Professional Documents
Culture Documents
ProTech V Series User Guide
ProTech V Series User Guide
ProTech V Series User Guide
Table of Contents
CHAPTER 1……………………………………………………………….....- 7-
About This Manual ............................................................................. - 8 -
Introduction ........................................................................................ - 9 -
SAFETY PRECAUTIONS ...................................................................................................................... - 10 -
SAFETY LABELS ............................................................................................................................... - 11 -
LIMITED WARRANTY .......................................................................................................................... - 12 -
LIMITATION ON LIABILITY ................................................................................................................... - 12 -
UNAUTHORIZED REPAIR .................................................................................................................... - 12 -
Installation ........................................................................................ - 13 -
GENERAL CONSIDERATIONS .............................................................................................................. - 13 -
ENCLOSURE CONSIDERATIONS .......................................................................................................... - 14 -
ENVIRONMENTAL CONSIDERATIONS ................................................................................................... - 15 -
POWER REQUIREMENTS, GROUNDING AND WIRING ............................................................................ - 15 -
ANALOG INPUT WIRING ..................................................................................................................... - 16 -
TEMPERATURE INPUT WIRING............................................................................................................ - 16 -
DIGITAL INPUT WIRING ...................................................................................................................... - 17 -
CURRENT TRANSFORMER WIRING ..................................................................................................... - 17 -
ANALOG OUTPUT WIRING ................................................................................................................. - 18 -
DIGITAL OUTPUT WIRING .................................................................................................................. - 18 -
MOTOR CONTROL OUTPUT WIRING.................................................................................................... - 18 -
COMMUNICATION WIRING .................................................................................................................. - 19 -
M AIN DRIVE MOTOR CONTROL .......................................................................................................... - 19 -
Specifications ................................................................................... - 21 -
USER INTERFACE MODULE (UIM) ...................................................................................................... - 21 -
M AIN LOGIC MODULE (MLM) ............................................................................................................ - 22 -
Troubleshooting ............................................................................... - 23 -
COMPRESSOR START FAILURE .......................................................................................................... - 24 -
SENSOR FAULT ............................................................................................................................ - 24 -
CONTROL PANEL INOPERATIVE ................................................................................................ - 25 -
DISPLAY CONTRAST POOR ........................................................................................................ - 25 -
MOTOR OVERLOAD ..................................................................................................................... - 25 -
ABNORMAL CONTROL PERFORMANCE ................................................................................... - 26 -
HIGH AIR PRESSURE ................................................................................................................... - 26 -
LOW AIR PRESSURE .................................................................................................................... - 26 -
CHAPTER 2………………………………………………………………....-32-
Introduction ...................................................................................... - 33 -
ProTech Checks: Before Turning Power On .................................. - 34 -
ProTech Checks: Initial Application Of Power ............................... - 35 -
Initial Start of Compressor............................................................... - 39 -
Initial Control Loop Tuning Process ............................................... - 40 -
Surge Testing ................................................................................... - 42 -
Natural Surge test ......................................................................................................................... - 42 -
High Throttle Surge Test .............................................................................................................. - 44 -
Mid Throttle Surge Test ................................................................................................................ - 44 -
Low Throttle Surge Test ............................................................................................................... - 44 -
CHAPTER 4………………………………………………………………..- 82 -
About This Guide.............................................................................. - 83 -
Installation ........................................................................................ - 84 -
Configuration .................................................................................... - 84 -
Modbus Protocol .............................................................................. - 85 -
Synchronization ............................................................................... - 85 -
Message Format ............................................................................... - 85 -
Address Field ................................................................................................................................ - 85 -
Function Field ............................................................................................................................... - 86 -
Data Field ....................................................................................................................................... - 86 -
Error Check Field .......................................................................................................................... - 86 -
All operating personnel should become familiar with the contents of this manual before the control
system is put into service. This is particularly important with regard to the safety precautions listed in
the Introduction section, and those included at relevant points of the procedures described in other
sections of this manual.
WARNING:
! Read, be sure to clearly understand, and then carefully follow all of the
directions and procedures included in this manual. Failure to adhere to the
guidelines and specific instructions provided could cause equipment damage
and serious personal injury or death.
AVERTISSEMENT:
Lit, est sûr clairement comprendre, et alors suivre toutes les directions et
procédures incluses dans ce manuel. Echec adhérer aux indications et
spécifique instructions fourni pourrait causer équipement et sérieux personnel
blessure ou mort.
Introduction
The ProTech controller uses two components, referred to as modules, with an interconnecting cable, to
provide a complete compressor control system (expansion modules can also be added to monitor
and/or control additional systems). This high integration architecture results in high reliability, simple
serviceability, and lower equipment and maintenance costs.
The two types of modules used with the ProTech are the User Interface Module (UIM), which contains a
graphic display and keypad, and the Main Logic Module (MLM), which contains the power supply,
microprocessor, memory, communications, and I/O processing circuitry.
Your ProTech controller may be packaged with other components in a control panel, or may have been
retrofitted into your previous compressor control system.
The control system software, configuration file, and set points, are loaded into the memory of the Main
Logic Module to tailor the control system for the specific compressor and control strategy to be used.
This software is licensed and configured for your specific compressor application.
Safety Precautions
Compressors are powerful industrial machines that utilize high-speed rotating elements and high
voltages to produce high gas pressures. Therefore, it is very important to use extra safety precautions
whenever the compressor is in operation as well as when performing maintenance or making repairs.
Bay Controls, LLC expressly disclaims responsibility or liability for any injury or damage caused by
failure to observe specified or other common safety precautions or failure to exercise ordinary caution,
common sense, and due care required in operating the compressor and auxiliary systems even though
not specified herein.
If this equipment is used in a manner not specified by Bay Controls, LLC, the protection provided by this
equipment may be impaired.
The alert messages shown here appear throughout this manual to indicate those situations and
times when special care is necessary to prevent equipment damage or personal injury. There are
three degrees of urgency:
CAUTION:
LA PRUDENCE:
Ceci indique que cela il peut y avoir la possibilité de dommages d'équipement.
!
WARNING:
This indicates that there could be the possibility of equipment damage or
personal injury.
AVERTISSEMENT:
Ceci indique cela là-bas pourrait être la possibilité de ou personnel.
!
DANGER:
This indicates that there will definitely be equipment damage and/or personal
injury or death if all proper safety precautions are not carefully followed.
DANGER:
Ceci indique cela là-bas sera équipement dommages personnel blessure ou
mort si tout propre sûreté ne sont pas suivi.
Safety Labels
The following safety labels alerts the installer or operator to possible hazards and serves to remind the
user of specific safety precautions. Before installing and/or operating this control system, be certain to
review the pertinent safety labels.
!
DO NOT REMOVE THE COVER.
NO SERVICABLE PARTS INSIDE.
REFER SERVICING TO QUALIFIED PERSONNEL.
READ OPERATORS MANUAL THOROUGHLY
BEFORE OPERATING EQUIPMENT.
Limited Warranty
Subject to the limitations contained below, and except as otherwise expressly provided herein, Seller
warrants to the Buyer that all tangible articles supplied by Seller or services provided by Seller will be
free of defects in materials or workmanship under normal use and care until the expiration of the
applicable warranty period. Goods are warranted for twelve (12) months from the date of initial field
installation or eighteen (18) months from the date of shipment, whichever period expires first. If Buyer
discovers any warranty defects and notifies Seller thereof in writing during the applicable warranty
period, Seller shall at its option promptly correct, repair, or replace F.O.B. point of manufacture that
portion of the good found by Seller to be defective, or refund the purchase price of the defective portion
of the goods/services. All replacements or repairs necessitated by inadequate maintenance, normal
wear and usage, unsuitable power sources, unsuitable environmental conditions, accident, misuse,
improper installation, modification, repair, storage or handling, or any other cause not the fault of Seller
are not covered by this limited warranty, and shall be at Buyer’s expense. Seller shall not be obligated
to pay any costs or charges incurred by Buyer except as may be agreed upon in writing in advance by
an authorized Seller representative. All costs of dismantling, reinstallation and freight and the time and
expenses of Seller’s personnel for site travel and diagnosis under this warranty clause shall be borne
by Buyer. Goods repaired and parts replaced during the warranty period shall be in warranty for the
remainder of the original warranty period or ninety (90) days, whichever is longer. Except as otherwise
expressly provided in the Agreement, THERE ARE NO REPRESENTATIONS OR WARRANTIES OF
ANY KIND, EXPRESS OR IMPLIED, AS TO MERCHANTABILITY, FITNESS FOR PARTICULAR
PURPOSE, OR ANY OTHER MATTER WITH RESPECT TO ANY GOODS OR SERVICES.
Limitation on Liability
THE SOLE AND EXCLUSIVE REMEDY FOR BREACH OF WARRANTY HEREUNDER SHALL BE
LIMITED TO REPAIR, CORRECTION, REPLACEMENT OR REFUND OF PURCHASE PRICE AS
PROVIDED UNDER THE FOREGOING LIMITED WARRANTY.
BUYER AGREES THAT IN NO EVENT SHALL SELLER’S LIABILITY TO BUYER AND/OR ITS
CUSTOMERS INCLUDE “CONSEQUENTIAL DAMAGES”. FOR THIS PURPOSE,
“CONSEQUENTIAL DAMAGES” SHALL INCLUDE, BUT NOT BE LIMITED TO, LOSS OF
ANTICIPATED PROFITS, LOSS OF USE, LOSS OF REVENUE AND LOSS OF CAPITAL.
Unauthorized Repair
In the event that the owner allows the ProTech Control System to be serviced or repaired by
unauthorized personnel, the coverage of the original warranty policy will be automatically terminated.
Installation
General Considerations
Advance planning and preparation will help to simplify and expedite the installation of the ProTech
control system with a new or retrofit installation.
