL SL
6.0 4.5 3.0 2N SL SL SL SL 2N 2N SL SL SL
7.0 5.3 3.5 2N SL SL SL SL 2N 2N SL SL SL NOTE:
8.0 6.0 4.0 2N SL SL SL SL 2N 2N SL SL SL To calculate the number of STUD-LOK fixings required,
9.0 6.8 4.5 SL SL SL SL SL 2N 2N SL SL SL
divide the wall length by the stud centres, add 1 to this
figure and locate this number of fixings as evenly as
10.0 7.5 5.0 SL SL SL SL SL 2N 2N SL SL SL
possible along the wall length. This figure includes the
11.0 8.3 5.5 SL SL SL SL SL 2N 2N SL SL SL
start and end studs in each wall length.
12.0 9.0 6.0 SL SL SL SL SL 2N 2N SL SL SL
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Copyright remains the property of Draftline Ltd unless specified in writing
DESIGN & DRAUGHTING SERVICES All dimensions are in millimetres unless otherwise stated Drawn Tim Mayo Rooney Group
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
56 Queen Street Waimate
PROPERTY MANAGEMENT
PROPERTY INSPECTION
Checked #### Drawing Number
PATRICK COLL NZCD Arch standards alike Drawing Title
A412
10 Beswick Street Timaru
Refer to specifications for timber strength
Ph/Fax 03 688 8455
Cell 0274 370 280
Proposed Building Conversion Project Number DL20007
LUMBERLOK Details
Email pat.coll@draftline.co.nz ALL DIMENSIONS TO BE VERIFIED ON SITE Print Date 28/07/2020
RevID ChID Revision Date
01 28/07/2020
09/2011
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
6kN Tylok 6T10 OR PLATE-LOK
3kN / 6kN
8.WALLS
6kN / 12kN
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Copyright remains the property of Draftline Ltd unless specified in writing
DESIGN & DRAUGHTING SERVICES All dimensions are in millimetres unless otherwise stated Drawn Tim Mayo Rooney Group
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
56 Queen Street Waimate
PROPERTY MANAGEMENT
PROPERTY INSPECTION
Checked #### Drawing Number
PATRICK COLL NZCD Arch standards alike Drawing Title
A413
10 Beswick Street Timaru
Refer to specifications for timber strength
Ph/Fax 03 688 8455
Cell 0274 370 280
Proposed Building Conversion Project Number DL20007
Supporting Details
Email pat.coll@draftline.co.nz ALL DIMENSIONS TO BE VERIFIED ON SITE Print Date 28/07/2020
RevID ChID Revision Date
01 28/07/2020
GIB AQUALINE ® WET AREA SYSTEMS – TYPICAL DETAILS GIB AQUALINE ® WET AREA SYSTEMS – TYPICAL DETAILS
A B A B
GIB Aqualine®
GAW-D014
GAW-D027
GAW-D028
GAW-D013
GIB Aqualine® GIB Aqualine®
GIB Aqualine®
Acrylic liner
over unsealed
GIB Aqualine® Silicone sealant
Silicone sealant or
tile edge bead
Acrylic liner Waterproof membrane
over unsealed Tap body recommended prior to tiling
GIB Aqualine® Waterproof membrane
Ceramic tiles recommended prior
Silicone sealant to tiling
5-10mm
5-10mm
Silicone sealant Ceramic tiles
Nogging
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
D
Silicone sealant
required – see bath
GAW-D016
manufacturer details
C D GIB Aqualine®
GIB Aqualine® C GIB Aqualine®
GIB Aqualine® “Good practice”
GAW-D029
GAW-D030
Impervious sheet
GAW-D015
Ceramic tiles material or waterproof
membrane
Silicone sealant
or edge jointer Waterproof membrane
required prior to tiling
E GIB Aqualine®
Silicone sealant
GAW-D017
Ceramic tiles
Silicone sealant
Vanity top
B
Silicone sealant C
between vanity
and wall E
A/B
GIB AQUALINE® WET AREA SYSTEMS
FOR FURTHER INFORMATION OR TO DOWNLOAD DETAILS VISIT WWW.GIB.CO.NZ 21 FOR FURTHER INFORMATION OR TO DOWNLOAD DETAILS VISIT WWW.GIB.CO.NZ 17
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Copyright remains the property of Draftline Ltd unless specified in writing
DESIGN & DRAUGHTING SERVICES All dimensions are in millimetres unless otherwise stated Drawn Tim Mayo Rooney Group
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
56 Queen Street Waimate
PROPERTY MANAGEMENT
PROPERTY INSPECTION
Checked #### Drawing Number
PATRICK COLL NZCD Arch standards alike Drawing Title
A414
10 Beswick Street Timaru
Refer to specifications for timber strength
Ph/Fax 03 688 8455
Cell 0274 370 280
Proposed Building Conversion Project Number DL20007
Wet Area Details (Acrylic)
Email pat.coll@draftline.co.nz ALL DIMENSIONS TO BE VERIFIED ON SITE Print Date 28/07/2020
RevID ChID Revision Date
01 28/07/2020
FRAMING method B1/VM1, paragraph 2.2.4. LINING The separation distance between the ceiling linings and any Inner layer 41mm x 6g GIB® 25mm x 6g GIB®
Timber framing to be in accordance Refer to Figure 1, 3, 4, 5 and 6 of the 13mm GIB Fyreline® installed as flooring or roofing material shall be 90mm minimum. Grabber® High Thread Grabber® Self Tapping
with NZS 3604 or in accordance with Fire and Acoustic Design Manual for specified below. Drywall Screws Drywall Screws
Linings shall be supported by framing members with a minimum
specific engineering design complying post fire stability design.
FIXING/JOINTING width of 35mm spaced at 600mm centres maximum. Outer layer 51mm x 7g GIB® 41mm x 6g GIB®
with AS/NZS 1170 and NZS 3603
CLADDING • 300mm centre around the sheet Grabber® High Thread Grabber® Self Tapping
standards. In respect of the FRR for this particular system, nogs are required Drywall Screws Drywall Screws
Non-combustible cladding as perimeter and intermediate studs.
only at the perimeter of the fire rated ceiling.
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
Minimum framing 90 x 45mm at per clause 5.8.1 of C/AS of the • Fixings to be 12mm from bound
600mm maximum centres with nogs/ NZBC fixed as per their technical sheet edges and 18mm from sheet If timber-framed construction applies, the nogs shall be Fastener centres (both layers)
dwangs at 800mm maximum centres. specification either on timber cavity ends. 70mm x 35mm minimum. Place fasteners 12mm from longitudinal sheet edges and
batten or direct fixed. 18mm from sheet ends. This distance may be reduced to
Timber framing treatment to be Fix with 41mm x 6g GIB® Grabber
CEILING LINING 12mm from sheet ends at butt joints on furring channels.
in accordance with the NZBC PRE-CLADDING High Thread Drywall Screws or
Acceptable Solution B2/AS1. 2 layers of 13mm GIB Fyreline ® shall be fixed at right angles to
6mm RAB Board. 40 x 2.8mm GIB® nails. Place fasteners at 200mm centres around the ceiling perimeter,
the underside of the framing members.
along each intermediate framing member and where sheet end
WALL HEIGHTS FIXING/JOINTING INSULATION
The joints of the second layer are offset 600mm from those in butt joints occur.
This fire rated system has been tested RAB Board fixed to all framing with James Hardie Mineral Insulation.
the first layer.
with a stud height of 3m maximum. fixings at 150mm centres maximum. Density - 60kg/m3.
WALL/CEILING JUNCTIONS
The fire rated walls built close to 90mm thick. All sheet end butt joints must occur over solid framing.
Joints taped as per James Hardie The internal angle between the ceiling and walls must be
boundary are also required to achieve
Rigid Air Barriers Installation Manual. Sheets shall be touch fitted. protected by GIB-Cove ® adhered with GIB-Cove ® Bond, or boxed
post fire stability in either direction in
corners (square stopped) filled and taped in accordance with the
accordance with the NZBC verification
publication entitled “GIB ® Site Guide”.
Timber Framing Outer layer: All fastener heads stopped and all sheet joints tape
reinforced and stopped in accordance with the publication entitled
“GIB® Site Guide”.
600mm
max
RAB Board
Timber or steel framing
For further information refer to the clauses in the Fire and Acoustic Design Manual.
