Supply and control voltage levels

EVM II
EVM Energía del Valle de Mexico II
Combined Cycle Power Plant

Cross checked
Department Name Date Signature

Revision History
Rev. Revision Date Created by Checked by Approved by Brief Description

Description current Revision

Owner Contractor

General Electric (Switzerland) GmbH


GE Power Systems Inc.
GE Global Services GmbH
Replaces Customer Code Project Document Code
EMX/00/E/001b---004/GS/001
Responsible Dept. Created by Checked by Approved by Format
GS-EE J. Menzel R. Hug J. Huser DIN A4
Document Type Document Status
GE POWER GS Invalid
Gas Power Document Title Identification Number
Systems Supply and control voltage levels 1GP006533
Rev. Date Lang. Sheet
A 2017-06-23 en 1/6
GE CLASS II (INTERNAL NON-CRITICAL)
© COPYRIGHT 2017 General Electric Company
All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company
and/or its affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All recipients of this information shall be
deemed to have agreed not to make duplications, reproductions of any nature by any means, modifications, disclosures, or use any portion of
this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.
Invalid

Table of Contents:

0. REVISION CHECK ............................................................................................................................................... 3


1. OBJECTIVE ........................................................................................................................................................... 4
2. SCOPE OF APPLICATION.................................................................................................................................. 4
3. REFERENCE DOCUMENTS ............................................................................................................................... 4
4. CODES AND STANDARDS ................................................................................................................................ 4
5. VOLTAGES AND FREQUENCIES ..................................................................................................................... 5

GE POWER Identification Number: Rev. Date Lang. Sheet


Gas Power Systems 1GP006533 A 2017-06-23 en 2/6
© COPYRIGHT 2017 General Electric Company GE CLASS II (INTERNAL NON-CRITICAL)
All rights reserved. The information herein is Proprietary and Technically Exclusive content of the General Electric Company and/or its legitimate
affiliates.
Invalid

0. REVISION CHECK

ISSUE NAME
Prepared: J. Menzel 2017-06-23
A Checked: R. Hug
Released: J. Huser

CHANGES
PAGE NO ITEM

GE POWER Identification Number: Rev. Date Lang. Sheet


Gas Power Systems 1GP006533 A 2017-06-23 en 3/6
© COPYRIGHT 2017 General Electric Company GE CLASS II (INTERNAL NON-CRITICAL)
All rights reserved. The information herein is Proprietary and Technically Exclusive content of the General Electric Company and/or its legitimate
affiliates.
Invalid

1. OBJECTIVE

This Technical Specification defines the supply and control voltages, frequencies and their tolerances
as well as the system earthing for the auxiliary power distributions in the Combined Cycle Power
Plant EVM II.

2. SCOPE OF APPLICATION
This Technical Specification is valid for Turbine Auxiliaries, Power Island and the Balance of Plant
(BoP) Systems in the Project EVM II.

3. REFERENCE DOCUMENTS

 Single Line Diagram EMX/00/E/001b---004/SD/001

4. CODES AND STANDARDS

1. IEC 60034-1, 2010-02


Rotating electrical machines
Part 1: Rating and Performance

2. IEC 60038, 2009-06


IEC Standard Voltages

3. IEC 60204-1, 2005-10


Safety of machinery — Electrical equipment of machines —
Part 1: General requirements

4. IEC 60364-1, 2005-11


Low-voltage electrical installations —
Part 1: Fundamental principles, assessment of general characteristics, definitions

5. IEC Guide 106, 1996-07


Guide for specifying environmental conditions for equipment performance rating

GE POWER Identification Number: Rev. Date Lang. Sheet


Gas Power Systems 1GP006533 A 2017-06-23 en 4/6
© COPYRIGHT 2017 General Electric Company GE CLASS II (INTERNAL NON-CRITICAL)
All rights reserved. The information herein is Proprietary and Technically Exclusive content of the General Electric Company and/or its legitimate
affiliates.
Invalid

