V MT(V) S (KVA) In (tramo)(A) I accum dist tramos In x Ln

12000
150 7.22 86.60 1830 158482.65
150 7.22 79.39 150 11907.85
300 14.43 72.17 94 6783.87
300 14.43 57.74 111 6408.59
300 14.43 43.30 133 5759.07
300 14.43 28.87 151 4358.99
300 14.43 14.43 63 909.33
TOT 194610.34
Sn (mm2)= 12.64
COMERC AWG 6

BT Poste N Empalme Dist ent post S (KVA) S/Fd (KVA) In (A)


400 0
P Cu 1 6 53 21.0 31.34 45.24
0.018 2 2 22.5 7.0 10.45 15.08
FS 3 9 32.4 31.5 47.01 67.86
0.7 4 5 36.8 17.5 26.12 37.70
FD 5 8 39 28.0 41.79 60.32
1.6 Dist tot 30 183.7
voltaje
caida dedetension
perdidapor Vp= 30
metro Vc= 0.16330974

Poste N Emp/fase Dist ent post S (KVA) S/Fd (KVA) In (A)


0
1 2 53 7.0 5.83 25.25
2 1 22.5 3.5 2.92 12.63
3 3 32.4 10.5 8.75 37.88
4 2 36.8 7.0 5.83 25.25
5 3 39 10.5 8.75 37.88
1/3..
P Cu/Al Vp(6%) CONDUCOR ALUMINIO

0.027 720

In Acum (A) Sn (Tra) mm2 Sn Com (mm2) AWG CONDUCTOR. COBRE

226.20 43.18 33.6 2


180.96 34.55 21.2 4
165.88 31.67 21.2 4
98.02 18.71 13.3 6
60.32 11.52 13.3 6

In Acum (A) Sn Com (mm2) Vp Tram Vp Acc

138.89 33.6 7.89 7.89


113.64 21.2 4.34 12.23
101.01 21.2 5.56 17.79
63.13 13.3 6.29 24.07
37.88 13.3 4.00 28.07