Ngd-1-7035 Sgt2b MK 400v Supplies

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Date : 27.07.

2016 Rev : A RK Checked


d: MP

Document : SGT2
2B MK 400V Supplies
S Cable Sizing Calculaations Approved
d: GP

SG
GT2B M
MK 400
0V Sup
pplies C
Cable Sizing
S Calcul ations
Con
nsulting & Strateg
gic Infrasttructure

Pro
oject: Foursstones 49
9.9MW Connectio
C on Works
ks
Customer N
Name: National Grid
Site: 275kVV Fourstoones

ocument Title:
Do SGT2
2B MK 40 00V Supp
plies Cab
ble Sizing
g Calculations
Do
ocument:: NGD--1-7035

Revisio
on Revisio
on Details Da
ate Prepared Checked
d Apprroved
A First isssue 27.07.2016 RK MP G
GP

3rd Floo
or, Victory Poiint, Nelson Co
ourt, Staffordshire Technolog
gy Park, Staffford, ST18 0WQ
Date : 27.07.2016 Rev : A RK Checked : MP

GP
Document : SGT2B MK 400V Supplies Cable Sizing Calculations Approved :

1. The SGT2B Marshalling Kiosk 400V supply will be fed from the LVAC Switchboard in the NG Control Building.
The circuit Parameters are as follows:

Circuit
Cable Voltage Cable
Voltage Design Current Circuit Protect Protective Derating
Cable Type Length Drop Calculated
(V) (Ib, Amps) Device Type Device Rating factors
(m) (Volts, %)
(In, Amps)
Copper,
400, XLPE 90°, Trench
17.5* BS88-2 63 130 1.79, 0.78 25mm², 4c
3ph+N SWA installation
Armoured

*Load data is taken from HICO transformer drawing number: ET5A100521S02 SHT3. REV.A, National Grid drawing number:
42_AME_0135

2. Calculation details:

3. Cable size shall be 4 core, 25mm², 90° Thermosetting (Copper), Armoured SWA to provide 17.5Amp load.

page 2