CTSizing Excel Calculation
CTSizing Excel Calculation
CTSizing Excel Calculation
Device connected VA
AMMETER 0.5 VA
KW METER 1 VA
CURRENT TRANSDUCER 1.5 VA
I=Secondary current
Rl = lead or cable Resistance
secondary current 1A
Cable used 2.5 Sq.mm
Cable resistance 8.87 Ω/Km
No of turns used 1
Length 50 m
P-class Sizing
VA
Feeder 5000KVA
VA Voltage 33kV
Fault Current 40kA
VA Full load Current 87.48A
10% Margin 96.23A
Relay Burden 1 VA
A Lead Burden 8 ohm/km
Calble Length 8 m
Selected VA 30 Rct
Selected ALF 20
Vk Required = 551.2
Vk Available = ALF*Is*(Rct+VA/I^2)
Vk Available = 630 V
is Vk available>Vk Required OK
Sin-Internal Burden of Secondary CT
VA
ohm/km
m
1.5 ohm
630 I(1.5+1.128)
239.726
l+Relay) 240