Cable Sizing Cal
Cable Sizing Cal
2 Source Data
2.1 Transformer Tag number 302-30-TR-X1
3 Load Data
3.1 Load Feeder tag / Equipment Tag Number 302-30-SB-X1
3.2 Load description 400V Switchboard
3.3 Load Rating - Name plate kVA 1000 Refer to Note 7.4
3.4 Power factor cosФ 0.85
3.5 Efficiency η 0.9
3.6 Voltage V 400
3.7 Full load current - name plate A 1603.751
5 Calculations 3 phase
5.1 Criterion: Ampacity with deration
5.1.1 Cable size considered sq. mm. 630
5.1.2 Cable ampacity as per vendor catalogue 956 Doha Cables, page-140
5.1.3 Ampacity after applying overall deration factor = (4.5) x (5.1.2) A 831.72
5.1.4 No. of parallel cable runs required - by calculation = (3.7) / (5.1.3) 1.93
5.1.5 No. of parallel cable runs required - whole number 2.00
5.1.6 Ampacity after applying overall deration factor & runs = (5.1.3) x (5.1.5) A 1663.44
5.1.7 Is selected cable capable of carrying rated full load current YES
6 Conclusion
2 Run of 1Cx630sq.
6.1 For the given load, the selected cable size and length considered is mm. /phase &
0.02km
7 Notes
7.1 This calculation is for LV cables between 33/0.42kV Distribution Transformer (302-30-TR-X1) and 400V Switchboard (302-30-SB-X1).
1C LV Cables will be installed in air in trefoil formation. LV Cables will be routed through cable ladder inside concrete cable trench from
7.2
Transformer room to LV Switchgear room.
7.3 Attachment-7 : Doha cables LV cable Parameters
7.4 Transformer rating is based on Electrical Load List doc JCWF-2-34-0001 & Transformer Sizing Calculation doc. 4172-GENON-2-12-0002.
2 Source Data
2.1 Transformer Tag number A6 TR 003
3 Load Data
3.1 Load Feeder tag / Equipment Tag Number A6 SB 002
3.2 Load description 400V Switchboard
3.3 Load Rating - Name plate kVA 315 Refer to Note 7.4
3.4 Power factor cosФ 0.85
3.5 Efficiency η 0.95
3.6 Voltage V 400
3.7 Full load current - name plate A 478.6
4 Cable de-rating factor
Refer Attachment-6, Doha Cables
4.1 For Group of Cables (Kg) (Two ckts in one tray) 1.00
Derating Factors, Table-9
Refer Attachment-6, Doha Cables
4.2 For Air Temperature (Kt) (Ambient air temperature of 52°C ) 0.87
Derating Factors, Table-3
4.3 Cf-Total De-rating factor = Kg x Kt 0.87
5 Calculations 3 phase
5.1 Criterion: Ampacity with deration
5.1.1 Cable size considered sq. mm 300 0.6/1 kV Voltage Grade
Refer Attachment-6, Doha Cables
5.1.2 Cable ampacity as per vendor catalogue 620
Current Rating Table
5.1.3 Ampacity after applying overall deration factor = (4.3) x (5.1.2) A 539.4
5.1.4 No. of parallel cable runs required - by calculation = (3.7) / (5.1.3) 0.89
5.1.5 No. of parallel cable runs required - whole number 1.00
5.1.6 Ampacity after applying overall deration factor & runs = (5.1.3) x (5.1.5) A 539.4
5.1.7 Is selected cable capable of carrying rated full load current YES
5.2 Criterion: Voltage drop steady state
5.2.1 Power factor (CosØ) CosØ 0.85
5.2.2 SinØ (Calculated) SinØ 0.53
Refer Attachment-6, Doha Cables
5.2.3 Cable Resistance (Ω/km) at 90 deg C conductor temperature Ω/km 0.0810
Current Rating Table
5.2.4 Cable Reactance (Ω/km) Ω/km 0.0903 Refer Attachment-7
5.2.5 Cable Length Considered (km) km 0.02
5.2.6 % Voltage drop % 0.483
5.2.7 Is voltage drop within permissible limit of less than 1 YES Sec.6.3 in main Document
5.3 Criterion: Short Circuit rating
5.3.1 Basic formula S = I√t/k
5.3.2 Short Circuit current (I) kA 25.00 From SLD MGDA6-2-54-0002
5.3.3 Duration of Short Circuit (t) sec 1.00
5.3.4 Constant for cable (k) 143.00 for XLPE
5.3.5 Minimum size of the cable recommended sq. mm 174.83
5.3.6 Is selected cable satisfying the criterion YES
6 Conclusion
1 Run of 1Cx300sq. mm
6.1 For the given load, the selected cable size and length considered is
/phase & 0.02km
7 Notes
7.1 This calculation is for LV cables between 11/0.42kV Distribution Transformer (A6 TR 003) and 400V Switchboard (A6 SB 002).
7.2 LV Cables will be routed through cable ladder inside concrete cable trench from Transformer room to LV Switchgear room.
7.3 Attachment-7 : Doha cables LV cable Parameters.
7.4 Transformer rating is based on Electrical Load List doc MGDA6-2-34-0001 & Transformer Sizing Calculation doc. MGDA6-2-12-0003.