At least two weeks before the projected startup date contact Bay Controls Customer Service
Department (419-891-4390) to schedule startup service.
Insure that you have the latest wiring diagrams and drawings, provided with your licensed software and
configuration, for your specific compressor. Contact the Customer Service Department if you have any
questions related to the installation drawings or wiring diagrams.
When designing and installing the control system, it is necessary to meet the following minimum
requirements:
Assure que vous a le dernier télégraphiant diagrammes et dessins, fourni avec votre autorisé logiciel et
configuration, pour votre spécifique compresseur. Contacte votre autorisé service si vous a n'importe
quelles questions relaté à le ou télégraphiers diagrammes. En concevant et l'installer le système de
contrôle, c'est nécessaire de rencontrer le suivre les conditions minimum:
Be certain that the main power supply meets the specifications, including voltage, frequency, and
most importantly the current carrying capacity of the wires.
Est certain que l'alimentation principale rencontre les spécifications, y compris la tension, la
fréquence, et le plus important le courant porter capacité des fils.
Provide an appropriate separate earth ground that meets local and national codes. In the United
States refer to section 250-26 of the National Electrical Code for earth ground definition.
Fournit un approprie séparé terre qui rencontre local et national codes. Aux états-unis réfère à
section 250-26 du National Electrique Code pour terre sol.
Include proper disconnects such as switches or circuit breakers to provide complete isolation from
the electrical supply. An approved external fused disconnect device (rated at 250 Volts AC, 15
Amps with 3.0 mm contact separation in all supply lines must be located near the equipment.
Inclure propre débranche tel que les commutateurs ou tel que les disjoncteurs pour fournir
l'isolement complet de la provision électrique. Un approuvé externe unifié débranche l'appareil
(évalué à 250 COURANT ALTERNATIF de Volts, 15 Amplis avec 3.0 mm la séparation de contact
dans toutes lignes de provision doit être localisée près de l'équipement.
If the main power switch that controls the compressor is remotely located or if it difficult to lock out
the main switch, install a local switch to enable maintenance personnel to isolate the unit.
Si l'interrupteur général principal qui règle le compresseur est vaguement localisé ou s'il difficile à
verrouiller hors le commutateur principal, installer un commutateur local pour rendre capable le
personnel d'entretien pour isoler l'unité.
Install and use a lockout system whenever performing maintenance procedures on this or any other
type of equipment.
Installer et utiliser un système de lockout quand les procédures d'entretien qui exécutant sur ceci
ou tout autre type d'équipement.
DANGER:
!
To ensure a proper and safe initial startup and optimum operation of the
ProTech control system, a factory trained and authorized service representative
should be present to inspect the site, supervise the final installation steps, assist
with the startup procedure, and train operating personnel. Failure to follow these
guidelines may result in equipment damage and/or personal injury or death.
DANGER:
Assurer un propre et sûr initial démarrage et optimum opération de l'AProTech
contrôle , une Baie Règle usine entraîné et autorisé service doit être actuel
inspecter le site, surveille le final installation , aide avec le démarrage , et train
opération . Echec suivre ces indications peut résulter dans équipement
dommages personnel blessure ou mort.
DANGER:
!
Be certain that all electrical work is performed by qualified personnel according
to product specifications and all applicable local and national codes. Failure to
follow this requirement may result in equipment damage and/or personal injury
or death.
DANGER:
Est certain que tout électrique travail est exécuté par qualifié personnel selon
produit et tout applicable local et national codes. Echec suivre cette condition
peut résulter dans équipement dommages personnel blessure ou mort.
Enclosure Considerations
The ProTech User Interface Module and Main Logic Modules must be mounted in a watertight
enclosure that requires the use of a key or tool to gain access. A NEMA 4 rated enclosure is
recommended for indoor use, a NEMA 4X rated enclosure is recommended for outdoor use or where
corrosive chemicals are present.
L'AProTech Interface utilisateur et Principal Logique doit être monté dans un watertight qui exige
l'usage d'une clef ou outil gagner accès. Un NEMA 4 clôture évaluée est recommandée pour l'usage
intérieur, un NEMA 4X a évalué la clôture est recommandée pour l'usage extérieur ou où les produits
chimiques corrosifs sont actuels.
If the ProTech is installed in a hazardous atmosphere, or at a location where there is any possibility of
the atmosphere becoming hazardous, an enclosure must be used that is appropriately rated for the
operating environment.
DANGER:
! Failure to install the ProTech control system using the proper enclosure may
cause equipment damage and/or personal injury or death.
DANGER:
Echec installer l'AProTech contrôle système le propre clôture peut causer
équipement dommages personnel blessure ou mort.
Environmental Considerations
The ProTech User Interface Module and Main Logic Modules are designed to operate at an ambient
temperature range of 0° to 60° C, 95% relative humidity, and non-condensing. If the temperature inside
the control enclosure exceeds these limits, panel heaters or coolers must be installed to maintain the
specified operating temperature range.
L'AProTech Interface utilisateur et Principal Logique sont conçu opérer à un ambiant température de 0°
à 60° C, 95% relatif , et non-condenser. Si la température dans les dépasse ces limites, ou coolers doit
être installé maintenir le spécifié opérere température .
CAUTION:
LA PRUDENCE:
l'Opération du système de contrôle hors de la portée de température spécifiée
qui opérant peut causer les dommages d'équipement.
The ProTech controller operates on 100 – 240 VAC, 50 or 60 Hz, up to 10 amps per Main Logic Module
(MLM). Connector J15 of each MLM must be wired with a single-phase power feed of 10 amps with
circuit protection using 14 gauge THHN, 600 volt, 105°C insulation wire. Terminal L1 of connector J15
is the single-phase hot connection, black color. Terminal L2 of connector J15 is the single-phase
neutral, white color. Copper conductors for connection to J15 must be made in accordance with the
NEC/CEC and local codes.
L’AProTech opère sur 100 – 240 , 50 ou 60 , jusqu'à 10 Principal Logique (MLM). Le connecteur J15 de
chaque MLM doit être télégraphié avec un pouvoir de seul-phase nourrit de 10 amps avec l'utilisation
de protection de circuit 14 THHN de jauge, 600 volt, 105°le fil d'isolation de C. Délimitant L1 de
connecteur J15 est la seul-phase la connexion chaude, la couleur noire. Délimitant L2 de connecteur
J15 est la seul-phase neutre, blanc couleur. Les conducteurs de cuivre pour la connexion à J15 doivent
être conformément faits au NEC CEC et les codes locaux.
Terminal GND of connector J15 of the Main Logic Module must be connected to earth
ground using 14 gage THHN, 600 volt, 105°C insulation wire, green/yellow color.
GND délimitant de connecteur J15 du Module de Logique Principal doit être connecté à l'utilisation de
sol de terre 14 THHN de gage, 600 volt, 105°le fil d'isolation de C, la couleur vert/jaune.
The case of the User Interface Module (UIM) must be connected to earth ground. This connection can
be accomplished either by attaching a ground wire directly to the module using one of the mounting
studs, or by attaching a ground wire to the enclosure door or plate that the UIM is mounted to. In either
case use 14 gage THHN, 600 volt, 105°C insulation wire, green/yellow color.
Le cas du Module d'Interface utilisateur (UIM) doit être connecté au sol de terre. Cette connexion peut
être accompli ou en attachant un directement au module en utilisant un des monters clous, ou en
attachant un sol A LA CLOTURE OU PLAQUE QUI LE UIM EST MONTE A. Dans ou le cas utilise 14
THHN de gage, 600 volt, 105°le fil d'isolation de C, la couleur vert/jaune.
!
DANGER:
Failure to properly ground the control system modules may cause equipment
damage and/or personal injury or death.
DANGER:
Echec convenablement mettre à terre le contrôle système peut causer
équipement dommages personnel blessure ou mort.
Analog Input Wiring
All of the analog input wiring, which is connected to connectors J5 and J6 of the Main Logic Module,
must be 18 gage twisted pair 2-conductor 300 volt cable, such as Belden # 9740 or equivalent.
Toute l'analogue données télégraphiant, qui est connecté à connecteurs J5 et J6 du Principal Logique ,
doit être 18 gage tordu paire a protégé 2-300-câble, tel que Belden # 9740 ou équivalent.
Analog wiring should be separated from digital and higher voltage wiring as much as possible. Do not
install analog wiring in the same conduit with higher voltage digital wiring.
Analogue installation éléctrique devrait être séparé de numérique et à haute tension installation
éléctrique autant que possible. Ne pas installe analogue installation éléctrique dans pareil conduit avec
A haute tension numérique installation éléctrique.
Temperature Input Wiring
All of the temperature input wiring, which is connected at connectors J7 and J8, must be 22 gage 3-
conductor 300 volt cable such as Belden # 8443 or equivalent.
Toute la température télégraphiant, qui est connecté à connecteurs J7 et J8, doit être 22 gage a
protégé 3-300-câble tel que Belden # 8443 ou équivalent.
Temperature input wiring should be separated from digital and higher voltage wiring as much as
possible. Do not install temperature input wiring in the same conduit with higher voltage digital wiring.
Température télégraphiant devrait être séparé de numérique et à haute tension installation éléctrique
autant que possible. Ne pas installe température télégraphiant dans pareil conduit avec A haute tension
numérique installation éléctrique.
Tout le numérique données télégraphiant, qui est connecté à connecteur J10 du Principal Logique , doit
être 18 gage tordu paire a protégé 2-300-câble, tel que Belden # 9740 ou équivalent.
Analog wiring should be separated from digital and higher voltage wiring as much as possible. Do not
install analog wiring in the same conduit with higher voltage digital wiring.
