METERING -CT SIZING

LOAD 2.5 MVA


VOLTAGE 6.6 kV
FULL LOAD CURRENT 219 A

10% MARGIN 241 A

SELECTED CT RATIO 250/1 A


METERING BURDEN -VA CAL

Device connected VA
AMMETER 0.5 VA
KW METER 1 VA
CURRENT TRANSDUCER 1.5 VA

TOTAL DEVICE BURDEN 3 VA

Lead burden =I^2 *2Rl

I=Secondary current
Rl = lead or cable Resistance

secondary current 1A
Cable used 2.5 Sq.mm
Cable resistance 8.87 Ω/Km
No of turns used 1
Length 50 m

Lead Resistance Rl 0.4435


2Rl 0.887
Lead burden -I^2 *Rl 0.887 VA

Total Connected Burden Lead Burden +Total Device burden


3.887 VA
Selected Burden 10 VA
5 ISF
Actual VA burden within 25% to
100% of rated VA Burden
CT-5P20

Fn-Rated Acccuracy limit factor 20

Sn-Rated Burden of the CT 30

Sa-Actual Burden of the CT 1.128

Sin-Internal Burden of Sec CT 0.75

Fa -Total Accuracy limit Factor 327.5


Required Accuracy Limit Factor 200

For 200/1A -will not saturate upto - 65495.208

Fa*CT Primary >Max fault Current


Fa -Total Accuracy limit Factor Sin-Internal Bu
Fn-Rated Acccuracy limit factor
Sin-Internal Burden of Secondary CT
Sn-Rated Burden of the CT 100
Sa-actual Burden of the CT 200

P-class Sizing
VA
Feeder 5000KVA
VA Voltage 33kV
Fault Current 40kA
VA Full load Current 87.48A
10% Margin 96.23A

Selected CT Ratio 200 1

Relay Burden 1 VA
A Lead Burden 8 ohm/km
Calble Length 8 m

Relay Resistance (VA/I^2) 1 ohm


Lead Burden 0.128 ohm

Total Burden 1.128 ohm

Selected VA 30 Rct

Selected ALF 20

Vk Required = If/CT Ratio*(Rct+2Rl+Relay)

Vk Required = 551.2

Vk Available = ALF*Is*(Rct+VA/I^2)

Vk Available = 630 V

is Vk available>Vk Required OK
Sin-Internal Burden of Secondary CT

Min Rct Max Rct


/1A 0.3 ohm 0.75 ohm
/1A 0.6ohm 1.5ohm

VA
ohm/km
m
1.5 ohm

630 I(1.5+1.128)
239.726

l+Relay) 240