ATTACHMENT - 2
HV CABLE SIZING CALCULATIONS
Sl. No. PARTICULARS Units VALUE REMARKS
2 Source Data
Isolator Switch for connection to
2.1 Equipment Tag number A6 IS 004
Temporary EDG
3 Load Data
3.1 Load Feeder tag / Equipment Tag Number A6 SB 002
3.2 Load description 400V Switchboard
3.3 Load Rating - Name plate kVA 315 Refer to Note 7.4
3.4 Power factor cosФ 0.85
3.5 Efficiency η 0.9
3.6 Voltage V 400
3.7 Full load current - name plate A 505.2
4 Cable de-rating factor
Refer Attachment-6, Doha Cables
4.1 For Group of Cables (Kg) (Two ckts in one tray) 1.00
Derating Factors, Table-9
Refer Attachment-6, Doha Cables
4.2 For Air Temperature (Kt) (Ambient air temperature of 52°C ) 0.87
Derating Factors, Table-3
4.3 Cf-Total De-rating factor = Kg x Kt 0.87
5 Calculations 3 phase
5.1 Criterion: Ampacity with deration
5.1.1 Cable size considered sq. mm 300 0.6/1 kV Voltage Grade
Refer Attachment-6, Doha Cables
5.1.2 Cable ampacity as per vendor catalogue 620
Current Rating Table
5.1.3 Ampacity after applying overall deration factor = (4.3) x (5.1.2) A 539.4
5.1.4 No. of parallel cable runs required - by calculation = (3.7) / (5.1.3) 0.94
5.1.5 No. of parallel cable runs required - whole number 1.00
5.1.6 Ampacity after applying overall deration factor & runs = (5.1.3) x (5.1.5) A 539.4
5.1.7 Is selected cable capable of carrying rated full load current YES
5.2 Criterion: Voltage drop steady state
5.2.1 Power factor (CosØ) CosØ 0.85
5.2.2 SinØ (Calculated) SinØ 0.53
Refer Attachment-6, Doha Cables
5.2.3 Cable Resistance (Ω/km) at 90 deg C conductor temperature Ω/km 0.0810
Current Rating Table
5.2.4 Cable Reactance (Ω/km) Ω/km 0.0903 Refer Attachment-7
5.2.5 Cable Length Considered (km) km 0.03
5.2.6 % Voltage drop % 0.764
5.2.7 Is voltage drop within permissible limit of less than 1 YES Sec.6.3 in main Document
5.3 Criterion: Short Circuit rating
5.3.1 Basic formula S = I√t/k
5.3.2 Short Circuit current (I) kA 25.00 From SLD MGDA6-2-54-0002
5.3.3 Duration of Short Circuit (t) sec 1.00
5.3.4 Constant for cable (k) 143.00 for XLPE
5.3.5 Minimum size of the cable recommended sq. mm. 174.83
5.3.6 Is selected cable satisfying the criterion YES
6 Conclusion
1 Run of 1Cx300sq. mm
6.1 For the given load, the selected cable size and length considered is
/phase & 0.03km
7 Notes
7.1 This calculation is for LV cables between Isolator switch A6 IS 004 (for connecting temporary EDG) and 400V Switchboard (A6 SB 002).
7.2 LV Cables will be routed through cable ladder inside concrete cable trench from Isolator switch A6 IS 004 located in transformer room to LV Switchgear room.
5.1.1 Cable size considered sq. mm. 630 0.6/1 kV Voltage Grade
7 Notes
7.1 This calculation is for LV cables between 400V Diesel Generator (36-GD-XXX1) and 400V Switchboard (36-SB-XXX1).
1Core LV Cables will be installed in air in trefoil formation. LV Cables will be routed through cable ladder inside concrete cable trench from EDG room to LV
7.2
Switchgear room.
7.3 Attachment-7 : Doha cables LV cable Parameters
7.4 EDG rating is based on Electrical Load List doc. JCWF-2-34-0001.
ATTACHMENT - 2
LV CABLE SIZING CALCULATIONS
Sl. No. PARTICULARS Units VALUE REMARKS
36-ELP-X11 &
1 Cable Tag number
36-ELP-X27
2 Source Data
2.1 Switchboard Tag number 400V SWBD (36-SB-XXX1)
3 Load Data
36-ST-XXX2 &
3.1 Load Feeder tag / Equipment Tag Number
36-ST-XXX3
Soft Starter Panel for Air
3.2 Load description
Compressor A&B
Sized for total load of air compressor motor
3.3 Load Rating - Name plate (Soft Starter rating for 132kW Motor) kW 165 and aux cooling fan motors.
Refer to Note 7.5
3.4 Power factor cosФ 0.9
3.5 Efficiency η 0.95
3.6 Voltage V 400
3.7 Full load current - name plate A 278.5
4 Cable de-rating factor
Refer Attachment-6, Doha Cables Derating
4.1 For Group of Cables (Kg) (9 Touching Cables and 2 Trays) 0.73
Factors, Table-8
Refer Attachment-6, Doha Cables Derating
4.2 For Air Temperature (Kt) (Ambient air temperature of 52°C ) 0.87
Factors, Table-3
4.3 Cf-Total De-rating factor = Kg x Kt 0.635
5 Calculations 3 phase
5.1 Criterion: Ampacity with deration
5.1.1 Cable size considered sq. mm. 185 0.6/1 kV Voltage Grade
Refer Attachment-6, Doha Cables Current
5.1.2 Cable ampacity as per vendor catalogue 375
Rating Table
5.1.3 Ampacity after applying overall deration factor = (4.3) x (5.1.2) A 238.1
5.1.4 No. of parallel cable runs required - by calculation = (3.7) / (5.1.3) 1.17
5.1.5 No. of parallel cable runs required - whole number 2.00
5.1.6 Ampacity after applying overall deration factor & runs = (5.1.3) x (5.1.5) A 476.3
5.1.7 Is selected cable capable of carrying rated full load current YES
5.2 Criterion: Voltage drop Starting state
5.2.1 Starting Power Factor (CosØ) CosØ 0.3
5.2.2 SinØ (Calculated) SinØ 0.95
Refer Attachment-6, Doha Cables Current
5.2.3 Cable Resistance (Ω/km) at 90 deg C conductor temperature Ω/km 0.129
Rating Table
5.2.4 Cable Reactance (Ω/km) Ω/km 0.072 Refer Attachment-7
5.2.5 Cable Length Considered (km) km 0.03
5.2.6 % Voltage drop % 0.194
5.2.7 Is voltage drop within permissible limit of less than 15 YES Sec.5.3 in main Document
5.2 Criterion: Voltage drop steady state
5.2.1 Power factor (CosØ) CosØ 0.9
5.2.2 SinØ (Calculated) SinØ 0.44
Refer Attachment-6, Doha Cables Current
5.2.3 Cable Resistance (Ω/km) at 90 deg C conductor temperature Ω/km 0.129
Rating Table
5.2.4 Cable Reactance (Ω/km) Ω/km 0.072 Refer Attachment-7
5.2.5 Cable Length Considered (km) km 0.030
5.2.6 % Voltage drop % 0.267
5.2.7 Is voltage drop within permissible limit of less than 5 YES Sec.6.3 in main Document
5.3 Criterion: Short Circuit rating
5.3.1 Basic formula S = I√t/k
5.3.2 Short Circuit current (I) kA 65.00 From SLD JCWF-2-54-0002
5.3.3 Duration of Short Circuit (t) sec 0.10 Refer to Note 7.4
5.3.4 Constant for cable (k) 143.00 for XLPE
5.3.5 Minimum size of the cable recommended sq. mm. 143.74
5.3.6 Is selected cable satisfying the criterion YES
6 Conclusion
2 Run of 3Cx185sq. mm. &
6.1 For the given load, the selected cable size and length considered is
0.03km
7 Notes
7.1 This calculation is for Soft Starter Panels of Air Compressor Motors 36-A-0001-XM-01A & B fed from 400V Switchboard (36-SB-XXX1).
7.2 LV Cables will be routed through cable ladder inside concrete cable trench from for LV switchboard (36-SB-XXX1) to Soft starter panel 36-ST-XXX2 & 36-ST-XXX3.
7.3 Attachment-7 : Doha cables LV cable Parameters
7.4 Min Conductor for short circuit current is calculated with fault clearing time of 0.1 Sec (considering Relay + CB operating time = 0.1 sec).
7.5 Soft Starter Panel kW rating considered in this cable sizing calculation is based on the total load of Air compressor motor and auxiliary cooling fan motors
ATTACHMENT - 2
LV CABLE SIZING CALCULATIONS
Sl. No. PARTICULARS Units VALUE REMARKS
1 Cable Tag number 302-ELP-X12 & X28
2 Source Data
2.1 Switchboard tag number 400V Switchboard (36-SB-XXX1)
2.2 Fed through soft starter 36-ST-XXX2 & 36-ST-XXX3
3 Load Data
3.1 Load Feeder tag / Equipment Tag Number 36-A-0001-XM-01A & B
3.2 Load description AIR COMPRESSOR A&B
3.3 Load Rating - Name plate kW 132
3.4 Power factor cosФ 0.85
3.5 Efficiency η 0.95
3.6 Voltage V 400
3.7 Full load current - name plate A 235.9
4 Cable de-rating factor
Refer Attachment-6, Doha Cables
4.1 For Group of Cables (Kg) (6 Touching cables) 0.56
Derating Factors, Table-7
Refer Attachment-6, Doha Cables
4.2 For Temperature (Kt) (Ground temperature of 40°C ) 0.95
Derating Factors, Table-2
Refer Attachment-6, Doha Cables
4.3 For Thermal Resistivity (Ks) (2.5 K-m/W) 0.73
Derating Factors, Table-5
Refer Attachment-6, Doha Cables
4.4 For Laying Depth (Kl) (Direct buried : 0.8m depth) 0.96
Derating Factors, Table-4
4.5 Cf-Total De-rating factor = Kg x Kt x Ks x Kl 0.373
5 Calculations 3 phase
5.1 Criterion: Ampacity with deration
5.1.1 Cable size considered sq. mm. 185 0.6/1 kV Voltage Grade
Refer Attachment-6, Doha Cables
5.1.2 Cable ampacity as per vendor catalogue 375
Current Rating Table
5.1.3 Ampacity after applying overall deration factor = (4.5) x (5.1.2) A 139.9
5.1.4 No. of parallel cable runs required - by calculation = (3.7) / (5.1.3) 1.7
5.1.5 No. of parallel cable runs required - whole number 2.00
5.1.6 Ampacity after applying overall deration factor & runs = (5.1.3) x (5.1.5) A 279.8
5.1.7 Is selected cable capable of carrying rated full load current YES
5.2 Criterion: Voltage drop Starting state
5.2.1 Starting Power factor (CosØ) CosØ 0.3
5.2.2 SinØ (Calculated) SinØ 0.95
5.2.3 Starting Current pu 3.50
Refer Attachment-6, Doha Cables
5.2.4 Cable Resistance (Ω/km) at 90 deg C conductor temperature Ω/km 0.1290
Current Rating Table
5.2.5 Cable Reactance (Ω/km) Ω/km 0.0720 Refer Attachment-7
5.2.6 Cable Length Considered (km) km 0.26
5.2.7 % Voltage drop % 5.0
5.2.8 Is voltage drop within permissible limit of less than 15 YES Sec.6.3 in main Document
5.2 Criterion: Voltage drop steady state
5.2.1 Power factor (CosØ) CosØ 0.85
5.2.2 SinØ (Calculated) SinØ 0.53
Refer Attachment-6, Doha Cables
5.2.3 Cable Resistance (Ω/km) at 90 deg C conductor temperature Ω/km 0.1290
Current Rating Table
5.2.4 Cable Reactance (Ω/km) Ω/km 0.0720 Refer Attachment-7
5.2.5 Cable Length Considered (km) km 0.26
5.2.6 % Voltage drop % 1.96
5.2.7 Is voltage drop within permissible limit of less than 5 YES Sec.6.3 in main Document
5.3 Criterion: Short Circuit rating
5.3.1 Basic formula S = I√t/k
5.3.2 Short Circuit current (I) kA 65.00 From SLD JCWF-2-54-0002
5.3.3 Duration of Short Circuit (t) sec 0.10 Refer to Note 7.4
5.3.4 Constant for cable (k) 143.00 for XLPE
5.3.5 Minimum size of the cable recommended sq. mm. 143.74
5.3.6 Is selected cable satisfying the criterion YES
6 Conclusion
6.1 For the given load, the selected cable size and length considered is 2 Run of 3Cx185sq. mm. & 0.26km
7 Notes
7.1 This calculation is for air compressor motor 36-A-0001-XM-01A & B fed from 36-ST-XXX2 & 36-ST-XXX3.
7.2 LV Cable is routed both direct in ground and in single way duct.
7.3 Attachment-7 : Doha cables LV cable Parameters
7.4 Min Conductor for short circuit current is calculated with fault clearing time of 0.1 Sec (considering Relay + CB operating time = 0.1 sec).