Analogue installation éléctrique devrait être séparé de numérique et à haute tension installation
éléctrique autant que possible. Ne pas installe analogue installation éléctrique dans pareil conduit avec
A haute tension numérique installation éléctrique.
Current Transformer Wiring
The current transformer wiring, which is connected at connector J11 of the Main Logic Module, must be
14 gauge THHN, 600 volt, 105°C insulation. The input voltage is 32 VAC, the maximum over current is
as follows: 6x (30 Amps) for 1 second, 4x (20 Amps) for 20 seconds, 2x (10 Amps) continuous.
L'installation éléctrique actuelle de transformateur, qui est connectée au connecteur J11 du Module de
Logique Principal, doit être 14 THHN de jauge, 600 volt, 105°l'isolation de C. La tension de données est
32 VAC, le maximum par-dessus le courant est comme suit: 6x (30 Amplis) pour de 1 seconde, 4x (20
Amplis) pour de 20 seconde, 2x (10 Amplis) continu.
The current transformer should typically be sized for twice the full load amps of the motor.
Le transformateur actuel typiquement devrait être sized pour deux fois les amplis de chargement pleins
du moteur.
Wiring of the current transformer (CT) should be separated from other wiring as much as possible. Do
not install the CT wiring in the same conduit with other wiring.
L'installation éléctrique du transformateur actuel (CT) devrait être séparé de l'autre installation
éléctrique autant que possible. Ne pas installer le CT qui télégraphiant dans le conduit pareil avec
l'autre installation éléctrique.
Tout l'analogue production télégraphiant, qui est connecté à connecteur J4, doit être 18 gage tordu
paire a protégé 2-300-câble, tel que Belden # 9740 ou équivalent.
Analog wiring should be separated from digital and higher voltage wiring as much as possible. Do not
install analog wiring in the same conduit with higher voltage digital wiring.
Analogue installation éléctrique devrait être séparé de numérique et à haute tension installation
éléctrique autant que possible. Ne pas installe analogue installation éléctrique dans pareil conduit avec
A haute tension numérique installation éléctrique.
Tout le numérique, qui est connecté à J13 et du Principal Logique, doit être, 600, 105°C.
Digital output wiring should be separated from low voltage wiring as much as possible. Do not install
digital output wiring in the same conduit with low voltage wiring.
Le moteur l'arrêt de de contrôle et cas urgent installation éléctrique de bouton de, qui sont connectées
au connecteur J12 du Module de Logique Principal, doit être 14 THHN de jauge, 600 volt,
105°l'isolation de C.
Communication Wiring
The communications wiring for the C-Link network (connector J2), MODBUS interface (connector J9),
and MLM Buss (connector J3), of the Main Logic Module must be 22 gauge 3-conductor shielded
twisted such as Belden # 3108A or equivalent.
Les communications télégraphiant pour la (connecteur J2), MODBUS (connecteur J9), et MLM
(connecteur J3), du Principal Logique doit être 22 jauge 3-protégé tordu tel que Belden # 3108A ou
équivalent.
Communication wiring should be installed in separate conduit and separated from other higher voltage
wiring as much as possible.
Communication devrait être installé dans séparé conduit et séparé d'autre à haute tension installation
éléctrique autant que possible.
The shields of the communication cables must be connected to earth ground at one point only. The
GND terminal of connector J2, J3, and J9 is used for this purpose. There should only be a single
connection to one GND terminal per network. The shield wires of communications cables connected to
modules that are in the middle of the network must be connected together without using a terminal in
the connectors.
Les protections des câbles de communication doivent être connectées au sol de terre à un point
seulement. Le GND de connecteur J2, J3, et J9 est utilisé à cet effet. Il seulement doit y avoir une
connexion seule à un terminal de GND par le réseau. Les fils de protection de câbles de
communications connectés aux modules qui sont au milieu du réseau doit être ensemble connecté
sans l'utilisation d'un terminal dans les connecteurs.
L'AProTech interface avec le compresseur principal unité moteur un solide état, , numérique A
CONNECTEUR J12. Cette interface est conçue pour utiliser un bouton d'arrêt de cas urgent
télégraphié dans le feuilleton avec le production d'AProTech, le fournir fonctionnement continu assuré
la fermeture du moteur quand le bouton d'arrêt de cas urgent est activé.
!
DANGER:
Failure to install and properly connect the emergency stop pushbutton may
cause equipment damage and/or personal injury or death.
DANGER:
Echec installer et convenablement connecter le cas urgent arrêt peut causer
équipement dommages personnel blessure ou mort.
DANGER:
!
Be sure to properly connect the motor control interface as shown in the
installation drawings provided by a factory trained and authorized service
representative. Improper wiring of the motor control output may cause
equipment damage and/or personal injury or death.
LE DANGER:
Etre sûr convenablement de connecter l'interface de contrôle de moteur selon
les dessins d'installation fournis par une usine a entraîné et a autorisé le
représentant de service. Déplacé installation éléctrique du moteur contrôle peut
causer équipement dommages personnel blessure ou mort.
The ProTech controller limits the maximum motor current by limiting the maximum flow through the
compressor, however this function is not designed to replace the motor overload protection function of
the motor control center. An operator may be able to set the maximum motor load set point above a
safe operating value for a given motor installation.
Le contrôleur d'AProTech limite le courant de moteur maximum en limitant le flux maximum par le
compresseur, cependant cette fonction n'est pas conçue pour remplacer la fonction de protection de
surcharge de moteur du centre de contrôle de moteur. Un opérateur peut pouvoir régler le point de
série de chargement de moteur maximum au-dessus d'une valeur sûre qui opérant pour une installation
de moteur donnée.
DANGER:
!
The main drive motor control must provide all necessary protection functions,
including but not limited to, overload, phase imbalance, and under-voltage, to
insure safe operation. Failure to insure safe operation of the motor protection
functions of the motor control may cause equipment damage and/or personal
injury or death.
DANGER:
Le principal unité moteur doit fournir tout nécessaire protection , y compris mais
A, SURCHARGE, PHASE , ET SOUS-TENSION, ASSURER SUR
OPERATION. Echec assurer sûr opération du moteur protection du moteur peut
causer équipement dommages personnel blessure ou mort.
Specifications
Environmental: Operating temperature range: 32 F to 122 F (0 C to 50 C). Storage
temperature range: -10 F to 140 F (-23 C to 60 C). Maximum
relative humidity of 92.5% (non-condensing), up to 2000 meters
altitude.
Keypad: 15 keys tactile feel polyester membrane keypad with integral display
window, stainless steel domes, UV hard-coated.
Display: Monochrome 640 x 480 pixel graphic LCD with CCFL backlighting.
Size: 17.5" (44.5 cm) W x 8" (20.3 cm) H x 3" (7.6 cm) D.
Environmental: Operating temperature range: 32 F to 122 F (0 C to 50 C). Storage
temperature range: -10 F to 140 F (-23 C to 60 C). Maximum
relative humidity of 92.5% (non-condensing), up to 2000 meters
altitude.
Power Requirements: 100 - 120 / 200 - 240 VAC (+/- 10%), 10 Amps, 50-60 Hz (+/- 3 Hz).
Battery Specification: Lithium type VL2020, 3.0 Volts DC. This battery cannot be accessed or
changed by the customer. Warning – Only this type of battery can be
used.
Monitoring Inputs: (13) 4-20 ma current loop analog inputs (24 VDC, 2 Wire).
(10) RTD temperature sensor inputs (3 Wire, 100-Ohm Pt).
(8) 24 VDC digital inputs (dry contact interface).
(1) 0 – 5 Amp current transformer input, 32 VAC,
Over current: 6x (30 Amp) for 1 seconds 4x (20 Amp) for 20 seconds,
2x (10 Amp) continuous.
(1) 100 – 240 VAC digital input (optically isolated E-stop motor start
circuit interface).
Control Outputs: (4) 4-20 ma current loop analog outputs (24 VDC, 2 wire).
(12) 240 VAC digital outputs (optically isolated, solid-state relay, 5 Amp
maximum load).
Troubleshooting
A general troubleshooting guide is listed below. It is intended to provide the user with possible solutions
to the most common problems that the support desk observes.
WARNING:
!
Do not attempt inspection, maintenance, or service procedures other than those
specified in this manual. For service of internal components, it is necessary to
contact a factory trained and authorized service representative.
AVERTISSEMENT:
ne tente pas inspection, entretien, ou service autrement que ces a spécifié dans
ce manuel. Pour service d'interne pièces, c'est nécessaire contacter une Baie
Règle entraîné et autorisé service.
DANGER:
!
When problems are encountered which are beyond the scope and experience of
operating or service personnel, always request assistance from a factory trained
and authorized service representative. Improper servicing of the ProTech
Control System may result in equipment damage and/or personal injury or
death.
DANGER:
Quand problèmes sont rencontré qui sont au delà de l'étendue et expérience
d'opération ou , toujours demande d'une Baie Règle usine entraîné et autorisé
service . Déplacé entretenir de l'AProTech Contrôle peut résulter dans
équipement dommages personnel blessure ou mort.
DANGER:
DANGER:
Aucun opérateur est permis à l'intérieur du contrôle système et le contrôle
système . Echec obtenir la clôture d'opérateur peut résulter dans personnel
blessure ou mort.
DANGER:
!
Service personnel must remove power to the control system prior to making any
connections to terminals J11, J12, J13, J14, and J15. Failure to remove power
may result in equipment damage and/or personal injury or death.
DANGER:
Service doit enlever pouvoir au contrôle avant de faire n'importe quelles
connexions à terminaux J11, J12, J13, J14, et J15. Echec enlever pouvoir peut
résulter dans équipement dommages personnel blessure ou mort.
If motor does not energize at all, AND start sequence is completed, the ProTech will trip off the
compressor when the start sequence is complete and the stop sequence will execute. The Protection
history will display a “trip” for the motor running signal or motor amps < 10.