OCTOBER 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO GIB® FIRE RATED SYSTEMS 73
Fire and Acoustic Design Manual August 2017 New Zealand 33
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Copyright remains the property of Draftline Ltd unless specified in writing
DESIGN & DRAUGHTING SERVICES All dimensions are in millimetres unless otherwise stated Drawn Tim Mayo Rooney Group
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
56 Queen Street Waimate
PROPERTY MANAGEMENT
PROPERTY INSPECTION
Checked #### Drawing Number
PATRICK COLL NZCD Arch standards alike Drawing Title
A415
10 Beswick Street Timaru
Refer to specifications for timber strength
Ph/Fax 03 688 8455
Cell 0274 370 280
Proposed Building Conversion Project Number DL20007
Fire Protection Details
Email pat.coll@draftline.co.nz ALL DIMENSIONS TO BE VERIFIED ON SITE Print Date 28/07/2020
RevID ChID Revision Date
01 28/07/2020
GBUW 60 FRR 60/60/60 Lining 2 layers 13mm GIB Fyreline® one side
LB/NLB Load bearing
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
LINING (FIRE SIDE)
Fastener centres
2 layers of 13mm GIB Fyreline® to one side of the frame.
Inner layer: 600mm centres up each stud.
Vertical or horizontal fixing permitted. For vertical fixing,
Outer layer: 300mm centres up each stud.
full height sheets shall be used where possible.
Place fasteners 12mm from longitudinal sheet edges and
Sheets shall be touch fitted.
18mm from sheet ends.
All sheet joints must be formed over framing, except for
Place fasteners at 200mm centres along sheet end butt joints.
longitudinal joints when the outer layer is fixed horizontally.
When sheet end butt joints are unavoidable, they shall be JOINTING
formed over framing. Inner layer: Unstopped.
Offset sheet joints between layers. Outer layer: All screw heads stopped and all sheet joints tape
In steel-framed options, linings are installed hard to floor. reinforced and stopped in accordance with the publication entitled
“GIB ® Site Guide”.
600mm
max
Any cladding system
18mm
Offset joints
between sheets
Screws at
300mm centres
up each stud
600mm
OCTOBER 2018 GIB ® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO GIB ® FIRE RATED SYSTEMS 49
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Copyright remains the property of Draftline Ltd unless specified in writing
DESIGN & DRAUGHTING SERVICES All dimensions are in millimetres unless otherwise stated Drawn Tim Mayo Rooney Group
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
56 Queen Street Waimate
PROPERTY MANAGEMENT
PROPERTY INSPECTION
Checked #### Drawing Number
PATRICK COLL NZCD Arch standards alike Drawing Title
A416
10 Beswick Street Timaru
Refer to specifications for timber strength
Ph/Fax 03 688 8455
Cell 0274 370 280
Proposed Building Conversion Project Number DL20007
Fire Protection Details
Email pat.coll@draftline.co.nz ALL DIMENSIONS TO BE VERIFIED ON SITE Print Date 28/07/2020
RevID ChID Revision Date
01 14 RFI 14 - Surface Finishes 28/07/2020
Notes
3 Structure
3.01.04 Internal Walls 3.0m max
Non Loadbearing generally construct with 90x45 SG8 H1.2
framing with studs @ 400mm crs to NZS3604:2011 Table.
Dwang at 800crs. Dwang for all fittings, fixtures, linings, 14
bracing panels & trims. DPC (malthoid) between bottom
plate and conc. slab.
150
5.01.12 Preperation Benchs 5.01.12 Preperation Benchs
316 Stainless Stell benctops to have seamless sink welded
into. All benchs are to be on SS adjustable legs which allow
benchs to be moved to allow cleaning of the floor and
walls.
5.01.13 Upstand
316 stainless stell upstand to be seamless welded into
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
bench tops.