ATTACHMENT - 2
LV CABLE SIZING CALCULATIONS
Sl. No. PARTICULARS Units VALUE REMARKS
1 Cable Tag number 302-ELP-X15
2 Source Data
400V Switchboard (302-
2.1 Switchboard Tag number
30-SB-X1)
3 Load Data
3.1 Load Feeder tag / Equipment Tag Number 302-30-ST-X1
3.3 Load Rating - Name plate (Soft Starter rating for 185kW Motor) kW 200 Refer to Note 7.5
3.4 Power factor cosФ 0.9
3.5 Efficiency η 0.946
3.6 Voltage V 400
3.7 Full load current - name plate A 339.059
5 Calculations 3 phase
5.1 Criterion: Ampacity with deration
5.1.1 Cable size considered sq. mm. 240
5.1.2 Cable ampacity as per vendor catalogue 488 Doha Cables, page-146
5.1.3 Ampacity after applying overall deration factor = (4.5) x (5.1.2) A 424.56
5.1.4 No. of parallel cable runs required - by calculation = (3.7) / (5.1.3) 0.80
5.1.5 No. of parallel cable runs required - whole number 1.00
5.1.6 Ampacity after applying overall deration factor & runs = (5.1.3) x (5.1.5) A 424.56
5.1.7 Is selected cable capable of carrying rated full load current YES
2 Source Data
400V Switchboard (302-
2.1 Switchboard Tag number
30-SB-X1)
3 Load Data
3.1 Load Feeder tag / Equipment Tag Number 302-03-PM-001
CO2 WAG Changeover
3.2 Load description
Pump
3.3 Load Rating - Name plate kW 185
3.4 Power factor cosФ 0.9
3.5 Efficiency η 0.946
3.6 Voltage V 400
3.7 Full load current - name plate A 313.630
5 Calculations 3 phase
5.1 Criterion: Ampacity with deration
5.1.1 Cable size considered sq. mm. 300
5.1.2 Cable ampacity as per vendor catalogue 457 Doha Cables, page-140
5.1.3 Ampacity after applying overall deration factor = (4.5) x (5.1.2) A 185.54
5.1.4 No. of parallel cable runs required - by calculation = (3.7) / (5.1.3) 1.69
5.1.5 No. of parallel cable runs required - whole number 2.00
5.1.6 Ampacity after applying overall deration factor & runs = (5.1.3) x (5.1.5) A 371.08
5.1.7 Is selected cable capable of carrying rated full load current YES
2 Source Data
3 Load Data
3.1 Load Feeder tag / Equipment Tag Number 302-37-KM-001-A
WAG Change over
3.2 Load description
Pump Motor
3.3 Load Rating - Name plate Kw 185
3.4 Power factor cosФ 0.9
3.5 Efficiency η 0.9
3.6 Voltage V 3300
3.7 Full load current - name plate A 39.959
5 Calculations 3 phase
5.1 Criterion: Ampacity with deration
5.1.1 Cable size considered sq. mm. 70
5.1.2 Cable ampacity as per vendor catalogue 193 Attachment-3, Table-B6
5.1.3 Ampacity after applying overall deration factor = (4.5) x (5.1.2) A 129.89
5.1.4 No. of parallel cable runs required - by calculation = (3.7) / (5.1.3) 0.31
5.1.5 No. of parallel cable runs required - whole number 1.00
5.1.6 Ampacity after applying overall deration factor & runs = (5.1.3) x (5.1.5) A 129.89
5.1.7 Is selected cable capable of carrying rated full load current YES
6 Conclusion
1 Run of 3Cx70sq.
6.1 For the given load, the selected cable size and length considered is
mm. & 0.25km
7 Notes
7.1 This calculation is typical for both the incomers of RMU connecting existing RLIC 11kV Cable ring network.
7.2 3C HV Cable, routed both direct in ground and in single way duct.
Source Data Load Data Cable De-Rating factor (Attachment-6) Voltage drop Criterion:
[11]=[8]/ {√3x[9]x[10]x[26]x1000}
SinØ (Calculated)
Load Rating (kW)
For Temperature
ACB/MCCB (A)
Efficiency [10]
deration factor
(sq.mm.) [19]
(Note-1) [14]
(Note-2) [15]
(Note-x) [16]
(Note-x) [17]
SI. No. [1]
[13]
[20]
[23]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
[33]
[34]
[35]
(Note-8) Number Description Physical Location [7] Remarks
[8]
[9]
[5] [6]
[2] [3] [4]
LV SWITCHGEAR
2 A6 ELP 0225 A6 SB 002 400V SWBD. A6 UPS 002 230V AC UPS-002 - FEEDER 1 (BY PASS) 12.75 400 0.9 24 - 80 0.73 0.9 - - 0.657 3C x 25 122 80.15 0.30 1.00 80.2 YES 0.85 0.53 - - 0.927 0.0895 0.03 0.26 - 1 YES
ROOM
LV SWITCHGEAR
3 A6 ELP 0226 A6 SB 002 400V SWBD. A6 UPS 003 230V AC UPS-003 - FEEDER 1 (BY PASS) 12.75 400 0.9 24 - 80 0.73 0.9 - - 0.657 3C x 25 122 80.15 0.30 1.00 80.2 YES 0.85 0.53 - - 0.927 0.0895 0.03 0.26 - 1 YES
ROOM
LV SWITCHGEAR
