Professional Documents
Culture Documents
Bettis RTS
Bettis RTS
PDS-02-04-60-1691-EN Rev. 3
December 2022
Main Features
Smart mechanical fail-safe quarter-turn actuator Figure 1. Bettis RTS FQ Series Cut-away
Mechanical driven fail-safe operation for reliability and safety
No battery or super-capacitor dependency for fail-safe action
Direct coupling of the fail-safe with the valve shaft
On/Off: Class A and B, ISO 22153
(S2-15 min. motor duty, IEC 60034)
Modulating: Class C and D, ISO 22153
(S4-1200 cycles/hr and S9-Continuous duty, IEC 60034)
Adjustable speed and torque
Fail-safe triggering selectable in case of drop-off 24 V DC
fail-safe signal or main power supply
Independently adjustable soft starts/stops
Reliable and high positioning control 0.1% accuracy
DC, single phase, three phase power supply options
Weatherproof and explosion proof construction options
SIL3 capable
Optional De-clutchable Handwheel
Local User Interface with wireless Bluetooth capability for
configuration, monitoring, and diagnostics of key parameters
DCMlink software interface available
Process Control via optional on-board PID Controller
Multilingual user interface
Configurable action on loss of control signal
3
Bettis RTS FQ Series Product Data Sheet
December 2022 PDS-02-04-60-1691-EN Rev. 3
Features
Figure 2. Local Display, Status and Configuration
4
Product Data Sheet Bettis RTS FQ Series
PDS-02-04-60-1691-EN Rev. 3 December 2022
Analog in and out uses the actuator's control unit common ground
5
Bettis RTS FQ Series Product Data Sheet
December 2022 PDS-02-04-60-1691-EN Rev. 3
Nominal Motor Current, Amps 4.6 1.47 0.46 4.6 1.47 0.46
Electric Max Torque Class A/B, ft-lb (Nm) 221 (300) 443 (600)
Max Shaft Diameter Acceptance, in. (mm) 1.0 (25) 1.57 (40)
Ambient Temperature Range, °F (°C) -40 to +140 (-40 to +60) -40 to +140 (-40 to +60)
Water Ingress Protection (3) IP66 (NEMA 4X), IP67 (NEMA 6), IP68 IP66 (NEMA 4X), IP67 (NEMA 6), IP68
Duty Cycle Class A/B Standard, C/D Optional Class A/B Standard, C/D Optional
High quality two component polyurethane High quality two component polyurethane
Coating and Color paint system - C2 ISO12944-5/RAL7012 paint system - C2 ISO12944-5/RAL7012
Other options available on request. Other options available on request.
Notes:
1. 24 V DC power supply characteristics are applicable for BLDC version 10.1 and higher.
2. At ambient temperatures below -4 °F (-20 °C), the f ail-safe spring operating time will increase.
3. CM32 and CM64 base units IP68 immersion: 5 m (16 feet) 21 days. All bolt-on gear boxes (linear drives, QT planetary gears, fail-safe units) are not
IP68 rated and need to be rebuilt in case of a flood event.
6
Product Data Sheet Bettis RTS FQ Series
PDS-02-04-60-1691-EN Rev. 3 December 2022
Electric Max Torque Class A/B, ft-lb (Nm) 738 (1000) 1475 (2000)
Max Travel Not Available 90° +/-5° Not Available 90° +/-5°
Max Shaft Diameter Acceptance, in. (mm) 1.93 (49) 2.36 (60)
Ambient Temperature Range, °F (°C) -40 to +140 (-40 to +60) -40 to +140 (-40 to +60)
- - - -
NEC-505 - NEC-505 -
Explosion Proof Certifications
- - - -
Notes:
1. 24 V DC power supply characteristics are applicable for BLDC version 10.1 and higher.
2. At ambient temperatures below -4 °F (-20 °C), the fail-safe spring operating time will increase.
3. CM32 and CM64 base units IP68 immersion: 5 m (16 feet) 21 days. All bolt-on gear boxes (linear drives, QT planetary gears, fail-safe units) are not
IP68 rated and need to be rebuilt in case of a flood event.
7
Bettis RTS FQ Series Product Data Sheet
December 2022 PDS-02-04-60-1691-EN Rev. 3
Electric Max Torque Class A/B, ft-lb (Nm) 2213 (3000) 3688 (5000)
Max Travel Not Available 90° +/-5° Not Available 90° +/-5°
Max Shaft Diameter Acceptance, in. (mm) 2.36 (60) 2.95 (75)
Ambient Temperature Range, °F (°C) -40 to +140 (-40 to +60) -40 to +140 (-40 to +60)
- - - -
NEC-505 - NEC-505 -
Explosion Proof Certifications
- - - -
8
Product Data Sheet Bettis RTS FQ Series
PDS-02-04-60-1691-EN Rev. 3 December 2022
Step-down converter
Non Fail-Safe Fail-Safe Bus System Enabled Bus system TCP
(400 V module)
1xM40,
1xM32,
2xM32,
1xM25
1xM40, 1xM40, 1xM40, 1xM25
+
Standard/WP 1xM32, 1xM32, 1xM32, + additional 4xM20
2xM12 connector
1xM25 1xM25 1xM25 (different connector
directly on housing
housing)
(different actuator
housing)
9
World Area Configuration Centers (WACC) offer sales support, service,
inventory and commissioning to our global customers.
Choose the WACC or sales office nearest you: