Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

DATAR ENGINEERING

FOR HOIST APPLICATION - L & T FX2000 SERIES VFD


SR.NO. PARAMETER PARAMETER NAME & DISCRIPTION SET RANGE SET VALUE

1 CNF-40 Factory setting 1(All Parameter)


Parameter Initialization (Reset) Press'MODE'
Button 3 Times to open CNF Group
2 DRV-3 Acceleration Time 0-6000sec 1sec

3 DRV-4 Deceleration Time 0-6000sec 0.5sec


4 DRV-6 Operating Command Method 0-3 1

5 DRV-7 Frequency setting method 0-8 0


6 DRV-14 Motor Capacity Select Motor Rating KW As per Motor

7 DRV-15 Torque Boost Option 0-3 0


8 DRV-16 Forward Torque Boost 0-15% 4

9 DRV-17 Reverse Torque Boost 0-15% 4


10 BAS-11 Poles As per Motor
Set Value from Motor name plate
Poles=(120XFrequency)/Sync RPM 4

11 BAS-12 Slip As per Motor


Difference between syncronizing
speed motor name plate speed 40

12 BAS-13 Motor Rated Current Set Value from Motor name plate As per Motor

13 BAS-14 NO Load Current Set Value 30-40% Less 40% As per Motor Current
14 BAS-15 Motor Voltage Set Value from Motor name plate 415
15 BAS-16 Motor efficiency Set Value from Motor name plate As Motor(85%)

16 BAS-19 Input power voltage 415 415


17 BAS-20 Auto Tunning 0-6 2 On Site Tunning
18 BAS-50 Fast Frequency 0-Maximum Freq. 50Hz
19 BAS-51 Slow Frequency 0-Maximum Freq. 20Hz

20 OUT-31 Relay-Output-1 (VFD OK Relay) 0-38 22

21 OUT-32 Relay-Output-2 (Brake Relay) 0-38 35

22 OUT-33 Transistor Output (Overload trip) 0-38 41 Deep switch setting


23 IN-67 P3 Input Terminal Function(External Trip) 0-32 4 0
24 ADV-01 Acceleration Pattern Linear 1 1
25 ADV-02 Deceleration Pattern Linear 1 0-Panel testing
Brake Control Parameter 1-site testing
26 ADV-35 Brake Release Fwd Frequency 0-400Hz 0.7Hz

27 ADV-36 Brake Release Rev Frequency 0-400Hz 0.7Hz

28 ADV-38 Brake Open Delay Time 0-10sec 0.2sec

29 ADV-39 Brake Release Fwd Current 0-180% (0-For Panel testing) 20.00%

30 ADV-40 Brake Release Rev Current 0-180% (0-For Panel testing) 20.00%

31 ADV-43 Brake Engage Fwd Frequency 0-400Hz 2 Hz

32 ADV-44 Brake Engage Rev Frequency 0-400Hz 3 Hz

33 ADV-46 Brake Engage Delay Time 0-10sec 0.2sec

Protection Parameter

34 PRT-5 Phase lose Input/Output 1

36 PRT-6 Input Phase Open Voltage Band 1-100V 35V

37 PRT-17 Overload Alarm Selection 0-1 1

38 PRT-18 Overload Alarm Level 30-180% 92% As per site

39 PRT-19 Overload Alarm Time 0-60sec 3sec

You might also like