4 A6 ELP 0223 A6 SB 002 400V SWBD. A6 DB 015 SMALL POWER DB 12.5 400 1 21 - 63 0.73 0.9 - - 0.657 4C x 25 122 80.15 0.26 1.00 80.2 YES 0.85 0.53 - - 0.927 0.0895 0.03 0.23 - 1 YES
ROOM
LV SWITCHGEAR
5 A6 ELP 0224 A6 SB 002 400V SWBD. A6 DB 014 NORMAL LIGHTING DB 15 400 1 25 - 63 0.73 0.9 - - 0.657 4C x 25 122 80.15 0.31 1.00 80.2 YES 0.85 0.53 - - 0.927 0.0895 0.03 0.27 - 1 YES
ROOM
LV SWITCHGEAR
6 A6 ELP 0227 A6 SB 002 400V SWBD. A6 DB 013 EMERGENCY LIGHTING DB 1 400 1 2 - 63 0.73 0.9 - - 0.657 4C x 16 90 59.13 0.03 1.00 59.1 YES 0.85 0.53 - - 1.47 0.0817 0.03 0.03 - 1 YES
ROOM
LV SWITCHGEAR
7 A6 ELP 0232 A6 SB 002 400V SWBD. A6 HAC 001 SPLIT TYPE A/C UNIT 3 230 0.9 15 - 32 0.73 0.9 - - 0.657 2C x 6 51 33.51 0.45 1.00 33.5 YES 0.85 0.53 - - 3.93 0.09 0.03 1.33 - 5 YES
ROOM
LV SWITCHGEAR
8 A6 ELP 0233 A6 SB 002 400V SWBD. A6 HAC 002 SPLIT TYPE A/C UNIT 3 230 0.9 15 - 32 0.73 0.9 - - 0.657 2C x 6 51 33.51 0.45 1.00 33.5 YES 0.85 0.53 - - 3.93 0.09 0.03 1.33 - 5 YES
ROOM
LV SWITCHGEAR
9 A6 ELP 0234 A6 SB 002 400V SWBD. A6 HAC 003 SPLIT TYPE A/C UNIT 3 230 0.9 15 - 32 0.73 0.9 - - 0.657 2C x 6 51 33.51 0.45 1.00 33.5 YES 0.85 0.53 - - 3.93 0.09 0.03 1.33 - 5 YES
ROOM
LV SWITCHGEAR
10 A6 ELP 0235 A6 SB 002 400V SWBD. A6 HAC 004 SPLIT TYPE A/C UNIT 3 230 0.9 15 - 32 0.73 0.9 - - 0.657 2C x 6 51 33.51 0.45 1.00 33.5 YES 0.85 0.53 - - 3.93 0.09 0.03 1.33 - 5 YES
ROOM
LV SWITCHGEAR
11 A6 ELP 0221 A6 SB 002 400V SWBD. A6 UPS 002 230V AC UPS-002 38.4 400 1 65 - 125 0.73 0.9 - - 0.657 3C x 35 147 96.58 0.67 1.00 96.6 YES 0.85 0.53 - - 0.669 0.0823 0.03 0.52 - 1 YES Sized For Rectifier Input Max Power
ROOM
LV SWITCHGEAR
12 A6 ELP 0222 A6 SB 002 400V SWBD. A6 UPS 003 230V AC UPS-003 38.4 400 1 65 - 125 0.73 0.9 - - 0.657 3C x 35 147 96.58 0.67 1.00 96.6 YES 0.85 0.53 - - 0.669 0.0823 0.03 0.52 - 1 YES Sized For Rectifier Input Max Power
ROOM
LV SWITCHGEAR
13 A6 ELP 0236 A6 SB 002 400V SWBD. A6 CAP 001 LV CAPACITOR BANK 45 400 0.9 85 - 100 0.73 0.9 - - 0.657 3C x 35 147 96.58 0.88 1.00 96.6 YES 0.85 0.53 - - 0.669 0.0823 0.03 0.68 - 1 YES
ROOM
LV SWITCHGEAR
14 A6 ELP 0251 A6 UPS 002 400V SWBD. A6 DB 018 230V AC UPS DB (A6 DB 018) 2 230 1 10 - 63 0.73 0.9 - - 0.657 2C x 16 90 59.13 0.17 1.00 59.1 YES 0.85 0.53 - - 1.47 0.0817 0.015 0.17 - 1 YES Single Phase
ROOM
LV SWITCHGEAR
15 A6 ELP 0261 A6 UPS 003 400V SWBD. A6 DB 018 230V AC UPS DB (A6 DB 018) 2 230 1 10 - 63 0.73 0.9 - - 0.657 2C x 16 90 59.13 0.17 1.00 59.1 YES 0.85 0.53 - - 1.47 0.0817 0.015 0.17 - 1 YES Single Phase
ROOM
LV SWITCHGEAR
1 36-ELP-XXX1 36-SB-XXX1 400V SWBD. 36-HPP-XXX1 HVAC POWER PANEL - FEEDER 1 332 400 1 564 - 630 0.73 0.9 - - 0.657 4C x 240 488 320.62 1.76 2.00 641.2 YES 0.85 0.53 - - 0.099 0.0709 0.035 0.52 - 1 YES 2R x4C x 240 sq.mm.
ROOM
LV SWITCHGEAR
2 36-ELP-XXX2 36-SB-XXX1 400V SWBD. 36-DB-XXX2 NORMAL LIGHTING DB 44.9 400 1 76 - 125 0.73 0.9 - - 0.657 4C x 70 220 144.54 0.53 1.00 144.5 YES 0.85 0.53 - - 0.343 0.08 0.035 0.38 - 1 YES
ROOM
LV SWITCHGEAR
3 36-ELP-XXX3 36-SB-XXX1 400V SWBD. 36-DB-XXX3 SMALL POWER DISTR BOARD 73.0 400 1 124 - 200 0.73 0.9 - - 0.657 4C x 70 220 144.54 0.86 1.00 144.5 YES 0.85 0.53 - - 0.343 0.08 0.035 0.63 - 1 YES
ROOM
LV SWITCHGEAR
4 36-ELP-XXX4 36-SB-XXX1 400V SWBD. 36-UPS-XXX1B 230V AC UPS B - BY PASS 64 400 0.98 236 - 250 0.73 0.9 - - 0.657 4C x 150 375 246.38 0.96 1.00 246.38 YES 0.8 0.6 - - 0.16 0.0741 0.04 0.70 - 1 YES
ROOM
LV SWITCHGEAR
5 36-ELP-XXX5 36-SB-XXX1 400V SWBD. 36-UPS-XXX1A 230V AC UPS A - BY PASS 64 400 0.98 236 - 250 0.73 0.9 - - 0.657 4C x 150 375 246.38 0.96 1.00 246.38 YES 0.8 0.6 - - 0.16 0.0741 0.04 0.70 - 1 YES
ROOM
LV SWITCHGEAR
7 36-ELP-XX20 36-SB-XXX1 400V SWBD. 36-CAP-XXX1 LV CAPACITOR BANK 150 400 0.9 241 - 400 0.73 0.9 - - 0.657 4C x 185 410 269.37 0.89 1.00 269.37 YES 0 1 - - 0.129 0.072 0.03 0.23 - 1 YES
ROOM
LV SWITCHGEAR
8 36-ELP-XX22 36-SB-XXX1 400V SWBD. 36-HPP-XXX1 HVAC POWER PANEL - FEEDER 2 332 400 1 564 - 630 0.73 0.9 - - 0.657 4C x 240 488 320.62 1.76 2.00 641.23 YES 0.85 0.53 - - 0.099 0.0709 0.035 0.52 - 1 YES 2R x4C x 240 sq.mm.