Check the start circuit wiring including terminal J12 on the main logic module (MLM), Emergency stop
wiring, and any relays wired to the main starter contactor. With the starter racked out, dry run the
compressor and verify that the indicator light on the MTR solid-state relay on the MLM turns on and that
any connected start relays are energized. The MTR indicator light will turn off quickly if there is no
motor running feedback signal.
If the MTR indicator light turns on at all, it indicates that, most likely, the ProTech controller is not the
source of the problem. Check the wiring, control relays, and starter.
If the MTR indicator light does not turn on at any point, then the problem lies with the ProTech control
system or related wiring. Verify that the wiring at J12 on the MLM is connected and that the E-stop is
not engaged. If the wiring is okay, then the solid-state relay or control output may have failed and the
SSR or MLM may need replaced.
SENSOR FAULT
Slave MLM not powered Power to slave modules, power all down, then
back up
A “short” status for a transmitter indicates that current loop for the device is greater than 20 mA.
An “open” status for a transmitter indicates that the current loop value is less than 3.8 mA and a wire
may be loose.
A “fail” status for a transmitter indicates that the current loop value is somewhere between zero and 4
mA. Try re-zeroing the transmitter if possible.
A ‘fault” status for any input indicates that the ProTech controller does not recognize the monitoring
point. Try resetting the controller by turning off the power for 5 seconds on all boards, then powering up
all boards simultaneously. If this does not resolve the problem, verify the input problem by checking the
device on an input that is currently working.
MOTOR OVERLOAD
Inlet valve control problems Smooth operation of inlet valve in auto mode
and manual valve control mode.
Current transformer (CT) problem CT reading normal
Starter Problem Check starter overloads
Motor Problem Check motor stator temperatures and current
imbalance
Inlet or Blow off Valve Performance Observe during automatic operation. Stop
compressor and test manual valve control,
review control air supply
Faulty Amperage or Kilowatt reading Monitoring point ready normal and reasonable
Failed inlet or blow off valve Normal valve operation, check supply air
Inlet and/or blow off valve poor operations Normal operation of inlet and blow off valve
Failed MLM blow off valve output Use electric meter to verify 4-20 mA or pulse AC
output depending on type of control action
!
WARNING:
Do not attempt inspection, maintenance, or service procedures other than those
specified in this manual. For service of internal components, it is necessary to
contact a factory trained and authorized service representative.
AVERTISSEMENT:
ne tente pas inspection, entretien, ou service autrement que ces a spécifié dans
ce manuel. Pour service d'interne pièces, c'est nécessaire contacter une Baie
Règle entraîné et autorisé service .
When contacting technical support, it is helpful to have the following information available before
calling:
Since the ProTech controller is specifically configured for each individual compressor application,
please be sure to supply the following information when ordering parts:
Parts Availability
ProTech modules are stocked for replacement purposes and are available for immediate shipment.
Standard instrumentation and control elements are also stocked for immediate service. Some specific
instrumentation and components supplied with engineered applications may require additional lead-
time to supply. Bay Controls may change the part number and/or may substitute a part of equal or
greater reliability.
Returning Parts
It is necessary to contact technical support for authorization before the return of any goods to the
factory. All approved returns are assigned a Return Materials Authorization (RMA) number to prevent
delays or loss of materials. Senders must include the RMA number on the outside of the package
whenever goods are being returned.
The ProTech Control System is implemented with a minimum number of high integration components
providing optimum reliability, simplifying service, and reducing the cost of maintaining spare parts.
Your ProTech Control System may have been retrofitted to a pre-existing control system and/or
packaged with other components by an authorized OEM, distributor, or by the end user. Information on
the other specific components packaged with your controller is beyond the scope of this manual. In this
case, refer to the information provided by the packager for replacement parts.
DANGER:
! Insure that all power is removed from the control system and that the compressor
motor is locked out before replacing modules. Failure to follow this procedure may
result in equipment damage and/or personal injury and death.
LE DANGER:
Assurer que tout pouvoir est enlevé du système de contrôle et que le moteur de
compresseur est hors verrouillé avant de remplaçant les modules. Echec suivre
cette procédure peut résulter dans équipement dommages personnel blessure et
mort.
CAUTION:
!
All connections to the ProTech modules use plug-in connectors. These
connectors are unidirectional and of differing sizes reducing the possibility of
incorrectly reconnecting modules, however, use care to insure that the correct
connections are made prior to applying power.
LA PRUDENCE:
Toutes connexions aux modules d'AProTech utilisent les connecteurs de
bouchon-dans. Ces connecteurs sont unidirectionnels et de différer de tailles qui
réduisant la possibilité de modules qui reconnectant inexactement, cependant,
le soin d'usage pour assurer que les connexions exactes sont faites avant la
demande de pouvoir.
1. Insure all power is removed from the control system, and the compressor motor is locked out.
2. Unplug the connectors to the module, make note of how the connector were plugged in.
3. Remove the nuts that secure the module to the enclosure.
4. Remove the module.
5. Install the replacement module using the nuts removed in step 3. Be sure to reconnect any
ground wires that were attached to the mounting stud of the User Interface Module.
6. Plug in the connectors.
7. Verify that the connections have been correctly made.
8. Apply power to the controller.
9. If the primary Main Logic Module was replaced, it will be necessary to set the software license
number and reload the controller software prior to use.
Chapter 2
ProTech V Series Control System
Initial Startup Guide
INTRODUCTION
The following document is intended to assist in the startup of air compressors with ProTech control
systems running the Version 5.0 operating system. The document provides the control system steps to
be taken during the initial compressor startup.
NOTE: Be sure that all of the compressor installation items are properly completed
before proceeding with this ProTech startup guide.
Supply power to the oil pump starter and check rotation of the oil pump. If the pump rotation
is incorrect, disconnect power and switch two of the oil pump leads at the starter.
If the Auxiliary oil pump is configured to be stopped when the compressor is stopped force
the pump on by setting the Set Point->Operator->Reset Oil Pump to YES.
Using ProTech Desktop, get the configuration from the ProTech panel and save it. Saving the
configuration synchronizes the laptop files with the existing ProTech configuration. In the ProTech
Desktop menus, select File -> New…and enter the license number and press Next. (the license number
can be obtained by pressing the View key on the ProTech controller and selecting the Information
page).
In the Choose Configuration dialog (shown below), select ‘Get from the ProTech Controller’ and press
Next. Note if your PC is not connected to the ProTech MLM you can not select ‘Get from the ProTech
controller’.
After the configuration is downloaded, the License Key Code dialog will be automatically filled in with
the correct Key Code from the ProTech controller.
When the upload to the PC is complete, the following dialog will appear. To complete the process, click
the FINISH button.
Note: To simplify the startup procedure, turn off the ProTechs access codes until the start up is
complete. The Access codes are accessed on the ProTech Desktop Security page. Set
each to ‘0000’.
Review Configuration
Using the ProTech Desktop; review the configuration. A review of the data on the General and the
Equipment screens will help to confirm the accuracy of the overall configuration. Using the “All” tab is
an easy way to verify that any optional monitoring and control options are configured as required for
your specific application.
Send Configuration
If any changes were made to the configuration, send the changes to the ProTech using the
ProTech Desktop menu “ProTech/Send Configuration”.
If the original ProTech configuration is desired, use the “Revert” function in the File/Revert menu.
Using the VIEW menu options on the ProTech Controller; check the following screens.
● Monitoring Points:
Check all points for valid Descriptions, Data and Status.
● Control Points:
Check all points for valid Descriptions, Data and Status.
● Protection (Running):
Check for correct Alarm and Trip set point values.
● Protection (Start-up):
Check Startup Protection for correct Alarm and Trip set point values.
● Permissive Startup Status:
Verify all permissive(s) are correct.
Test the Emergency Stop operation check for Ready to Not Ready change.
Start the compressor and measure the acceleration time to full speed
Record the acceleration time, in seconds, as this is required for proper control settings in
the ProTech and motor starter.
Hint: Setting the System Pressure Setpoint to 0 PSI will prevent the compressor from
automatically loading after the completion of the start sequence.
● Check the position of the compressor inlet valve, to make sure the compressor is not in
surge, or excessively loaded.
● Check all operating parameters for proper values (motor current, pinion vibration, oil
pressure, temperatures, air pressures, etc.).
Using the down key, review each parameter and change as desired. After entering the last parameter,
the tuning graph will appear, watch the responses as you change the Maximum Load set point with the
‘+’ and ‘-‘ keys.
Note: The Set Point and Scale Minimum and Maximum are in % of motor FLA.
Press the BACK key to access the tuning parameters. Continue tuning until a satisfactory response to a
step change is achieved.
CAUTION: Both control valves are placed in manual while changing the tuning parameters. No
surge or over pressure protection is being provided.
NOTE: For 4-20mA controlled valves the Maximum and Minimum Pulse width changes to Rate Limits
on the screen above.
MANUALLY CLOSE THE INLET VALVE AND TEST YOUR TUNING AT 90 % MOTOR LOAD AND
OBSERVE TIME TO ATTAIN SET POINT AND STABILITY
MANUALLY OPEN THE INLET VALVE TO FLA AND TEST YOUR TUNING AT 70 %
MOTOR LOAD AND OBSERVE TIME TO ATTAIN SET POINT AND STABILITY
At the Manual Valve Control page open the inlet to near FLA and press ENTER. Using the down key;
review each parameter, changing as desired. After entering the last parameter, the tuning graph will
appear. Watch the response. The Maximum Load set point is changed with the ‘+’ and ‘-‘ keys, forcing a
step response.
