Sigineer Power Any Power Combi High Power PSW7 Powerstar Inverter Service Manual
Sigineer Power Any Power Combi High Power PSW7 Powerstar Inverter Service Manual
Summary
1、Main Function;
2、General Specification;
3、Battery & Charger
4、Alarm & Indicators
5、Block Diagram
6、Key Part Of The Electrical Schematic
7、Inverter State Diagram
8、Trouble shooting
9、Something keep in mind
10、RMA record
All Rights Reserved. Shenzhen Sigineer Power CO.,LTD. www.sigineer.com
1、Main Function
2、General Specification
All Rights Reserved. Shenzhen Sigineer Power CO.,LTD. www.sigineer.com
CC √ × √ × × × × √ × × ×
Line
CV √ × √, blink × × × × √ × × ×
Mode
Float √ × × √ × × × √ × × ×
Standby √ × × × × × × × × × ×
Inverter
on
× √ × × × × × × √ × ×
Invert
Mode Power
saver × × × × × × √ × × × ×
beep
Battery
Low × √ × × × × × × √ √ 0.5s
every 5s
beep
Battery
High
× √ × × × × × × √ √ 0.5s
every 1s
Overload Refer to
on invert × √ × × × √ × × √ √ “Audible
mode alarm”
Alarm
Mode OverTem
Beep
p on
invert × √ × × √ × × × √ √ 0.5s
every 1s
mode
OverTem beep
p on line √ × √ × √ × × √ × √ 0.5s
mode every 1s
beep
Over
charge
√ × √ × × × × √ × √ 0.5s
every 1s
All Rights Reserved. Shenzhen Sigineer Power CO.,LTD. www.sigineer.com
beep
Fan lock × × × × × × × × × × continuous
Battery beep
High
× √ × × × × × × √ × continuous
Inverter
beep
mode × × × × × √ × × × × continuous
Fault overload
Mode
beep
OverTemp × × × × √ × × × × × continuous
Over beep
charge × × √ × × × × √ × × continuous
5 、Block Diagram
All Rights Reserved. Shenzhen Sigineer Power CO.,LTD. www.sigineer.com
Standby Alarm:
1.Fan Locked Power On Mode
2..Bat.Weak 1. MCU is power on
UPS AutoReStart:
Auto Start Delay Off
&& Mains OK && Not Bat.Low
MODE
1.DC start && Mains NG Line Mode Test:
2.! DC start && Mains NG 1.Test SW On && battery fully charged
2.Test Command Received && battery LINE MODE
BATTERY full charged 1.UPS supplies the load
MODE power from Utility
1.UPS supplies the load 1.Mains Not OK
power from Battery
1.Mains OK Line Alarm:
1.Fan Locked
Battery Mode Alarm:
Self Test Mode Fail: 2.Over Loaded
1.Battery Low
1.Over Loaded Timeout 3.Bad Battery
2.Over loaded
2.Over Temperature Line Mode Fail: 4.Overcharged
3.Fan Locked Battery Mode Fail:
3.Output Shorted 1.Over Loaded Timeout 5..Inverter failed
1.Over Loaded Timeout
2.Over Temperature 4.Fan Locked Timeout 2.Over Temperature
3.Inverter Failure 5. first power on && inverter failed 3.Output Shorted
4.Output Shorted 6. first power on && battery bad 4.Fan Locked Timeout
5.Fan Locked Timeout
Standby Mode Fail: Fault Reset:
1.Over Temperature 1. (Fanlock || Overcharged || Overtemperature)
2.Fan Locked Timeout && ( main SW off || battery low) && no mains
3.Over charged
FAULT 2. ( !Fanlock && !Overcharged && !Overtemperature)
&& ( main SW off || battery low)
1.UPS is fault condition
2.Ouput has no power
All Rights Reserved. Shenzhen Sigineer Power CO.,LTD. www.sigineer.com
8、Trouble Shooting
The most possible failure components are listed as following:
1、UPS fault at the battery mode (IGBT Damage Q1~Q24)