ROOM
LV SWITCHGEAR
9 36-ELP-XX23 36-SB-XXX1 400V SWBD. 36-UPS-XXX1A 230V AC UPS A 144 400 1 208 - 250 0.73 0.9 - - 0.657 4C x 150 375 246.38 0.84 1.00 246.38 YES 0.8 0.6 - - 0.16 0.0741 0.04 0.62 - 1 YES
ROOM
LV SWITCHGEAR
10 36-ELP-XX24 36-SB-XXX1 400V SWBD. 36-UPS-XXX1B 230V AC UPS B 144 400 1 208 - 250 0.73 0.9 - - 0.657 4C x 150 375 246.38 0.84 1.00 246.38 YES 0.8 0.6 - - 0.16 0.0741 0.04 0.62 - 1 YES
ROOM
LV SWITCHGEAR
11 36-ELP-XX25 36-SB-XXX1 400V SWBD. 36-DB-XXX1 EMERGENCY LIGHTING DB 4.3 400 1 7 - 63 0.73 0.9 - - 0.657 4C x 25 122 80.15 0.09 1.00 80.15 YES 0.85 0.53 - - 0.927 0.0895 0.035 0.09 - 1 YES
ROOM
LV SWITCHGEAR
12 36-ELP-XX26 36-SB-XXX1 400V SWBD. 36-DB-XXX4 MOV - DISTR. BOARD 6.3 400 1 13 - 63 0.73 0.9 - - 0.657 4C x 25 122 80.15 0.16 1.00 80.15 YES 0.68 0.73 - - 0.927 0.0895 0.04 0.16 - 1 YES
ROOM
13 36-ELP-XX27 36-SB-XXX1 400V SWBD. 36-XX-XXX1 EOT CRANE EDG ROOM EDG ROOM 15 400 0.9 35 - 63 0.73 0.9 - - 0.657 4C x 16 90 59.13 0.59 1.00 59.13 YES 0.68 0.73 - - 1.47 0.0817 0.035 0.56 - 1 YES
14 36-ELP-XX28 36-SB-XXX1 400V SWBD. 36-LCP-XXX1 EDG LOCAL CONTROL PANEL EDG ROOM 10 400 0.9 24 - 63 0.73 0.9 - - 0.657 4C x 10 69 45.33 0.53 1.00 45.33 YES 0.68 0.73 - - 2.33 0.096 0.035 0.60 - 1 YES
LV SWITCHGEAR
14 36-ELP-XX55 36-UPS-XXX1A 400V SWBD. 36-DB-XXX5 230V AC UPS DB (36-DB-XXX5) 1 230 1 5 - 40 0.73 0.9 - - 0.657 2C x 10 69 45.33 0.11 1.00 45.3 YES 0.85 0.53 - - 2.33 0.096 0.015 0.13 - 1 YES Single Phase
ROOM
LV SWITCHGEAR
15 36-ELP-XX77 36-UPS-XXX1B 400V SWBD. 36-DB-XXX5 230V AC UPS DB (36-DB-XXX5) 1 230 1 5 - 40 0.73 0.9 - - 0.657 2C x 10 69 45.33 0.11 1.00 45.3 YES 0.85 0.53 - - 2.33 0.096 0.015 0.13 - 1 YES Single Phase
ROOM
Notes:
3 Cable ampacity is based on Multi core cables with Three Loaded conductors,refer current rating table of Doha cables in Attachment-6.
4 Allowable voltage drop for LV cables between LV Switchboards to equipment shall be as per Section 4.5 of Cable Sizing document 4172-GENON-2-12-0006.
5 Only Main interconnecting cables between LV Switchboard and distribution boards/ equipements located in staion A6 E-House and JCWF station are listed in this attachments.
6 For cable sizing of outgoing cables from distribution boards (Normal lighting, Emergency lighting ,Small power,MOV DB and UPS DBs) please refer Attachment-3
ATTACHMENT - 2 LV CABLE SIZING CALCULATIONS
Source Data Load Data Cable De-Rating factor (Attachment-6) Voltage drop Criterion:
[11]=[8]/ {√3x[9]x[10]x[26]x1000}
SinØ (Calculated)
Load Rating (kW)
For Temperature
ACB/MCCB (A)
Efficiency [10]
deration factor
(sq.mm.) [19]
(Note-1) [14]
(Note-2) [15]
(Note-x) [16]
(Note-x) [17]
SI. No. [1]
starting%
Normal%
Cable Tag Number Source
Source Tag Number Load Tag Number Load Description
[13]
[20]
[23]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
[33]
[34]
[35]
(Note-8) Description Physical Location [7] Remarks
[8]
[9]
[3] [5] [6]
[2] [4]
1 A6 ELP 0220 A6 SB 002 400V SWBD. A6 WSKT 06 WELDING OUTLET STATION A6 25 400 1 74 - 125 0.54 0.95 0.73 0.97 0.363 4C x 70 220 79.92 0.93 1.00 79.92 YES 0.85 0.53 - - 0.343 0.08 0.17 1.82 - 4 - YES
2 A6 ELP 0228 A6 SB 002 400V SWBD. A6 TRU 001 CPTR FOR BURIED PIPELINE STATION A6 1.5 400 0.8 3 - 20 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.11 1.00 27.61 YES 0.85 0.53 - - 2.33 0.096 0.21 0.55 - 4 - YES
3 A6 ELP 0229 A6 SB 002 400V SWBD. A6 MOV 001 MOV - STATION A6 INLET VALVE STATION A6 2 400 0.72 6 - 80 0.54 0.95 0.73 0.97 0.363 3C x 10 76 27.61 0.22 1.00 27.61 YES 0.68 0.73 - - 2.33 0.096 0.15 0.64 - 4 - YES
4 A6 ELP 0230 A6 SB 002 400V SWBD. A6 MOV 002 MOV - PIG LAUNCHER BY PASS LINE VALVE STATION A6 2 400 0.72 6 - 63 0.54 0.95 0.73 0.97 0.363 3C x 10 76 27.61 0.22 1.00 27.61 YES 0.68 0.73 - - 2.33 0.096 0.14 0.60 - 4 - YES