After entering the last parameter, the tuning graph will appear, watch the response. The discharge
pressure set point can be change with the ‘+’ and ‘-‘ keys, forcing a step response for the controller.
Press the BACK key to access the tuning parameters.
MANUALLY OPEN THE INLET VALVE TO FLA – OPEN THE BLOW-OFF VALVE AND TEST YOUR
TUNING AT DESIGN PRESSURE AND OBSERVE TIME TO ATTAIN SET POINT AND STABILITY
CAUTION: Both control valves are placed in “Manual” (frozen in place) while changing the tuning
parameters. No surge or over pressure protection is being provided. Be sure to return to Automatic
control mode when all tuning is completed.
Surge Testing
NOTE: When surge testing a compressor equipped with a solenoid (Open/Closed) blow-off valve, surge
testing will need to be done manually.
With the compressor in Manual control and blow-off valve closed, use the manual system block valve to
ramp the compressor toward surge.
After entering the fourth acquisition point, the Manual Valve Screen will be displayed. Open the inlet
100% and if a modulating blow-off valve is being used, close the blow-off valve to bring discharge
pressure to a point below surge pressure. If using a Digital (Open/Closed, solenoid) blow-off valve
leave the valve open.
Note: The Monitoring points displayed on the Manual Valve Control Screen may be changed in the Set
Point->Tools->Manual Valve Control Setup page.
Press ENTER and the blow-off valve will ramp closed, to allow discharge pressure to increase to the
natural surge point. As it is doing this, the following screen is displayed.
When the compressor surges, press ENTER, and the Surge Test Results screen will display the last 19
data points collected. Using the data on this screen, record the discharge pressure and motor current
just prior to surge.
The High Throttle Surge test defines the high operating pressure surge point. This surge point should
be taken 10 to 15 psi below the natural surge pressure. Access through (SET POINTS-
>Commissioning->High Throttle Surge Test). Using the down arrow key review each parameter,
changing as desired. The test Ramp rate is the rate the inlet valve closes during the test. The
acquisition points are typically those used for the Natural Surge Test.
The Manual Valve Control screen follows. Open inlet valve & press ENTER .
The ProTech will modulate the blow-off valve to control to the Surge Test Pressure. When the pressure
has stabilized, press Enter. The Surge Test in Progress screen appears, as the inlet valve ramps
closed while discharge pressure is maintained with the blow-off valve. When the compressor surges,
press Enter and record the High Throttle surge point.
Repeat the same process again, through (SET POINTS->Commissioning->Low Throttle Surge
Test). Set the surge test pressure at 80% of the Mid Throttle surge pressure, or the lowest expected
operating pressure.
Commissioning Settings
High, Mid and Low Surge Points: Define the actual compressor surge line and are set to
the values recorded during the surge tests.
Surge Control Offset: Defines the proximity (in Amps) between the actual surge line and
the Surge Control Line. Typically set at an amperage value 5 % greater than the Mid
Throttle Surge Point amps.
Discharge Pressure Limit: The maximum discharge pressure that the compressor is
allowed to operate. In the Auto Offline and Auto Standby control modes, ProTech will
modulate the blow-off valve to limit the discharge pressure to this value. In Auto Unload
mode, the compressor will unload if the discharge pressure reaches this setpoint.
Check Valve Offset: This setpoint is used to verify that the check valve has closed. The
value indicates the result of subtracting actual discharge pressure from actual system
pressure (typically 3 psig). The compressor will unload in Auto-Offline mode, or decrease to
the Standby pressure setting if in Auto-Standby mode.
Surge Count: Set to 0. This indicates the recorded number of surges. Each detected surge
will index the initial Surge Offset by the value of the Surge Watch Adapt setpoint.
Gain: The Gain setting is a multiplier used to adjust the SurgeWatch parameter. Gain
directly affects the results (doubling the Gain will double the SurgeWatch value at surge).
Set the Gain to achieve SurgeWatch point values exceeding 100 during a surge, while
remaining well below 100, when away from surge.
Standby Pressure Offset (Auto-Standby mode only): Defines the discharge pressure
that the compressor will maintain while blowing off with the check valve closed. The
discharge pressure maintained equals the System Pressure setpoint minus the Standby
Pressure Offset setpoint.
SurgeWatch Adapt: defines the amount that the surge line offest is adjusted in the event
of a surge. Total surge offset = Surge Offset + Surge Count x SurgeWatch Adapt.
You can use the ProTech Desktop to access the Performance control tab to set the additional
parameters shown below:
Control Parameters
Inlet Control Kp Ki
System Pressure: 9.00 3.00
Surge Control: 1.50 15.00
Maximum Current: 1.50 15.00
Mass Flow: 9.00 3.00
Rate Limits (+/-): 20.0 20.0
Date: 06-23-06
Time: 15:56:47
Auto-Unload is used when the compressor does not have a modulating blow off
valve. The compressor is unloaded when reaching the System Pressure Offset
setpoint.
Auto-Offline controls by modulating both the inlet and the blow-off valves to
maintain system pressure. The compressor unloads if the check valve closes
during blow off.
Constant Flow maintains a constant delivered flow to the process based on a flow
setpoint and supplied delivered flow signal.
Note: See Appendix C of compressor Handbook for complete description of control modes.
Set Point: In the pressure control modes, this is the System Pressure setpoint for the inlet
valve System Pressure control loop. In the Constant Flow mode, it is the inlet Constant
Flow loop setpoint.
Offset: In the pressure control modes, this establishes the blow-off valve’s System
Pressure Offset loop setpoint. In Constant Flow control this setpoint defines the Blow-off
Flow loop setpoint.
Strip Chart Speed: Sets the update rate of the strip chart portion of the performance
control screen.
Temporarily set the System Pressure setpoint a little bit higher than the actual system pressure to
ensure compressor loading. While tuning the System Pressure loops, it is important to have the highest
system pressure setpoint to ensure prevent other compressors in the system from interacting.
Place the compressor in automatic by pressing the Auto Key and watch the compressor’s performance
using the Performance View screen.
Observe the compressor’s operation in the automatic mode. If any additional tuning is required, access
the screens (SET POINTS->Commissioning->Commissioning Settings) and proceed as explained
previously.
Shutdown Compressor
To shutdown the compressor, press the Stop key. During the unload sequence note any compressor
surging. If the compressor surges during unloading, either
Observe the Stop sequence to verify correctness. Make any required changes.
Note: the compressor can not be restarted until the stopping sequence is complete.
The operating history should be reset after completing the startup. It is accessed in (SET POINTS-
>Tools>Edit Operation History). Change ‘Reset Operation History’ from No to Yes and press ENTER.
Obtain the final ProTech configuration settings using the ProTech Desktop menu “ProTech Get
Configuration”. Save it in a properly named folder.
In the “Security” screen of the Desktop, set the access codes and send the final configuration to the
ProTech controller.
If a question or situation develops which is not answered directly in this guide, contact Bay Controls for
more information.
The UIM is a full-page, back-lit liquid crystal LCD display with an integrated 15 key, tactile keypad. The
display provides detailed information on the operational condition and settings of the compressor.
One or more Main Logic Modules (MLM) are included in the panel. Each MLM contains a power supply, a
microprocessor, and I/O (input / output) channels. For applications that require increased I/O capacity, an
additional slave MLM may accompany a master MLM in a single control package.
Cleaning - If the MLM becomes dirty, use only a dry cloth to clean the part. Never apply water or any
solvent. If the display, or UIM, should become dirty, a mild detergent can be used for cleaning. Use a soft,
non-abrasive cloth to clean the display. Do not submerge any part.
Function Keys
LCD Display
Information Keys
This key group enables access to various display screens for viewing current compressor operation,
historical event data, and network information if applicable.
Function Keys
This key group lets the user operate the compressor and access certain screens for changing control
settings.
Information Keys
The four keys in this group provide access to informational screens that display current operating and
control data, historical logs and networking information. Accessing these view-only screens does not
affect operation of the compressor.
The descriptions and sample screens here show typical data from a specific compressor model and
configuration that may differ from your system.
Home
Press this key to display your selected Home page.
View
Pressing the View key opens the menu of available view pages. To go to a specific
screen, use the Up [] and Down [] keys to move to the desired page, then press Enter.
You can adjust the display contrast (or backlight) by pressing the Up or Down key while
holding down the View key.
View Pages
The following section describes typical view pages that are available. Due to differences in installations or
options purchased, your controller may have additional or different pages than those shown.
View Pages
Performance Control
Monitor Points
Control Points
Protection (Running)
Protection (Startup) Press Up and
Permissive Status Down keys to
Information navigate. Use
Auxiliary Control Enter key to select.
Performance Control
The Performance Control screen displays current information on the operating state of the compressor.
The three sections on the left side of this screen show, Inlet, Blow-Off, and Status. The two graphs on the
right show Pressure over Current and Pressure over Time. The box labels and contents that appear
depend on the control mode selected and options available.
Inlet [upper left]: Shows the inlet valve control mode and its activity or position.
Mode indicates the inlet valves current control loop or mode (Manual, Unload, System, Min Flow,
Max Load, Sys Flow.)
Position is the percentage of full modulation of the valve for applications with an analog (4-20mA)
controlled valve; for a modulating digital output, this shows relative move size.
The bar graph is a graphical representation of the relative position of the valve.
Blow-Off [middle left]: Shows the blow-off valve control mode and activity or position.
Mode indicates the inlet valves current control loop or mode (Manual, Unload, System, Dischg,
Standby, Sys Flow.)
Position is the percentage of full modulation of the valve for applications with an analog (4-20mA)
controlled valve; for a modulating digital output, this shows relative move size.
The bar graph is a graphical representation of the relative position of the valve.
Status [bottom left]: Shows the operating status of the compressor and relevant set point. The actual
items included in the status box will vary based on control method:
The vertical bar in the lower dynamic graph moves left to right and plots the system pressure over time.
