Earthing Calculation Junpukur Rev 2
Earthing Calculation Junpukur Rev 2
1.0 CONSIDERATIONS
GRID
5.0 DESIGN DATA
a) IEEE 80:1986
b) IS - 3043
c) CBIP Technical Report No.- 5
2.0 CONSIDERATIONS
NY
Width (Y)
5.5
5.5
35 NX
Length (X)
Length in m, X = 43.00 Width in m, Y = 35
Considering spacing of conductor along X-diection in m = 5.5
Considering spacing of conductor along Y-diection in m = 5.5
NX = Numbers of conductor along X-direction = 9
NY = Numbers of conductor along Y-direction = 7
Total length of Grid conductors in meter Lg = 616.00 [Lg= L x Nl + W x Nw]
Total length including grid corner & aux. mat & ground rod = LR 138 m
Total Length of Burried Conductor LT = LR +Lg = 754.0 m
Total area covered by the ground grid = 1505.00 m2
The calculated step voltage is less than tolerable step voltage. Hence, the grid design is correct.
The calculated touch voltage is less than tolerable touch voltage. Hence grid design is correct.