5 A6 ELP 0231 A6 SB 002 400V SWBD. A6 MOV 003 MOV - PIG LAUNCHER OUTLET VALVE STATION A6 2 400 0.72 6 - 63 0.54 0.95 0.73 0.97 0.363 3C x 10 76 27.61 0.22 1.00 27.61 YES 0.68 0.73 - - 2.33 0.096 0.13 0.56 - 4 - YES
A.1 A6 DB 014 : 400/230V NORMAL LIGHTING DISTRIBUTION BOARD (STATION A6) - OUTDOOR FLOODLIGHTS
1 A6 EL 0362 A6 DB 014 400V CIRCUIT #4 LED FLOOD LIGHTS - PLANT STATION A6 2.26 400 0.9 5 - 16 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.18 1.00 27.61 YES 0.68 0.73 - - 2.33 0.096 0.3 1.07 - 4.0 - YES
2 A6 EL 0363 A6 DB 014 400V CIRCUIT #5 LED FLOOD LIGHTS - PLANT STATION A6 2.26 400 0.9 5 - 16 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.18 1.00 27.61 YES 0.68 0.73 - - 2.33 0.096 0.3 1.07 - 4.0 - YES
3 A6 EL 0364 A6 DB 014 400V CIRCUIT #6 LED FLOOD LIGHTS - PLANT STATION A6 2.7 400 0.9 6 - 16 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.22 1.00 27.61 YES 0.68 0.73 - - 2.33 0.096 0.3 1.29 - 4.0 - YES
4 A6 EL 0365 A6 DB 014 400V CIRCUIT #7 LED FLOOD LIGHTS - PLANT STATION A6 2.7 400 0.9 6 - 16 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.22 1.00 27.61 YES 0.68 0.73 - - 2.33 0.096 0.3 1.29 - 4.0 - YES
1 36-ELP-XXX6 30-SB-XXX1 400V SWBD. 36-TRU-XXX1 CP TRANSFORMER RECTIFIER JCWF AREA 2.5 415 0.8 5 20 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.18 1.00 27.61 YES 0.85 0.53 - - 2.33 0.096 0.19 0.81 - 3 - YES
2 36-ELP-XXX8 30-SB-XXX1 400V SWBD. 30-SB-XXX1-WSKT2 WELDING SOCKET 2 JCWF AREA 25 400 1 42 125 0.54 0.95 0.73 0.97 0.363 4C x 70 220 79.92 0.53 1.00 79.92 YES 0.85 0.53 - - 0.343 0.08 0.23 1.40 - 4 - YES
3 36-ELP-XXX9 30-SB-XXX1 400V SWBD. 30-SB-XXX1-WSKT1 WELDING SOCKET 1 JCWF AREA 25 400 1 42 125 0.54 0.95 0.73 0.97 0.363 4C x 70 220 79.92 0.53 1.00 79.92 YES 0.85 0.53 - - 0.343 0.08 0.2 1.21 - 4 - YES
4 36-ELP-XXX14A 30-SB-XXX1 400V SWBD. 36-A-6201-PM-01A DEMULSIFIER PUMP MOTOR A JCWF AREA 0.55 400 0.9 1 7.5 20 0.54 0.95 0.73 0.97 0.363 3C x 4 46 16.71 0.06 1.00 16.71 YES 0.68 0.73 0.3 0.95 5.88 0.0933 0.22 0.39 1.32 4 15 YES
5 36-ELP-XXX14B 30-SB-XXX1 400V SWBD. 36-A-6201-PM-01B DEMULSIFIER PUMP MOTOR B JCWF AREA 0.55 400 0.9 1 7.5 20 0.54 0.95 0.73 0.97 0.363 3C x 4 46 16.71 0.06 1.00 16.71 YES 0.68 0.73 0.3 0.95 5.88 0.0933 0.22 0.39 1.32 4 15 YES
6 36-ELP-XXX15A 30-SB-XXX1 400V SWBD. 36-A-6201-PM-02A DEMULSIFIER PUMP MOTOR A JCWF AREA 0.55 400 0.9 1 7.5 20 0.54 0.95 0.73 0.97 0.363 3C x 4 46 16.71 0.06 1.00 16.71 YES 0.68 0.73 0.3 0.95 5.88 0.0933 0.22 0.39 1.32 4 15 YES
7 36-ELP-XXX15B 30-SB-XXX1 400V SWBD. 36-A-6201-PM-02B DEMULSIFIER PUMP MOTOR B JCWF AREA 0.55 400 0.9 1 7.5 20 0.54 0.95 0.73 0.97 0.363 3C x 4 46 16.71 0.06 1.00 16.71 YES 0.68 0.73 0.3 0.95 5.88 0.0933 0.22 0.39 1.32 4 15 YES
7 36-ELP-XXX15B 30-SB-XXX1 400V SWBD. UNLOADING PUMP SOCKET FOR DEMULSIFIER PAKAGE UNLOADING PUMP JCWF AREA 1 400 0.9 2 7.5 20 0.54 0.95 0.73 0.97 0.363 3C x 4 46 16.71 0.12 1.00 16.71 YES 0.68 0.73 0.3 0.95 5.88 0.0933 0.22 0.77 2.65 4 15 YES
9 36-ELP-XXX20 30-SB-XXX1 400V SWBD. EOT CRANE EOT CRANE FOR IA COMPRESSOR SHADE JCWF AREA 7.5 400 0.86 16 7.5 40 0.54 0.95 0.73 0.97 0.363 4C x 16 98 35.60 0.45 1.00 35.60 YES 0.81 0.59 0.3 0.95 1.47 0.0817 0.25 2.15 6.74 4 15 YES
10 36-ELP-XXX30 30-SB-XXX1 400V SWBD. 36-PM-0002 WASH WATER PUMP JCWF AREA 0.37 400 0.9 1 7.5 20 0.54 0.95 0.73 0.97 0.363 3C x 4 46 16.71 0.06 1.00 16.71 YES 0.68 0.73 0.3 0.95 5.88 0.0933 0.24 0.42 1.44 4 15 YES
11 36-ELP-XXX31 30-SB-XXX1 400V SWBD. 36-MJB-XX31 JUNCTION BOX 1- WELLHEAD MAIN DB DK969 34.08 400 1 55 - 100 0.54 0.95 0.73 0.97 0.363 4C x 95 265 96.26 0.57 1.00 96.26 YES 0.9 0.44 - - 0.248 0.0733 0.05 0.30 - 0.35 - YES
12 36-ELP-XXX31/1 36-MJB-XX31 400V SWBD. DK969-MJB-X31 JUNCTION BOX 2- WELLHEAD MAIN DB DK969 34.08 400 1 55 - 100 0.54 0.95 0.73 0.97 0.363 4C x 185 375 136.22 0.40 2.00 272.44 YES 0.9 0.44 - - 0.129 0.072 1.34 2.36 - 2.50 - YES 2R x4C x 185 sq.mm.