Monitor Points
The Monitor Points screen shows the current the value or status for each configured monitoring point.
The monitoring points include all analog and digital inputs to the MLM along with some calculated values
and control outputs. Use the Up () and Down () keys to view the full list when more than 20 monitoring
points are available.
The Data and Status columns in the Monitor Points screen are dynamic and reflect the current condition
for each point.
Monitor Points
The value that appears in the Status column for each point reflects that point’s condition, as follows:
Normal: The signal is within the expected range for the sensor (for a 4-20mA sensor this
indicates a signal between 3.75 mA – 20.2 mA) and with in the expected operating range for the
monitored condition.
Open: No signal at all (0 mA), indicating device failure wiring problem or input channel failure.
Short: The input is shorted to 24 Volts (>20.25mA), indicating device failure, wiring problem, or
input channel failure.
Fault: For RTD inputs fault indicates either a miss wired or failed RTD. For the CT input indicates
over 5 amps of current.
Control Points
The Control Points screen shows the status and value of the ProTech configured outputs. Use the Up()
and Down() keys to view the full list, if more than 20 control points are available.
Control Points
Protection (Running)
The Protection (Running) screen displays all the monitoring points plus the alarm and trip values that
apply to each point when the compressor is in the running mode. Running protection levels take effect
upon completion of the start sequence and remain active until the stopping sequence begins.
Protection (Running)
Protection (Startup)
The Protection (Startup) page displays all of the monitoring points plus trip values that apply when the
compressor is in the starting mode.
The startup protection levels take effect when the Start Sequence issues the Start command. These
levels remain active until the Start Sequence has completed, at which point the Protection (Running)
criteria takes effect.
Protection (Startup)
Permissive Status
The Permissive Status screen displays the status of all permissives configured in Start Sequence. The
Sequence can begin only if Ready appears in the Status column for every item listed. A status of Not
Ready for any permissive item prevents the compressor from starting.
Permissive Status
Information
The Information screen displays the product serial numbers, ProTech software and hardware versions,
license numbers and installed options. The information is unique to the specific compressor system and
useful during compressor commissioning and for troubleshooting.
Information
Auxiliary Control
The Auxiliary Control feature of the ProTech enables up to four additional control loops (P&I) which can
be configured to control auxiliary devices such as a cooling water valve, heat tracing, and dampers. The
Auxiliary Control view screen shows the process variable, its set point and the control variable or output
for each of up to four auxiliary control loops.
Auxiliary Control
History Pages
Pressing the History key opens the menu that lists the history pages that are available
History Pages
Protection History
Event History
Operation History
Motor Trip History
Surge Test Results
Performance Log
Protection History
The Protection History screen shows a listing of all the most recent protection alarms and trips, each with
a date and time stamp. The type of monitoring point and its monitoring data are displayed in chronological
order, from newest to oldest. Up to 256 protection history events are stored in the ProTech controller. Use
the Up () and Down () keys to scroll through the entire list.
Protection History
Alarms and Trips are acknowledged by pressing the Home, View, History, or Network keys. This action
clears the display and turns off any associated alarm outputs (horn, light, pager etc), but it does not reset
the alarm. The alarm status returns to Normal only when the condition has been corrected and data from
the monitoring point no longer exceeds the alarm value.
Event History
The Event History screen shows a history of all control actions including start, stop, sensor faults, power
resets, set point adjustments initiated by an operator, the controller, or by network or remote devices. Up
to 256 events are stored with date and time stamp, type, source, and comment fields. Use the Up() and
Down() keys to page through the event data.
Event History
Operation History
The Operation History screen shows a breakdown of the compressor the compressor running hours along
with the hours of the operating state.
Operation History
Performance Log
This screen displays the Performance Log menu which the operator to select display a daily or monthly
performance log or accumulated compressor data for each of the most recent 24 hour period or for each
of the most recent months. This function is available only on systems with the ProTech Performance Log
Software option.
Performance Log
The Network key provides access to two menus, one for the optimal Compressor Network
package and the other for the standard Modbus Interface.
Network Pages
Compressor Network
Modbus Interface
Compressor Network
The Compressor Network screen is available if the Distributed Capacity Control (DCC) feature of the
ProTech was purchased. DCC networks several ProTech controllers to provide energy-saving automation
of the compressors through coordinated control, reduced blow-off, lower overall operating pressure, and
reduced compressor run time. The listed information shows status of the compressors in the network as it
pertains to their sequence of operation.
Compressor Network
Network Set Point: 95.0
## Pri Net Mode Motor Availability Pressure Set Point Power Time
01 02 Lead Running Automatic 95.1 95.0 123.2 007
02 04 Follow Stopped Start Ready 95.5 97.0 0.0 011
The following explains the data displayed on the Compressor Network screen:
Modbus Interface
The Modbus Interface screen enables the user to verify the Modbus mode and the quality of the
communication.
Modbus Interface
Access: Read-Only
Messages Received: 1247
Messages Sent: 1247
CRC Errors: 0
Function Errors: 0
The following explains the data displayed on the Compressor Network screen:
Access Defines the level of machine control allowed when using the
Modbus serial protocol.
The access levels are:
Read Only - Devices read information but not initiate control or
change Set Points
Read-Write - Devices change set points and initiate remote
control functions
Read-Write-DCC - Enables the distributed capacity control
network thru Modbus
Full Control - Allows full access
Function Keys
These keys are user to control the compressor and modify operating set points.
Start
Pressing the Start key initiates the compressor starting sequence. The ProTech controller
dynamically displays each step in the programmed start sequence. A typical start
sequence appears below.
Stop
Pressing the Stop key initiates the programmed compressor-stop sequence. The
dynamic screen below appears during the sequence and is similar to the screen you see
after you press Start.
Description Status
1: Motor Enable = OFF Completed
2: Motor Running = OFF Completed
Auto
Pressing the Auto key puts the compressor into the automatic control mode, where the
compressor responds automatically to changes in system demand in accordance with the
ProTech set points.
(The control method for each system is determined at the time of order to accommodate
the specific application. For information on control strategies and the methods available,
refer to the Control Logic Appendix.)
Unload
Pressing this key disables the Auto mode and immediately unloads the compressor by
opening the blow off valve and closing the inlet valve. The system continues to run in the
Unload mode and does not respond to either change in system demand or to any control
set point changes.
Set Points
Through this key, authorized users can access the various levels of set point control. The
first item on the opening set point menu (as shown below) permits the user to change the
language.
This function key provides access to a list of areas of set points that can be modified, and to switch to use
an alternate language. All but the first two screens, Change Language and Operator, are for the use of
authorized service personnel. Normal security settings for a typical system allow the operator/end user
access to only the first two functions. The remaining items listed are not discussed in this document.
Set Points
Change Language
Operator
Commissioning
Tools
Auxiliary Control
Compressor Network
Automatic Start/Stop
Change Language
The ProTech can be configured with two languages. English is always the primary language. The
secondary language, if desired, is selected during the commissioning of the controls. By highlighting this
menu choice and pressing Enter, the operator can toggle between English and the designated secondary
language. There is no additional screen associated with is function.
Operator
The Operator screen lets the user change some of the ProTech control settings as explained below.
Operator .
Date: 06-23-03
Time: 15:56:47
Operating Mode Selects the basic control mode for the compressor. Modes available
depend on the presence of certain instrumentation and the type of blow off
valve. Refer to the Control Logic appendix for a full description of the
ProTech control modes.
Set Point The system pressure control set point for ProTech control modes. For
constant flow control, Set Point is the delivered flow setting.
Offset A control setting slightly above the system pressure (or delivered flow) set
point. The compressor blow off control loop typically uses the offset set
point.
Home Page Sets the Home page from any of the View or History screens. The home
page is the screen that opens at the end of the start sequence.
Strip Chart Speed Sets the sweep speed of the dynamic Pressure vs. Time graph on the
Performance Control screen.
Options:
Fast 7 minutes
Medium 8 hours
Slow 1 day.
Date Current date, used to set the date.
Time Current time, used to set time.
Commissioning
This function is intended only for authorized service personnel at the time of initial start up and includes
screens for such items as:
Tools
This function allows the setting of various protective functions, manual control override options, and
software and firmware links within ProTech. All these tools are intended for authorized service personnel
only.
Raise or lower the value of any numeric or alpha character highlighted on a data
entry screen.
Toggle between two conditions (e.g.: ON/OFF; Alarm/Normal; Yes/No).
Manually step open or close the compressor inlet valve or inlet guide vanes.
(Requires access to Set Points / Tools screen)
Enter:
Opens a highlighted field or screen.
Advances the cursor to the next entry data field or to the next digit within a data
entry field.
Back:
Returns to the previous display screen.
Moves the cursor back within a particular selection screen or data entry field.
Note - Using either of these keys to move away from a page confirms the
changed/displayed values.
Up and Down
This pair of keys work together as follows:
Note: To adjust the LCD display contrast, use the Increase and Decrease keys, while
holding down the View key.
Each ProTech control method uses compressor inlet and blow off valve control loops, and their
associated control set point to match the compressor’s output to the system air requirement.
*Note: Auto-Offline, Auto-Standby and Constant Flow modes require a modulating blow off valve.
An overview of each control mode and each control loop is provided in the following pages.
Auto-Offline Control
With Auto-Offline Control, the inlet valve is modulated to satisfy the System Pressure set point, within the
constraint of the Maximum Motor Load set point. In cases of low demand, the control throttles back to the
Surge Control Offset line. At this point, the control will modulate the inlet valve to allow the actual system
pressure to increase to the System Pressure Offset set point.