Firm Name Notes Job Title Design Pat Coll Client Name Scale
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
Firm Name Notes JobJob Title Design #Designer Client Name Scale
Firm Name Notes Title Design Pat Coll Client Name Scale
Copyright
Copyright remains
remains
All dimensions
thethe property
property of Draftline
of Draftline LtdLtd unless
unless specified
specified in writing
in writing
Drawn TimTim
Mayo
Adrian
Rooney Tuffley
Group
DESIGN
DESIGN & DRAUGHTING
& DRAUGHTING SERVICES
SERVICES All dimensions areare in millimetres
in millimetres unless
unless otherwise
otherwise stated
stated Drawn Mayo Drawing Title
56395 Thames Highway Oamaru
PROPERTY MANAGEMENT
All construction
All construction to comply
to comply withwith NZBC/NZ
NZBC/NZ 3604:
3604: 2011,
2011, alongside
alongside all current
all current Drawing Number
Queen Street Waimate
PROPERTY MANAGEMENT
Checked
PROPERTY INSPECTION
PATRICK COLL
PROPERTY INSPECTION
NZCD Arch standards
standards alike
alike Checked #Checked
#### Drawing Title Drawing Number
A421
PATRICK COLL NZCD Arch
10 Beswick StreetTimaru
Refer to specificationsfor for timber strength
New Dwelling Project Number DL19379
DL20007 Gas Clearance Details A418
10 Beswick Street Timaru
Refer to specifications timber strength
Ph/Fax 03 688
Ph/Fax 03 688 8455
Cell 0274 370
Cell 0274 370 280
8455
280 Proposed Building Conversion Project Number
Gas Details
EmailEmail pat.coll@draftline.co.nz
pat.coll@draftline.co.nz ALL
ALL DIMENSIONS
DIMENSIONS TOTO
BEBE VERIFIED
VERIFIED ONON SITE
SITE Print Date
Print Date 14/05/2020
28/07/2020
RevID ChID Revision Date
01 26 RFI 26 - Accessible Tape 28/07/2020
TEMPERATURE / PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
WATER HEATER, F WATER HEATER, F EXPANSION CONTROL VALVE
RESTRAINT , 25X1MM GALV RESTRAINT , 25X1MM GALV
100MM MAXIMUM PIPE LENGTH
100
STRAP, STRAP TO BE STRAP, STRAP TO BE
TENSIONED WHEN FIXED IN TENSIONED WHEN FIXED IN (STRAIGHT OR BENT)
26
PLACE. STRAP FIXED TO PLACE. STRAP FIXED TO 25MM AIR GAP
WALLL FRAMING WITH 10G X WALLL FRAMING WITH 10G X
25
80MM COACH SCREW WITH 80MM COACH SCREW WITH
30X2MM WASHER 30X2MM WASHER TUNDISH
DRAIN DISCHARGE
PIPE TO KITCHEN SICK 15MM DIA, FLOW RATE 0.2 @ 60°C (HOT) 0.2 (COLD)
DETAIL A HOT WATER DELIVERY TO TEMPERATURE &
KITCHEN & LAUNDRY
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
PRESSURE
45X45MM CONTINUOUS 1M RELIEF VALVE & DRAIN
VERTICAL BLOCKING TO MIN
10
RESTRAINT ELEVATION
AIR
GAP
AIR GAP IN
EQUAL PRESSURE COLD WATER ACCORDANCE
COLD WITH FIG. 12
DELIVERY
45X45MM CONTINUOUS WATER
VERTICAL BLOCKING TO
EXTEND FULL HEIGHT
OF WATER HEATER, EXPANSION CONTROL STORAGE
FIXED TO WALL VALVE AND WATER
FRAMING WITH 100X3.75 RELIEF DRAIN HEATER
GALV. NAILS @ 600 CRS
Firm Name Notes Notes Job Title Job Title Design Client Name Client Name
DesignPat Coll Pat Coll Scale Scale
RAUGHTING SERVICES
Copyright remains the property
All dimensions are in millimetres
DESIGN & DRAUGHTING SERVICES
of Draftline
Copyright remainsLtdtheunless
unless otherwise
All dimensions
propertyspecified in writing
of Draftline Ltd unless specified in writing
stated unless otherwise stated
are in millimetres 19 Limeston Road Kakahu Drawn Drawn Tim Mayo EvanTim& Clare Rooney Group
Mayo Chapman
1:10 1:1
PROPERTY MANAGEMENT
All construction to complyAll
with NZBC/NZ to
construction 3604: 2011,
comply alongside
with NZBC/NZ all 3604:
current2011, alongside all current
Geraldine 56 Queen Street Waimate
PROPERTY MANAGEMENT
PROPERTY INSPECTION
Checked Drawing Number Drawing Number
Checked #### Drawing Title #### Drawing Title
PROPERTY INSPECTION
LL NZCD Arch PATRICK COLL standards
NZCD Arch alike standards alike
A419
reet Timaru
8 8455
280
10 Beswick Street
Refer
Ph/Fax 03 688 8455
Cell 0274 370 280
Timaru
to specifications forRefer
ALL DIMENSIONS TO
timbertostrength
specifications for timber strength
Proposed Building ConversionProject Number
Proposed Addition ProjectDL20063
Number
HWC DL20007
Details HWC Details A409
@draftline.co.nz Email pat.coll@draftline.co.nz ALLBE VERIFIED ON
DIMENSIONS TOSITE
BE VERIFIED ON SITE Print Date Print Date
16/06/2020 28/07/2020
RevID ChID Revision Date
NOTE Notes 7.02.11 Accessible Suitable Wall Basin 05 RFI 5 - Door Change
550mmx400mm Caroma concorde 500 wall basin 1th with
OWNER TO CONFIRM FINISHES 4 Enclosure caroma caravelle/comcourde shroud or similar. Fitted 01 21 RFI 21 - Bathroom Layour Details 28/07/2020
with caroma care plus basin mixer care handle H/C. Basin 26 RFI 26 - Accessible Tape
WET AREA ROOM FLOOR (BATH, LAUNDRY, KITCHEN 4.12.08 Safety Glass to comply with G1/AS1 & NZS4121:2001 accessible toilet
ETC) SLIP RESISTANCE TO COMPLY WITH 'D1/AS1 2.1 Grade A safety glass to all showers & overhead glazing, All standards.
