n
- Enthalpy
High degree of protection against condensation & pollution
IP65
n Surface (Wall), Duct, Outside & Remote sensor versions
n Convenient installation with 2-part housing with fixed back and
removable electronics
n Integral sensor (default) or remote sensor
n Flush mount application
ABOUT HTW201
HTW201 accurately measures humidity using capacitive sensor technology & temperature using band gap sensor
technology or RTD.
It generates upto dual 2-wire loop powered 4~20 mA outputs or 0~10 VDC outputs that can be assigned to RH, T or
Dewpoint using handheld configurator & PC based configurator. Temperature output can be analog output or resistance
output from Class A RTD, Pt100 or Pt1000.
APPLICATIONS
n Commercial buildings
n Outdoor temperature and relative humidity reference
n Greenhouses
n Swimming halls
n Storage rooms & cooling chambers
n Air economizers, Air quality
DCC501 USB to Serial converter can be used to Handheld Configurator can be used to configure and
program the parameters. The Programmer DCC501 calibrate the parameters. The Configurator must be
must be purchased separately. purchased separately.
DCC501
Handheld
USB
INTERFACE Configurator
HHC202
SPECIFICATIONS
All specifications at ambient of 25 °C, 24VDC unless specified otherwise
INPUT
Integral sensor type a. Smart Sensor for RH and/or temperature
b. i) Smart Sensor for RH
ii) RTD : Pt100/Pt1000
Range limits See table 1
INDICATION
Display Dual row LCD display
Digits 6-digit, 10.5mm height, with unit indication
7-digit, 6.94mm height, with unit indication
Resolution 1 & 0.1 for RH (<100%RH),
Temperature and Dewpoint
Backlight Enable/Disable option
Status indication Healthy and failure conditions
OUTPUTS
Analog output 4~20 mA loop powered load 800 Ω @ 24 V DC
0~10 V DC, Load > 1K (0~1 V DC, 0~5 V DC outputs available on request)
Resistance output Two wire resistance output for class A RTD sensor (Pt100/Pt1000 etc.)
ACCURACY
RH ± 2% RH, ± 3% RH, ± 4% RH
See fig 1 and ordering information
Temperature ± 0.5 °C for bandgap temperature sensor,
± 0.2 °C for RTD (Class A)
Dewpoint ±1 °C
ELECTRICAL CONNECTION
Removable screw terminal block suitable for cable 14~22AWG
Torque 4kgf.cm/M2.5
Mounting orientation Not position sensitive
COMMUNICATION
Port Isolated RS485
Isolation Between RS485 port and supply
Protocol MODBUS RTU
Slave ID User programmable (1~247)
Supported baud rate 4800, 9600, 19200, 57600, 115200
SPECIFICATIONS
All specifications at ambient of 25 °C, 24VDC unless specified otherwise
ISOLATION
Mutual isolation between supply 1000 V AC RMS, 50 hz / 1 second, 500 V / minute
and RS485 output
PERFORMANCE PARAMETER
Response time RH - 8 seconds for t 63%
T - 5 to 30 seconds for t 63%
Hysteresis ±1 %RH
Repeatability ±0.1 %RH & ±0.1 °C
Long term drift (for RH+T sensor) RH - <0.25 %RH/yr
T - <0.02 °C/yr
Environment Air & Neutral gas
Temperature effect on accuracy ± 0.5% of span / 25 °C
Supply voltage effect ± 0.002% of span / V
Supply ripple effect, 50/60 hz, 5 Vp - p ± 0.005% of span
POWER SUPPLY
4~20 mA loop powered models 8~30 VDC,<40mW power consumption