If the compressor output still exceeds demand, ProTech begins its blow off control loop, by modulating
the compressor blow off valve. If blow off increases to the point that the discharge check valve closes; the
compressor will unload. The compressor will automatically reload as soon as the system pressure decays
to the original System Pressure set point value.
Auto-Standby Control
This control mode operates in the same manner as Auto-Offline until reaching the System Pressure
Offset set point. Then, if the check valve closes during blow-off, Auto–Standby does not unload the
compressor. Instead, it continues to open the blow off valve until the compressor’s discharge pressure
drops to the Standby Pressure Offset set point. This method allows the unit to quickly load when the
system pressure drops below the System Pressure set point.
1. During the loading sequence, the inlet valve is opened to achieve the System Pressure set point, at
the maximum allowable flow and power (position 1)
2. If the compressor output exceeds the demand, the Inlet System Pressure control loop throttles the
inlet valve to the Surge Control Offset line (pos. 2).
3. If the compressor output still exceeds demand, the Inlet Surge Control loop modulates the inlet valve
to allow system pressure to increase to the System Pressure Offset point (pos. 3).
4. At that point (pos. 3), control switches to the Blow Off System Pressure control loop, which begins to
modulate the compressor blow off valve. If blow off increases to the point that the discharge check
valve closes, Auto-Standby continues to modulate the blow off valve open, until the compressor
discharge pressure drops to the Standby Offset set point (pos. 4).
5. When the system pressure drops below the System Pressure set point, the blow off valve closes, and
normal control is resumed.
Auto-Unload Control
This control mode operates in the same manner as Auto-Offline until reaching the System Pressure
Offset set point. Then, the compressor is automatically unloaded (blow-off valve fully opened, inlet valve
to the close position). The compressor remains unloaded until the system pressure falls below the System
Pressure set point. It will then be automatically reloaded.
This control mode is only used on compressors that do not have a modulating blow off valve.
1. During the loading sequence, the inlet valve is opened to achieve the System Pressure set point, at
the maximum allowable flow and power (position 1)
2. If the compressor output exceeds the demand, the Inlet System Pressure control loop throttles the
inlet valve to the Surge Control Offset line (pos. 2).
3. If the compressor output still exceeds demand, the Inlet Surge Control loop modulates the inlet valve
to allow system pressure to increase to the System Pressure Offset point (pos. 3).
4. At that point (pos. 3), the Auto-Unload control method unloads the compressor by first fully opening
the compressor blow-off valve, and then closing the inlet valve to its minimum position (pos.4).
5. The compressor automatically reloads when system pressure drops below the System Pressure set
point.
1. During the loading sequence, the inlet valve is opened to achieve the System Flow set point, at the
maximum allowable flow and power (position 1)
2. If demand is within the turndown range of the compressor, the inlet valve maintains the delivered flow
(position 2).
3. If the required flow is less than Inlet Minimum Load (as determined by the Surge Control line), then
the inlet controls to the surge control line.
4. If the delivered flow increases to the point that the Blow off System Flow is exceeded, the blow off
valve is modulated to maintain flow at that set point. (position 3).
In the case of ProTech’s Pressure Control modes, (Auto-Offline, Auto-Standby and Auto-Unload), the
control loops and set points are:
In the case of ProTech’s Flow Control mode (Constant Flow), the control loops and set point are:
NOTES:
1. The surge control point is a function of the actual discharge pressure, the entered surge points
and the Surge Control Offset set point.
2. The Blow Off System Pressure set point is equal to the System Pressure set point plus the
System Pressure Offset set point.
3. Blow Off System Flow is equal to the System Flow Set point plus the System Flow Offset set
point.
B
Pressure
System
System Pressure Set
Pressure Point
A Standby Offset
Pressure Standby
Offset Pressure
Maximum
Motor Load
In this control loop, the inlet valve is controlled along the surge control line, allowing the system
pressure to increase to the Blow Off System Pressure set point. When this value is reached, control is
transferred to the blow off valve loops
The Maximum Discharge Pressure control loop, and its corresponding Discharge Pressure Limit set
point come into play under certain compressor operating conditions. This control loop provides a fast
response when the discharge pressure climbs suddenly. This can occur because of a sticking check
valve, closed block valve, or plugged dryer. The setting of the Discharge Pressure Limit set point is a
value below the natural high-pressure surge point of the compressor.
This guide contains the basic information necessary to interface the ProTech control system with plant
automation systems, Man-Machine-Interface (MMI) software, and other data logging systems using the
Modbus communications interface. However, since installations may vary, these instructions may not
cover all details or variations in the equipment supplied or every question that may arise during use.
More detailed information on the Modbus protocol is available using the desktop under
Help/Documents.
Installation
The communications interface is installed by connecting the Modbus Network Port, connector J9 on the
ProTech Main Logic Module (MLM), to the plant, MMI, or other equipment. The ProTech operates as
the slave device, the plant system or MMI operates as the Master device.
The physical link uses an RS-485 two-wire, half duplex, serial communications interface. The RS-485
standard defines the signal levels and other characteristics of the physical link. The equipment that is to
be connected to the ProTech must implement this same RS-485 standard. Refer to the documentation
of master device to be connected to confirm the standards used and how the connections are made.
The connection must be made using 22 Gauge, twisted 3-wire shielded cable, such as Belden # 3108A,
or equivalent.
The positive terminal on the ProTech is connected to the positive terminal on the master device, and
the negative terminal to the master negative terminal. The COM terminal on the ProTech is connected
to the common terminal on the master device. The common connection is used to insure that both
pieces of equipment have the same signal reference level.
Up to thirty one (31) ProTech controllers can be connected together with the master device. The
ProTech controllers should be connected together in a daisy chain and then connected to the master
device at one end.
The RS-485 standard specifies the maximum length of the physical connection at 5000 feet (1524
meters) between the farthest connections.
It is recommended that a RS-485 isolator be installed between the network of ProTech controllers and
the Master device if the Master is located in a different building, if the Master may have a different
ground reference, or if problems are experienced reliably communicating between the Master and
ProTech(s).
There are a number of RS-485 isolators that will work well for this application. The Westermo RD-48
repeater has been tested and known to work well in this application. Refer to www.westermo.com, also
available through Industrial Networking Solutions 800-889-1461, and Gross Automation 262-446-0000.
Configuration
The Modbus interface on the ProTech controller must be configured to match the speed and data
format used by the master device. If multiple ProTech controllers are connected together, they must all
be configured to use the same speed and data format.
The ProTech Desktop software is used to configure the ProTech controller. The Communications Tab
on the desktop contains the Modbus settings. The communication speed is in bits per second, referred
to as Baud rate. The data format is expressed as the number of data bits followed by the parity type,
and then the number of stop bits. The parity can be Even, Odd, or None. Set the ProTech Modbus
speed and data format to match that used by the master device. Refer to the online help in the ProTech
Desktop for more information.
The Modbus access is selected based on what type of functionality you wish to implement from the
master device. The default is Read-Only which prevents the master from changing any setting or
executing any control function in the ProTech. Refer to the online help in the ProTech Desktop for more
information.
Modbus Protocol
The Modbus protocol describes an industrial communications and distributed control system developed
by Gould-Modicon to integrate PLC’s, computers, terminals, and other monitoring, sensing, and control
devices. Modbus is a Master/Slave communications protocol, whereby one device, (the Master),
controls all serial activity by selectively polling one or more slave devices. The protocol provides for
one master device and up to 247 slave devices on a common line. Each device is assigned an address
to distinguish it from all other connected devices. The RS-485 physical link used by the ProTech limits
the maximum number of slave devices to 31.
Only the master initiates a transaction. Transactions are either a query/response type, (only a single
slave is address), or a broadcast/no response type, (all slaves are addressed). A transaction
comprises a single query and single response frame or a single broadcast frame.
Certain characteristics of the Modbus protocol are fixed, such as the frame format, frame sequences,
handling of communications errors and exception conditions, and the functions performed.
Other characteristics are user selectable. These include a choice of transmission media (physical link),
baud rate, character parity, number of stop bits, and the transmission modes, (ASCII or RTU). The
ProTech only supports the RTU transmission mode of the Modbus protocol.
Synchronization
Frame synchronization can be maintained in RTU transmission mode only by simulating a synchronous
message. The receiving device monitors the elapsed time between receipt of characters. If three and
one-half character times elapse without a new character or completion of the frame, then the device
flushes the frame and assumes that the next byte received will be an address.
Message Format
A transaction consists of a single request from the master to a specific slave device, and a single
response from that device back to the master. Both of these messages, request and response, are
formatted as Modbus message frames. Each message frame consists of a series of bytes grouped into
four fields as described below:
Address Field
The address field immediately follows the beginning of frame and consists of one byte. This byte
indicates the user assigned address of the slave device that is to receive the message sent by the
master.
Each slave must be assigned a unique address and only the addressed slave will respond to a query
that contains its address. When the slave sends a response, the slave address informs the master
which slave is communicating. In a broadcast message, an address of 0 is used. All slaves interpret
this as an instruction to read and take action on the message, but not to issue a response message.
The slave address is configured for the ProTech using the ProTech Desktop software, in the General
Tab. The Unit Number specifies the Modbus slave address.
Function Field
The Function field tells the addressed slave (ProTech) what function to perform. Modbus function
codes are specifically designed for interacting with a PLC on the Modbus industrial communications
system. The high order bit in this field is set by the slave device to indicate an exception condition in
the response message. If no exceptions exist, the high-order bit is maintained as zero in the response
message.
Data Field
The data field contains information needed by the slave (ProTech) to perform the specific function or it
contains data collected by the slave in response to a query. This information may be values, address
references, or limits. For example, the function code tells the slave to read a holding register, and the
data field is needed to indicate which register to start at and how many to read.
This field allows the master and slave devices to check a message for errors in transmission.