TABLE'. glazing to comply with N.Z.S 422301:2016. Refer to window
and door schedule for glass selections. 7.02.12 Accessible and Mobility Toilet
WALLS PAINTED WITH SEMI GLOSS OR GLOSS FINISH Caroma Care 100 connector suite or similar accessible
OR ANY FINISH COVERED IN 'E3/AS1 3.1.2'. 10MM GIB
toilet pan to comply with G1/AS1 & NZS4121:2001
AQUALINE TO ALL BATHROOM WALLS & CEILINGS
7 Services
7.02.14 Towel and Soup Dispenser Zone
FOR TIMBER FRAMING AT THE TIME OF INSTALLING 7.02.10 Grab Rail Towel and Soup Dispenser Zone
LININGS, THE MAXIMUM ACCEPTABLE MOISTURE 750mmx750mm grab rail (30-40mm OD) 900mm up from
CONTENT SHALL BE: 18% OR LESS FOR BUILDINGS 7.02.15 Toilet Paper Holder Zone
floor level.
Toilet Paper Holder Zone
BLOCKING TO ALL WALL FRAMING WHERE REQUIRED 21 05
FOR BATHROOM JOINERY FIXING
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
7.02.14 Towel and Soup Dispenser Zone 7.02.10 Grab Rail
650MM MIN.
650MM MIN.
45
70 230
1,000MM
300MM MIN
1,000
700MM
700MM
460MM
460MM
26
Accessible Toilet Detail A 1:20 Accessible Toilet Detail B 1:20 Accessible Toilet Detail C 1:20
Firm Name Notes Job Title Design Pat Coll Client Name Scale
25
*
increased by providing 150 mm clear
(b) The parts of the telephone that are essential to its basic operation under space around base of walls.
nd
shall not be higher than 1200 mm above the ground or floor;
(c) Accessible telephones shall be equipped with a minimum handset
cord length of 750 mm;
it but not more than 10% of the documents subscribed to may be held in printed form at any one time.
ala
(d) Accessible telephones should have push button controls whenever
Masterspec subscribers are licensed to termporarily download this document and may print
possible;
(e) Telephone directories, if provided, should be in a position that is
Ze
convenient for use by a wheelchair user;
(f) Shelving shall be set at 775 mm minimum above the ground or
floor; and
w
(g) Open cubicles shall be 540 mm minimum deep.
Ne
All construction to comply with NZS3604:2011. Do NOT Scale off drawings. (only use figured dimensions) All dimensions are in millimetres unless stated otherwise. Read in conjuction with manufacturers specifications before installing products.
s
rd
da
an
St
ht
rig
py
Co
63
Firm Name Notes Job Title Design Pat Coll Client Name Scale
Copyright remains the property of Draftline Ltd unless specified in writing
DESIGN & DRAUGHTING SERVICES All dimensions are in millimetres unless otherwise stated Drawn Tim Mayo Rooney Group
All construction to comply with NZBC/NZ 3604: 2011, alongside all current
56 Queen Street Waimate
PROPERTY MANAGEMENT
PROPERTY INSPECTION
Checked #### Drawing Number
PATRICK COLL NZCD Arch standards alike Drawing Title
A421
10 Beswick Street Timaru
Refer to specifications for timber strength
Ph/Fax 03 688 8455
Cell 0274 370 280
Proposed Building Conversion Project Number DL20007
Accessible Counter Detail
Email pat.coll@draftline.co.nz ALL DIMENSIONS TO BE VERIFIED ON SITE Print Date 28/07/2020