Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Reporte de Prueba de Apartarrayo-

PR201

Nameplate
Country PERU Manufacturer Siemens Serial Number 35176232
Company CHINALCO Type 3EP21LD2 Arrester ID PR201-R
Region 700 Rated Voltage (kV) 198.0 System Voltage (kV) 220.0
Substation TOROMOCHO MCOV (kV) 158.0 Installation Date 2011-Jan-01
Location L2284T Correction Applied Normal Status Bueno
Phase R

Results
Resistive Corrected Total Ambient Operating Third
Current Resistive Current Current Temp Voltage Harmonic
Date
I [res] ȝA I [corr res] ȝA I [tot] ȝA T [amb] °C U [oper] kV %

3/25/2021 2:51:57 54.2 73.4 1144.9 16.0 220.0 0.0


PM
3/2/2023 11:24:41 48.9 66.2 1091.4 16.0 220.0 0.2
AM
4/1/2024 9:31:40 49.9 66.2 1083.8 8.0 220.0 0.1
AM

Measurement Plots

Filename C:\Users\sala700\Documents\Doble Engineering\LCM Viewer\Pruebas guardadas automáticamente\PR 201_FASE R.lcmx

Report generated on 4/1/2024 5:30:44 PM 1-3


[Header]

Nameplate
Country PERU Manufacturer Siemens Serial Number 35176233
Company CHINALCO Type 3EP21LD2 Arrester ID PR201-S
Region 700 Rated Voltage (kV) 198.0 System Voltage (kV) 220.0
Substation TOROMOCHO MCOV (kV) 158.0 Installation Date 2011-Jan-01
Location L2284T Correction Applied Normal Status Bueno
Phase S

Results
Resistive Corrected Total Ambient Operating Third
Current Resistive Current Current Temp Voltage Harmonic
Date
I [res] ȝA I [corr res] ȝA I [tot] ȝA T [amb] °C U [oper] kV %

3/25/2021 2:52:43 55.7 75.4 1182.8 16.0 220.0 0.2


PM
3/2/2023 11:23:22 57.0 77.2 1111.4 16.0 220.0 0.2
AM
4/1/2024 9:32:31 52.8 70.1 1131.6 8.0 220.0 0.1
AM

Measurement Plots

Filename C:\Users\sala700\Documents\Doble Engineering\LCM Viewer\Pruebas guardadas automáticamente\PR 201_FASE S.lcmx

Report generated on 4/1/2024 5:30:44 PM 2-3


[Header]

Nameplate
Country PERU Manufacturer Siemens Serial Number 35176234
Company CHINALCO Type 3EP21LD2 Arrester ID PR201-T
Region 700 Rated Voltage (kV) 198.0 System Voltage (kV) 220.0
Substation TOROMOCHO MCOV (kV) 158.0 Installation Date 2011-Jan-01
Location L2284T Correction Applied Normal Status Bueno
Phase T

Results
Resistive Corrected Total Ambient Operating Third
Current Resistive Current Current Temp Voltage Harmonic
Date
I [res] ȝA I [corr res] ȝA I [tot] ȝA T [amb] °C U [oper] kV %

3/25/2021 2:53:38 72.4 98.0 1206.8 16.0 220.0 0.3


PM
3/2/2023 11:25:55 64.3 87.4 1141.8 17.0 220.0 0.4
AM
4/1/2024 9:33:53 84.6 112.2 1132.0 8.0 220.0 0.6
AM

Measurement Plots

Filename C:\Users\sala700\Documents\Doble Engineering\LCM Viewer\Pruebas guardadas automáticamente\PR 201_FASE T.lcmx

Report generated on 4/1/2024 5:30:44 PM 3-3