FDVMC120 23/01/2008

OUT RELAY MODULE

- Installation instructions -

DESCRIPTION CONNECTIONS EXAMPLE


FDVMC120 is an output micro-module useful to interface external devices with a addressable analogic detection A loop connection example and internally relay configurations are following showed:
line. It’s relevant characteristics are following described:
• The micro-module is addressable (from user) using FD P100 programmer tool.
• Relay activation state will be showed from green led turned on fixed
• Whit out relay’s load inductive, connect in parallel to the load an 1A diode in order to eliminate overshot.
• An integrated insulator is provided for every module
• The module is compatible exclusively with Teledata panels.
• The output relay electrical specifications are the following:
- 0.5A / 125V AC;
- 2A / 30V DC

TECHNICAL SPECIFICATION
Power supply........................................................................................................ 15-40 Vdc
Standby consuption .............................................................................................. 0,15 mA-
Optical visualisation ............................................................................................ green / yellow / red led
Led fixed on consuption ............................................................................................6 mA-
Addressing............................................................................................................ With FD P100 Loop + to next device
Loop+
Operating temperature range ...................................................................................(-30 ÷ +70) °C
Operating humidity ...................................................................................................(5 ÷ 85) % U.R.
Dimentions (HxPxL)............................................................................................ 75 x 55 x 30 mm Loop – to next device
Loop -

CONNECTIONS
Connection Description
1 Loop + (input)
C1
2 Loop + (output)
3 Loop - (input) NO1
N
4 Loop – (output) A
NC1
5 Not used
6 Not used
C2
7 relay 1 common (C1)
8 relay 2 common (C2) NO2
9 relay 1 NO connect. (NO1) N
A
10 relay 2 NO connect. (NO2) NC2
1 12 11 relay 1 NC connect. (NC1)
12 relay 2 NC connect. (NC2)

TELEDATA srl. - VIA Giulietti 8 - 20132 Milan - +39 02.27201352 -  +39 02.2593704 - e - m ai l : te l e d ata@ te l e d ata- i . c o m