Technical Data: Date Rev. Date Project ID Tracking Number Project Name AHU Name AHU Model

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Unit ID: 8150-22-00-003

TECHNICAL DATA
Date 09.09.2022 Rev. Date 09.09.2022
Project ID 8150 Tracking Number
Project Name 2022_09_09_SOWAID(T22-6769)
AHU Name HCAT-09-1,50-M-4K - (1 QTY) HVACCALC V. 2.2.3.24
29.08.2022

AHU Model HCAT-09 [361] Page 1/3


RIGHT VIEW

TOP VIEW
GENERAL SPECIFICATIONS
Air Flow Frame Dimensions (mm)(Size+Pedestal+
Dampers+Pipes)
3.607 m³/h 40'lık Oval Profil W 760 x H 800 x L 1.050
Air Velocity Insulation Material Total Weight Altitude

2,61 m/s 22 mm Rockwool 52 kg/m³ 148,8 kg 0m


Air Density Outside Sheet Material Base Height Roof (Outside)
1,2922 kg/m³ 0,8 mm Painted Galvanize 100 mm Sac
Design Outdoor Temp.(W-S) Inside Sheet Material Motor Power

(0°C/0%)-(0°C/0%/WB:-6,04°C%/DP:-83,42°C) 0,8 mm Galvanize 1,1 kW


Total Absorbed Power

0,74 kW
Specific Fan Power(SFP Total) ErP Code External Static Pressure Return External Static Pressure

536 W/(m³/s) NRVU - UVU 120 Pa


SOUND POWER LEVEL (dB)
Frequency Hz 125 250 500 1000 2000 4000 8000 LwA-tot
Airborne Sound Power Level 53,6 40,1 42,2 42,6 42,4 37,5 27,3 47,9 dBA
Air Outlet Induct Sound Power Level 72,6 67,1 73,2 76,6 76,4 74,5 69,3 81,4 dBA
Air Inlet Induct Sound Power Level 75,5 66,0 68,8 72,0 72,9 71,3 66,5 77,4 dBA
MB MECHANICAL PROPERTY CLASSIFICATIONS
CAL Class CAL Class CASING ACOUSTICAL INSULATION [dB]
Model CS Class -400 Pa (M) +700 Pa (M) FBL Class TT Class TBF Class
-400 Pa (R) +400 Pa (R) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
19 27 31 34 34 37 42

ACCESSORIES
Lightening,Observation Glass,Maintenance Switch,Esnek Bağdaştırıcı

www.activent.com.tr Office Tel: 0212 565 73 03 Factory Tel: 0212 698 02 25


info@activent.com.tr Office Fax: 0212 698 02 26 Factory Fax:

Designer: Arzu KARABACAK 09.09.2022


HVAC Calculator
Unit ID: 8150-22-00-003
TECHNICAL DATA
Date 09.09.2022 Rev. Date 09.09.2022
Project ID 8150 Tracking Number
Project Name 2022_09_09_SOWAID(T22-6769)
AHU Name HCAT-09-1,50-M-4K - (1 QTY) HVACCALC V. 2.2.3.24
29.08.2022

AHU Model HCAT-09 [361] Page 2/3


FRESH AIR CONNECTION
Connection Type Control Type Pressure Drop
Flange 10 Pa
Air Flow Dimensions Air Velocity
3.607 m³/h W 600 mm x H 250 mm 6,68 m/s
SUPPLY CONNECTION
Connection Type Control Type Pressure Drop
Flange 0 Pa
Air Flow Dimensions Air Velocity
3.607 m³/h W 298 mm x H 262 mm 12,83 m/s
SUPPLY FAN (M1)
Air Flow Motor Type Fan Model Quantity Section Weight
3.607 m³/h AC-AGM 90 S-4 Nicotra-AT 9-9 S 1 148,8 kg
Internal Static Pressure Motor P./Pha./Volt./Freq. Isolator Isolator Count
10 Pa 1,1 kW/3P/220V/50V-Hz Arch 4
External Static Pressure Motor Speed Backup Fan Backup Motor Backup Inverter
120 Pa 1500 (1380)rpm 0 0 0
Total Static Pressure Fan Pulley
130 Pa SPA 150x2+2012 Ø20 mm
Total Pressure Motor Pulley
236 Pa SPA 100x2+1610 Ø24 mm
Total / Static Efficiency Belt
47,60 / 47,60 % 2xSPA 1.100 mm
Motor / Inverter Efficiency Frequency Inverter Included
76,80 / 97,00 %
Shaft Power / Absorbed Power Absorbed Pow.With VFD
0,5 / 0,72 kW 0,74 kW
Fan Speed Running Frequency
927 rpm (Max. 2100 rpm) 50,00 Hz
Fan Outlet Air Velocity Air Density
12,83 m/s 1,2922 kg/m³
Specific Fan Power (SFPe int) Electrical Current
536 W/(m³/s) 1,13 A (Max. 2,49 A)
Sound Power Level (dB)
Hz 63 125 250 500 1000 2000 4000 8000 LwA-tot
Outlet Side 59,7 72,6 67,1 73,2 76,6 76,4 74,5 69,3 81,9 dBA
Inlet Side 69,1 78,5 69,0 71,8 75,0 74,9 73,3 68,5 80,6 dBA
* The fan system effect is taken into account in the fan performance
* The fan calculated for wet conditions

Energy Efficiency Class

SERVICE DOORS (M1)


ID Type Size Position Hinge Position Alignment Opposing Door

1 Standard (Handle + Hinge) 500 mm x 620 mm Right Right Left


ACCESSORIES (M1)
Lightening,Observation Glass,Maintenance Switch,Esnek Bağdaştırıcı

www.activent.com.tr Office Tel: 0212 565 73 03 Factory Tel: 0212 698 02 25


info@activent.com.tr Office Fax: 0212 698 02 26 Factory Fax:

Designer: Arzu KARABACAK 09.09.2022


HVAC Calculator
Unit ID: 8150-22-00-003
TECHNICAL DATA
Date 09.09.2022 Rev. Date 09.09.2022
Project ID 8150 Tracking Number
Project Name 2022_09_09_SOWAID(T22-6769)
AHU Name HCAT-09-1,50-M-4K - (1 QTY) HVACCALC V. 2.2.3.24
29.08.2022

AHU Model HCAT-09 [361] Page 3/3


LOADING SIZES

LOADING SIZES
Section Width Height Length Weight Total Weight
Fan - (M1) 760 mm 800 mm 1.050 mm 148,8 kg 148,8 kg
148,8 kg 148,8 kg
SPECIFIC FAN POWER (TOTAL)
(Filter Pressure Drop + Heat Exchanger Pressure Drop) / ((Fan Efficiency / 100) * (Motor Efficiency /
Formula
100) * (Frequency Converter Efficiency / 100))
Absorbed power is calculated with (Filter Pressure Drop (F7 and M5) + Heat Exchanger Pressure
Explanation
Drop)
SPECIFIC FAN POWER (INT)
(Filter Pressure Drop + Heat Exchanger Pressure Drop) / ((Fan Efficiency / 100) * (Motor Efficiency /
Formula
100) * (Frequency Converter Efficiency / 100))
Absorbed power is calculated with (Filter Pressure Drop (F7 and M5) + Heat Exchanger Pressure
Explanation
Drop)

www.activent.com.tr Office Tel: 0212 565 73 03 Factory Tel: 0212 698 02 25


info@activent.com.tr Office Fax: 0212 698 02 26 Factory Fax:

Designer: Arzu KARABACAK 09.09.2022


HVAC Calculator