0~10 VDC output models 18~30 V AC/DC
Min <450 mW, Max <1W power consumption
TEMPERATURE, HUMIDITY
Parameter Operating Range Storage Range
RH 0~100 %RH 0~100 %RH non-condensing
Temperature & Dewpoint -40~80 °C (-40~176 °F) without display -40~80 °C (-40~176 °F) without display
Temperature & Dewpoint -20~70 °C (-4~158 °F) with display -25~80 °C (-4~176 °F) with display
MECHANICAL
Dimensions See Fig 2, Fig 3
Mounting/Sensor version Surface mount, Duct mount, Outside air or remote sensor version
Sensor filter PTFE or sintered filter
Enclosure material Polycarbonate
Protection IP65
Conduit connection Provision for 1/2" conduit clamping
Duct Sensor housing i) Polycarbonate (for T range <80°C)
ii) Stainless steel SS304 (for 80° C >T range < 120 °C)
ACCURACY OF RH & T
Fig 1
For 2880 XXXXX1X order code (4% RH) For 2880 XXXXX2X order code (3% RH) For 2880 XXXXX3X order code (2% RH)
INSTALLATION
Fixed back
Removable front for cabling
with electronics
DIMENSIONS mm
42.1
Fig 2 : Surface MOUNT
70
82 42.1
161.6
41.4
73
161.6
161.6
Outside air Application
41.9
Back View Front View Side View Bottom View
flange
get
12
12
locked
80
Front View
282.3
280.7
280.7
241.2
241.2
241.2
50
80
60 Ø 14
CONNECTION DIAGRAM
V1
Indicator 1
HTW201 HTW201 or PLC1
I1
1 2 3 4 1 2 3 4 5 6
V1 I1 V2 I2 V1 I1 V2 I2
A B
V2 I2
RH or Temperature
O/P1 or O/P2 RH or Temperature Indicator 2
receiver receiver O/P1 or O/P2 or PLC2
receiver receiver Resistance
Temperature
Output
+ - + - + -
24 VDC 24 VDC 24 VDC 4~20 mA non-isolated output for RH & T
Power Power Power
Supply Supply Supply Clean Room
+
V1 VTX Monitor
I1 I1 / RHIN
Isolated RH & T Output Non-Isolated RH & T Output
+
V2
I2 I2 / TIN
Voltage Output
24 VAC Connection
HTW201
24 VAC
Vs+ RH+ VIN1+
1 2 3 4 5 6
VIN - PID
V+ V- RH+ T+ A B 230 VAC HTW201-1 COM
CONTROLLER
-- -
Vs T VIN2+
- -
+
24 VAC
RH or O/P1 Resistance
receiver Vs+ RH+ VIN1+
Temperature
Output VIN - PID
230 VAC HTW201-2 COM
CONTROLLER
--
+
24 VAC/DC Temperature -
Vs T VIN2+
POWER or
SUPPLY O/P2 receiver
Note: Common can be shorted with 24VDC- Note : Each HTW201 should have a separate winding or transformer
ORDERING INFORMATION
Example 2880 1 1 1 1 1 1 1 1
Product Code 2880**
1 RH & Temperature
2 RH, Temperature & Dewpoint
Configuration
RH, Temperature, Dewpoint, Absolute humidity, Enthalpy,
3
Heat index, Air density etc
1 Surface
Mounting
2 Duct
1 Smart Sensor (Bandgap)
Temperature Measurement 2 RTD : Pt100
3 RTD : Pt1000
1 None
LCD Display
2 Provided
1 4~20 mA loop powered
RH Output
2 0~10 VDC output
1 None
2 Analog output (same as RH output)
Temperature Output
3 Pt100* resistance output
4 Pt1000* resistance output
1 4%
%RH Accuracy 2 3%
3 2%
1 PTFE
Sensor Filter
2 Sintered stainless steel filter
EXAMPLE
2880 1 1 1 1 1 1 1 1
CONFIGURATORS
Product Model Order Code
Instruments: sales@radix.co.in
ENQUIRIES
Sensors: sensors@radix.co.in
Gauges: gauges@radix.co.in
EL-135/136/137, Electronics Zone, TTC Indl. Area, MIDC, Mahape
Automation: automation@radix.co.in
Navi Mumbai - 400 710, India
Level: level@radix.co.in
+ 91 22 42537707 · sales@radix.co.in