Professional Documents
Culture Documents
Derby VC0-Report
Derby VC0-Report
Derby VC0-Report
Normalized productions (per installed kWp): Nominal power 441 kWp Performance Ratio PR
6 1.0
Lc : Collection Loss (PV-array losses) 0.4 kWh/kWp/day PR : Performance Ratio (Yf / Yr) : 0.823
0.9
Ls : System Loss (inverter, ...) 0.07 kWh/kWp/day
5 Yf : Produced useful energy (inverter output) 2.18 kWh/kWp/day
0.8
[kWh/kWp/day]
0.7
4
Performance Ratio PR
0.6
Energy
3 0.5
0.4
Normalized
2
0.3
0.2
1
0.1
0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Derby
Balances and main results
Legends: GlobHor Horizontal global irradiation GlobEff Effective Global, corr. for IAM and shadings
DiffHor Horizontal diffuse irradiation EArray Effective energy at the output of the array
T_Amb Ambient Temperature E_Grid Energy injected into grid
GlobInc Global incident in coll. plane PR Performance Ratio
PVSYST V6.81 12/05/23 Page 4/6
3000
Values from 01/01 to 31/12
2500
[kWh/day]
2000
grid
into
1500
injected
1000
Energy
500
0
0 2 4 6 8 10
Global incident in coll. plane [kWh/m².day]
10000
Values from 01/01 to 31/12
Bin]
8000
/
[kWh
6000
grid
into
injected
4000
Energy
2000
0
0 100 200 300 400
Power injected into grid [kW]
PVSYST V6.81 12/05/23 Page 5/6
The probability distribution variance is also depending on some system parameters uncertainties
Specified Deviation PV module modelling/parameters 1.0 %
Inverter efficiency uncertainty 0.5 %
Soiling and mismatch uncertainties 1.0 %
Degradation uncertainty 1.0 %
Global variability (meteo + system) Variance 1.9 % (quadratic sum)
Probability distribution
0.50
0.45
P50 = 343401 kWh
0.40
0.35
0.30
Probability
0.25
E_Grid simul =
0.20 350409 kWh
P90 = 335163 kWh
0.15
0.05
0.00
325000 330000 335000 340000 345000 350000 355000 360000 365000
E_Grid system production kWh