Hourly bank voltage & current recorded in Battery Charger panel during the recharging after the discharge cycle
Time Elapsed
Date Amps Volts Remarks
(Hrs.) Time
22:00 0 Hr. 116.30 209.0 Start of Recharging
22.10.2021 23:00 1 Hr. 114.20 225.4
24:00 2 Hrs. 116.90 227.8
1:00 3 Hrs. 114.7 230.6
2:00 4 Hrs. 115.2 234.3
3:00 5 Hrs. 116.0 238.0 Auto BOOST Charging
4:00 6 Hrs. 115.9 241.8
5:00 7 Hrs. 77.6 242.9
6:00 8 Hrs. 53.6 243.1
7:00 9 Hrs. 38.3 243.0
8:00 10 Hrs. 13.7 238.3 Auto Float Charging Changeover
9:00 11 Hrs. 12.1 237.6
10:00 12 Hrs. 10.7 237.7
11:00 13 Hrs. 9.3 237.7
23.10.2021 12:00 14 Hrs. 8.3 237.7
13:00 15 Hrs. 7.2 237.8
14:00 16 Hrs. 6.5 237.8
15:00 17 Hrs. 6.0 237.9
Auto FLOAT Charging
16:00 18 Hrs. 5.4 237.9
17:00 19 Hrs. 4.9 237.9
18:00 20 hrs. 4.4 237.9
19:00 21 Hrs. 4.1 237.9
20:00 22 Hrs. 3.8 238.0
21:00 23 Hrs. 3.6 238.0
22:00 24 Hrs. 3.4 238.0
23:00 25 Hrs. 3.2 238.0 End of Recharging
Annexure-2c
235
60 225
0 205
0 Hr.
1 Hr.
2 Hrs.
3 Hrs.
4 Hrs.
5 Hrs.
6 Hrs.
7 Hrs.
8 Hrs.
9 Hrs.
10 Hrs.
11 Hrs.
12 Hrs.
13 Hrs.
14 Hrs.
15 Hrs.
16 Hrs.
17 Hrs.
18 Hrs.
19 Hrs.
21 Hrs.
22 Hrs.
23 Hrs.
24 Hrs.
25 Hrs.
20 hrs.
22:00 23:00 00:00 01:00 02:00 03:00 04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00
22.10.2021 23.10.2021
Charging Date/Time/Hrs
Charging Current (A) Bank Voltage (V)
Figure 1: Plot of battery charging current (A) & bank voltage (V) ‘vs’ charging time