FIRE ALARM SYSTEM FOR THE MONTH OF JAN 2024

CLIENT NAME : QTY SERVICING NOS :

LOOP / ZONE No: PANEL NO: 1 ,2 & 3.

DEVICE TYPE: SD, HD, MCP & Hooter. LOCATION -: All tower & Parking.
Sr. No Description of work Done Remarks
FIRE PANEL

1 All FAS equipment should be provied with UPS power supply Done

2 Panel On/Off condition Done


3 Checking of loops and rectification of faultin each loops Done
4 Battery, voltage and condition Done
5 Display check/ panel password Done

6 LED status for all loop card, communication card, mother board. Done

7 Panel supply voltage Done


i)Phase to neutral 240 AC
ii)Phase to earth 230 AC
iii)Neutral to earth 0.01 AC
8 Panel loop voltage(DC) 25.8 DC
9 Additional power supply AC/DC
10 Panel wiring termination Done
11 Panel lock and key Done
If require, programming of repalced or new detectors, MCPs,
12
hooters and sounders
13 Programming backup

FIELD DEVICE
1 Smoke detectors cleanning and checking Done
2 Checking MCP Done
3 Checking sounders Done
4 Checking control module
5 Checking monitor module
6 Checking zone module
7 Checking device voltage Done
8 Checking device connections Done
9 Checking device blinking Done

Remark :-1)All fire alarm system are working in normal condition. 2) B & D wing Repater panel faulty.

Customer Sign :- Engineer Sign :-


STATUS OF FIRE ALARM SYSTEM FOR THE MONTH OF JANUARY 2024
CLIENT NAME :
SR LOOP WORKING REPEATER
DEVICE NAME DEVICE TYPE LOCATION REMARKS
NO NO. STATUS PANEL

A&B
A WING RECEPTION
01 NOS

1 1 PS STANDER BASE SMOKE P0 TO 23TH FLOOR


DETECTOR 83 NOS. 19th & 13th floor MCP Cover missing. 2nos.

19th & 14th floor Detector Damage. 2nos.

2 CT-1 MODULE MCP P0 TO 23TH FLOOR


27 NOS

3 CONVENTIONAL HOOTER P0 TO 23TH FLOOR 18th floor hooter not working.


WITH 27 NOS
FLASHER

Remarks -:

For SEWEPL: Name/ Designation For Client: Name/ Designation


SR PANEL ZONE
LOOP NO. DEVICE TYPE LOCATION WORKING STATUS REMARKS
NO NO NO

1 1 SMOKE DETECTOR MULTI CLUB HOUSE ALL AREA : 46 NOS

2 1 HOOTER CLUB HOUSE ALL AREA : 03 NOS

3 2 SD & HD MULTI STANDARD BASE P1 ALL PARKING AREA : 290 NOS

4 2 MCP P1 ALL PARKING AREA : 16 NOS

5 2 HOOTER P1 ALL PARKING AREA : 30 NOS P1 level 2nos Hooter foulty.

P0 Level Parking No 1575 & 1291 Detector


6 3 SD & HD MULTI STANDARD BASE P0 ALL PARKING AREA : 260 NOS
Damage = 2nos.

7 3 MCP P0 ALL PARKING AREA : 15 NOS

8 3 HOOTER P0 ALL PARKING AREA : 27 NOS

Remark :-