• Background information
• System information
• Field replacement
The new pump has a new pilot and a new position transducer (LVDT) It is
internally different with an increased number of pistons and a new sliding
stroke ring
This presentation covers the various issues that will occur in the field.
-The new Moog LVDT parts are all different to the old Bosch parts.
Further, the flange interface differs because a centralising counter-bore is required. Hence mechanical
interchangeability is ruled out from the start.
-The Bosch Transducer is matched with the Bosch core. It is supplied only as a matched set and cannot be
separated. If the Bosch transducer is changed without fitting the matched core that comes with it, then a gain
(hence flow) error results. Generally this error is small and this repair is acceptable in an emergency. It is however
necessary that the transducer mechanical null be
re-set by experienced personnel.
- Finally any remaining flow errors can be minimized by adjustments on the pQ-card, namely:
- Poti “Qmax” for the Qmax-adjustment
- Poti “Valve” for the Qmin-adjustment
Transducer notes
-The Moog transducer is not paired with the Moog core so that the transducer can be changed without changing
the core. However the mechanical null must still be re-adjusted and this should only be done by trained personnel.
- Finally any remaining flow errors can be minimized by adjustments on the pQ-card, namely:
- Poti “Qmax” for the Qmax-adjustment
- Poti “Valve” for the Qmin-adjustment
- General Note
The Moog warranty for the pump is void if any conversion or adjustments of the transducer takes place
It cannot be assumed from the information in these briefing notes that Moog officially approves of Moog transducer
repairs – rather the notes are provided with the knowledge that such unauthorised repairs have been carried out for
years in individual cases and that this practice will probably continue with the new EHV2.
• Background information
• System information
• Field replacement
Bosch-Transducer
Bosch-pL6-Pilot valve
Bosch-pQ-Card
Bosch-Card
Bosch-transducer
b6,b8 b22, b24, z30,b30 b26,b28,z30,b30
Matched !
Bosch-pL6
Features
- Change-over solution for existing EHV pumps
- same connector as EHV pump
- same dynamic behaviour as the EHV-Pump
(ie no new adjustment to the pQ-Karte is needed)
Based on:
- new Moog Transducer
- new Moog Pilot valve and new block
- new Pump working elements & housing
To note:
- The dimensions of the Pilot valve, the transducer and
the pump are slightly different (the pump has a
larger suction port)
- The Bosch-Controller Card is still needed to maintain
Warning: this picture is of a pre-series unit with
the same tuned response the solenoid connector in a different position!
Moog transducer
Bosch-Card
b26,b28,z30,b30 b22, b24, z30,b30 b6,b8
Not matched
LVDT
Pilot
Bosch-extension +
Magnet Bosch-core
Transducer
conditioner
Moog-D920
Moog-block
with
recessed
counterbore
Control Ring
LVDT
• Background information
• System information
• Field replacement
If any of the listed replacement options are carried out by the end user,
then Moog warranty no longer applies.
Full warranty only applies if these repairs are done by Moog or their authorised
agent.
Improper execution of these measures can lead to faults or faulty pump operation.
Control
Bosch-extension +
Ring
Bosch-core
Pilot LVDT
Magnet LVDT
defective !
Bosch block
Bosch-pL6
Action:
Fit Moog pilot valve !
Bosch-Card
Bosch transducer
b6,b8 b22, b24, z30,b30 b26,b28,z30,b30
LVDT
Control
Pilot
Bosch-extension +
Ring
Bosch-core
LVDT
Transducer
conditioner
Moog-D920
Bosch block
new !
No connector
Magnet
protective
required
Sealed
with a
cap
Control Bosch-extension +
Ring Bosch-core
LVDT
Pilot
Magnet LVDT
Regular Actions:
- Return to Moog for change-over to Moog LVDT and Moog pilot.
- Return to Moog for Bosch LVDT repair – only possible in the short term
Emergency repair :
Bosch-pL6 • Fit a new Bosch LVDT
• Leave existing Bosch Core & Core extension & pressure tube in
the pump
• Trained personnel to retrim null
• Readjust Qmin and Qmax on the controller
LVDT
Pilot
Magnet
Transducer
conditioner
Moog-D920
defective !
LVDT defective !
Pilot
Magnet
conditioner
Transducer
Moog-D920
Regular Action:
- Return to Moog for Moog LVDT change-over
- Emergency repair by trained personnel
• Replace Moog transducer with built-in pressure tube.
control ring • Leave Core + Core holder in the pump
LVDT • Retrim the mechanical null
• Check Qmin and Qmax on the controller card and trim if required
Vibration-proof
Moog Transducer Null-adjust screw SW10