Sometimes, because of electrical noise or other interference, a message may be changed slightly while
it’s on its way from one device to another. The error checking assures hat the slave or master does not
react to messages that have changed during transmission. This increases the safety and the efficiency
of the Modbus system. The error check field uses a CRC-16 algorithm in the RTU mode.
Error Detection
There are two types of errors which may occur in a communications system: transmission errors and
programming errors. The Modbus system has specific methods for dealing with either type of error.
Communications errors usually consist of a changed bit or bits within a message. The most frequent
cause of communications errors is noise: unwanted electrical signals in a communications channel.
These signals occur because of electrical interference from machinery, damage to the communications
channel, impulse noise, (spikes), etc. Communications errors are detected by character framing, a
parity check, and a redundancy check.
When the character framing, parity, or redundancy checks detect a communications error, processing
of the message stops. A ProTech will not act on or respond to the message. (The same occurs if a
non-existent slave address is used.)
When a communications error occurs, the message is unreliable. The ProTech cannot know for sure if
this message was intended for it. So the ProTech might be answering a message which was not its
message to begin with. It is essential to program the Modbus Master to assume a communications
error has occurred if there is no response in a reasonable time. The length of this time depends upon
the baud rate, type of message, and scan time of the ProTech. Once this time is determined, the
master may be programmed to automatically retransmit the message.
The Modbus system provides several levels of error checking to assure the quality of the data
transmission. To detect multibit errors where the parity has not changed, the system uses the Cyclical
Redundancy Check (CRC).
Exception Responses
Programming or operation errors are those involving illegal data in a message, no response from the
ProTech to the master, or difficulty in communicating with a ProTech. These errors result in an
exception response from either the master or the ProTech, depending on the type of error.
The exception response codes are listed below. When a ProTech detects one of these errors, it sends
a response message to the master consisting of the slave address, function code, error code, and error
check fields. To indicate that the response is a notification of an error, the high-order bit of the function
code is set to one.
Memory Notation
Data points in the ProTech are referenced in the same manner as points in a Modicon PLC. This
notation allows for four different types of data: coils, discrete inputs, input registers, and holding
registers. Register variables consist of two bytes, while coils and discrete inputs are single bits. The coil
and discrete input data types are not used as they have no application to a ProTech controller.
Each function references only one type of data and uses a relative address in the message frame with
a zero offset. For example, holding register 40001 relative address is 0000, input register 30003 relative
address is 0002, and so on.
The read holding registers function is used to obtain the values of set points, and status information
from a ProTech controller. The format of the request frame is as follows:
REQUEST FRAME
ADDRESS FUNCTION STARTING REGISTER ERROR
CODE REGISTER COUNT CHECK
1 BYTE 1 BYTE 2 BYTES 2 BYTES 2 BYTES
PROTECH 03 SEE NUMBER OF CRC-16
UNIT HOLDING REGISTERS
NUMBER REGISTER
MAP
The starting register number is shown in the following table. The register count specifies how many
consecutive register values will be returned in the response message. An exception message will be
returned when specifying a register number that is not defined. Note that the message frame uses
relative addressing; see Memory Notation above for more information.
Notes:
1. Data is formatted as a signed integer in the range of -32767 to 32767. There is an implied
decimal point based upon the configuration of the corresponding monitoring point. The set point
is expressed in engineering units configured for the associated monitoring point. Refer to the
ProTech controller configuration. For example, if the ProTech is configured for the System
Pressure monitoring point with a precision of 1 and units of PSI, then a register value of 1123
indicates 112.3 PSI.
RESPONSE FRAME
ADDRESS FUNCTION BYTE DATA ERROR
CODE COUNT CHECK
1 BYTE 1 BYTE 1 BYTES VARIABLE 2 BYTES
PROTECH 03 NUMBER OF SEE CRC-16
UNIT REQUESTED HOLDING
NUMBER REGISTERS REGISTER
X2 TABLE
The response message contains a variable length data field that is equal to the number of registers
requested multiplied by 2. The registers are ordered consecutively in the data field as 2 byte values;
high byte followed by low byte.
Exceptions
Exception code 02 is returned if the registers requested are not defined. Note that the protection set
point registers are defined based upon the configuration in the ProTech controller.
REQUEST FRAME
ADDRESS FUNCTION STARTING REGISTER ERROR
CODE REGISTER COUNT CHECK
1 BYTE 1 BYTE 2 BYTES 2 BYTES 2 BYTES
PROTECH 4 SEE INPUT NUMBER OF CRC-16
UNIT REGISTER REGISERS
NUMBER MAP
Notes:
1. Monitoring point data is formatted as a signed integer in the range of -32767 to 32767 with an
implied decimal point determined by the ProTech configuration. The value is expressed in the
engineering units configured for the respective point. Refer to the ProTech monitoring point
configuration listing. Digital points are expressed as 0 for the OFF or inactive state, and 1 for
the ON or active state.
2. Control point data is formatted as an unsigned integer in the range of 0 to 65535. Refer to the
ProTech control point configuration listing. Digital points are expressed as 0 for the OFF or
inactive state, and 1 for the ON or active state.
3. An unsigned integer indicating the number of monitoring points that are in the faulted state.
4. Monitoring point status is an unsigned integer enumerated as follows:
0 Normal
1 Alarm
2 Open
3 Short
4 Fault
5 Fail
5. The ProTech software version is expressed as two unsigned integer bytes. The high byte
contains the major version number; the low byte contains the minor version number.
RESPONSE FRAME
ADDRESS FUNCTION BYTE COUNT DATA ERROR
CODE CHECK
1 BYTE 1 BYTE 1 BYTE VARIABLE 2 BYTES
PROTECH 4 SEE MAP SEE MAP CRC-16
UNIT TABLE TABLE
NUMBER
The response message contains a variable length data field that is equal to the number of registers
requested multiplied by 2. The registers are ordered consecutively in the data field as 2 byte values;
high byte followed by low byte.
Exceptions
Exception code 02 is returned if the registers requested are not defined. Note that the monitoring and
control point registers are defined based upon the configuration in the ProTech controller.
REQUEST FRAME
ADDRESS FUNCTION REGISTER REGISTER ERROR
CODE NUMBER DATA CHECK
1 BYTE 1 BYTE 2 BYTES 2 BYTES 2 BYTES
PROTECH 06 SEE PRESET SEE CRC-16
UNIT REGISTER REGISTER
NUMBER MAP MAP NOTES
Notes:
1. Data is formatted as a signed integer in the range of -32767 to 32767. There is an implied
decimal point based upon the configuration of the corresponding monitoring point. The set point
is expressed in engineering units configured for the associated monitoring point. Refer to the
ProTech controller configuration. For example, if the ProTech is configured for the System
Pressure monitoring point with a precision of 1 and units of PSI, then a register value of 1123
indicates 112.3 PSI.
2. Set the motor start register to 1 to start the compressor, 0 to stop the compressor.
3. Set the alarm acknowledge register to 1 to acknowledge and silence the alarm.
4. An unsigned integer in the range of 1 to 32.
5. An unsigned integer greater than or equal to 1 that expresses a time value in seconds.
6. An unsigned integer greater than or equal to 1 that expresses a time value in minutes.
7. The capacity control mode is enumerated as follows:
0 Automatic
1 Unload
2 Base Load
8. The auto start lockout is enumerated as follows:
0 Normal – Automatic start and stop are enabled.
1 Bypass – Disabled but will be re-enabled on successful start.
2 Locked – Automatic start and stopped are disabled.
RESPONSE FRAME
ADDRESS FUNCTION REGISTER REGISTER ERROR
CODE NUMBER DATA CHECK
1 BYTE 1 BYTE 1 BYTES 2 BYTES 2 BYTES
PROTECH 06 SAME AS SAME AS CRC-16
UNIT REQUEST REQUEST
NUMBER FRAME FRAME
The response frame is the same as the request message; returned to indicate that the specified
holding register was set to the data value in the request message.
Exceptions
Exception code 02 is returned if the registers requested are not defined. Note that the protection set
point registers are defined based upon the configuration in the ProTech controller.
Exception code 03 is returned if the register data is out of range or invalid for the specified holding
register.
REQUEST FRAME
ADDRESS FUNCTION DIAGNOSTIC DATA ERROR
CODE CODE VALUE CHECK
1 BYTE 1 BYTE 2 BYTES 2 BYTES 2 BYTES
PROTECH 08 0000 TEST DATA CRC-16
UNIT
NUMBER
RESPONSE FRAME
ADDRESS FUNCTION DIAGNOSTIC DATA ERROR
CODE CODE VALUE CHECK
1 BYTE 1 BYTE 2 BYTES 2 BYTES 2 BYTES
PROTECH 08 0000 TEST DATA CRC-16
UNIT
NUMBER
The response frame is identical to the request frame if the test is successful. Typically the data value is
checked in the response to confirm the same as the value sent. Successful completion of this test
confirms that the physical and protocol layers of the communication system are functioning properly.
Exceptions
Exception code 01 is returned if a diagnostic code other than 0000 is specified in the request frame.
Plant automation systems and/or other master devices that were configured to interface with a Quad 2000
controller will need to be modified for interfacing with the ProTech. The following configuration changes need to
be made in the master device:
1. The address of the data points need to be configured in the master to point to the new locations
in the ProTech. Refer to the ProTech Modbus Memory Map. Also there is additional information
available in the ProTech; you may want to add data values into the master system.
2. All of the data in the ProTech controller is expressed in engineering units. The data in the Quad
2000 had to be scaled by the master into the appropriate units to have meaning. The
temperature RTD inputs in the Quad 2000 required a look up table to translate the data value
into engineering units. The data scaling functions should be turned off in the master when using
the ProTech as they are not needed.
The following table shows the ProTech data and control functions addressed as data points in a
Modicon PLC.