5. VOLTAGES AND FREQUENCIES

Table 1 defines the voltages and frequencies for alternating current (AC) and direct current (DC)
systems, the applicable tolerances and the system earthing.
Distribution Boards/ Loads/
Remark
Supply 1 Consumers 2
Frequency
Frequency 60 Hz 60 Hz
Tolerance +4% / –5% +4% / –5%
AC Voltages
Medium Voltage
Voltage 6'900 V 6'600 V
Tolerance +5 % / –15 % +10% / –10% For Motor Start: – 20 % at terminals
System earthing Resistance earthed,
10  , 400 A/10sec {ON HOLD} Motor Heaters: 127 V AC, 1-phase,
Distribution network 3 phases, 3 wires (L1, L2, L3) 3 wires (L, N, PE)
Low Voltage three-phase
Voltage 600 V3 575 V Motors
Tolerance +5% / –15% +10% / –10% Loads > 63 A without Neutral4
System earthing Solidly earthed, TN-S System
Distribution network 3 phases, 4 wires For Motor Start: – 25% at terminals
(L1, L2, L3, PE)
Motor Heaters: 127 V AC, 1-phase,
3 wires (L, N, PE)
Voltage 480 V 460 V Motors
Tolerance +5% / –15% +10% / –10% Loads > 63 A without Neutral4
System earthing Solidly earthed, TN-S System
Distribution network 3 phases, 4 wires For Motor Start: – 25% at terminals
(L1, L2, L3, PE)
Motor Heaters: 127 V AC, 1-phase,
3 wires (L, N, PE)
Voltage 220 / 127 V 220 / 127 V BoP & Actuators
Tolerance +10% / –10% +10% / –10% Loads with Neutral, Ir < 63 A4
System earthing Solidly earthed, TN-S System
Distribution network 3 phases, 5 wires Dedicated voltage level for e.g. small
(L1, L2, L3, N, PE) power & lighting
Low Voltage single-phase
Voltage 127 V 127 V Only for BoP
Tolerance max. +10% / –10% +10% / –10%
System earthing Solidly earthed
Distribution network 3 wires (L, N, PE)
Low Voltage UPS single-phase
Voltage 127 V 127 V At distribution board:
Tolerance max. +10% / –10% +10% / –10% - via DC/ AC Converter: + 1% / – 1%
System earthing Solidly earthed, TN-C-S System - via Bypass: +10% / –10%
Distribution network 3 wires (L, N, PE)

1 Nominal Voltage/ Nominal Frequency


2 Rated Voltage / Rated Frequency
3 For ACC fan motors only
4 Loads with Neutral Ir > 63A: Supplied by 460V 4-wires, neutral to be created locally at consumer by transformer

GE POWER Identification Number: Rev. Date Lang. Sheet


Gas Power Systems 1GP006533 A 2017-06-23 en 5/6
© COPYRIGHT 2017 General Electric Company GE CLASS II (INTERNAL NON-CRITICAL)
All rights reserved. The information herein is Proprietary and Technically Exclusive content of the General Electric Company and/or its legitimate
affiliates.
Invalid

DC Voltages
Low Voltage
Voltage 220 V 220 V
Tolerance +10% / –15% +10% / –20% Floating voltage: +10% continuously
System earthing Isolated from earth, IT System For Motor Start: –30% at terminals
Distribution network 3 wires (L+, L-, PE)
Low Voltage
(Solenoid valves)
Voltage 24 V 24 V From the control system, for solenoid
Tolerance +10% / –5% +10% / –15% valves with rated current of max. 3.15
System earthing Isolated from earth, IT System A. 220 V DC for higher current ratings
Distribution network 3 wires (L+, L-, PE)
Table 1: Voltages and Frequencies

GE POWER Identification Number: Rev. Date Lang. Sheet


Gas Power Systems 1GP006533 A 2017-06-23 en 6/6
© COPYRIGHT 2017 General Electric Company GE CLASS II (INTERNAL NON-CRITICAL)