13 36-ELP-XXX32 30-SB-XXX1 400V SWBD. 36-MJB-XX32 JUNCTION BOX 1- WELLHEAD MAIN DB DK965 40.4 400 1 65 - 100 0.54 0.95 0.73 0.97 0.363 4C x 95 265 96.26 0.68 1.00 96.26 YES 0.9 0.44 - - 0.248 0.0733 0.05 0.36 - 0.40 - YES
14 36-ELP-XXX32/1 36-MJB-XX32 400V SWBD. DK965-MJB-X32 JUNCTION BOX 2- WELLHEAD MAIN DB DK965 40.4 400 1 65 - 100 0.54 0.95 0.73 0.97 0.363 4C x 240 435 158.02 0.41 2.00 316.03 YES 0.9 0.44 - - 0.099 0.0709 1.65 2.79 - 2.95 - YES 2R x4C x 240 sq.mm.
15 36-ELP-XXX33 30-SB-XXX1 400V SWBD. DK960-MDB-XX1 DK960 MAIN DISTRIBUTION BOARD - 400/230V AC WELLHEAD AREA 10.3 400 1 16 - 63 0.54 0.95 0.73 0.97 0.363 4C x 50 185 67.20 0.24 1.00 67.20 YES 0.9 0.44 - - 0.494 0.08 0.63 2.09 - 2.5 - YES
16 36-ELP-XXX 30-SB-XXX1 400V SWBD. WINCH MOTOR WINCH MOTOR POWER SOCKET FLARE AREA 3.5 400 0.86 7 7.5 20 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.25 1.00 27.61 YES 0.81 0.59 0.3 0.95 2.33 0.096 0.4 2.36 7.19 4 15 YES
17 36-ELP-XXX34 36-DB-XXX5 400V SWBD. 36-LP-8001 FLARE CONTROL PANEL FLARE AREA 1.0 230 1 5 - 10 0.54 0.95 0.73 0.97 0.363 2C x 16 98 35.60 0.14 1.00 35.60 YES 0.8 0.6 - - 1.47 0.0817 0.4 1.85 - 4 - YES
18 36-ELP-XXX36 30-SB-XXX1 400V SWBD. 36-AT-0007 GAS CHROMATOGRAPH - A/C UNIT & AUX JCWF AREA 6.0 400 1 11 - 32 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.40 1.00 27.61 YES 0.8 0.6 - - 2.33 0.096 0.22 2.01 - 4 - YES
19 36-ELP-XXX37 30-SB-XXX1 400V SWBD. 36-AT-0008 CO2 ANALYZERS - A/C UNIT & AUXILIARIES JCWF AREA 6.0 400 1 11 - 32 0.54 0.95 0.73 0.97 0.363 4C x 16 98 35.60 0.31 1.00 35.60 YES 0.8 0.6 - - 1.47 0.0817 0.23 1.34 - 4 - YES
20 36-ELP-XXX38 30-SB-XXX1 400V SWBD. 36-AT-0009 CO2 ANALYZERS - A/C UNIT & AUXILIARIES JCWF AREA 6.0 400 1 11 - 32 0.54 0.95 0.73 0.97 0.363 4C x 16 98 35.60 0.31 1.00 35.60 YES 0.8 0.6 - - 1.47 0.0817 0.22 1.28 - 4 - YES
B.1 36-DB-XXX2: 400/230V NORMAL LIGHTING DISTRIBUTION BOARD (JCWF) - OUTDOOR FLOODLIGHTS
1 36-EL-XX34 36-DB-XXX2 400V CIRCUIT #8 LED FLOOD LIGHTS - PLANT JCWF AREA 2.03 400 0.9 5 - 16 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.18 1.00 27.61 YES 0.68 0.73 - - 2.33 0.096 0.3 1.07 - 4.0 - YES
2 36-EL-XX35 36-DB-XXX2 400V CIRCUIT #9 LED FLOOD LIGHTS - PLANT JCWF AREA 2.03 400 0.9 5 - 16 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.18 1.00 27.61 YES 0.68 0.73 - - 2.33 0.096 0.3 1.07 - 4.0 - YES
3 36-EL-XX36 36-DB-XXX2 400V CIRCUIT #10 LED FLOOD LIGHTS - PLANT JCWF AREA 2.03 400 0.9 5 - 16 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.18 1.00 27.61 YES 0.68 0.73 - - 2.33 0.096 0.3 1.07 - 4.0 - YES
4 36-EL-XX37 36-DB-XXX2 400V CIRCUIT #11 LED FLOOD LIGHTS - PLANT JCWF AREA 2.03 400 0.9 5 - 16 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.18 1.00 27.61 YES 0.68 0.73 - - 2.33 0.096 0.3 1.07 - 4.0 - YES
5 36-EL-XX38 36-DB-XXX2 400V CIRCUIT #12 LED FLOOD LIGHTS - PLANT JCWF AREA 2.03 400 0.9 5 - 16 0.54 0.95 0.73 0.97 0.363 4C x 16 98 35.60 0.14 1.00 35.60 YES 0.68 0.73 - - 1.47 0.0817 0.45 1.03 - 4.0 - YES
6 36-EL-XX39 36-DB-XXX2 400V CIRCUIT #13 LED FLOOD LIGHTS - PLANT JCWF AREA 2.03 400 0.9 5 - 16 0.54 0.95 0.73 0.97 0.363 4C x 16 98 35.60 0.14 1.00 35.60 YES 0.68 0.73 - - 1.47 0.0817 0.45 1.03 - 4.0 - YES
ATTACHMENT - 2 LV CABLE SIZING CALCULATIONS
Source Data Load Data Cable De-Rating factor (Attachment-6) Voltage drop Criterion:
[11]=[8]/ {√3x[9]x[10]x[26]x1000}
SinØ (Calculated)
Load Rating (kW)
For Temperature
ACB/MCCB (A)
Efficiency [10]
deration factor
(sq.mm.) [19]
(Note-1) [14]
(Note-2) [15]
(Note-x) [16]
(Note-x) [17]
SI. No. [1]
starting%
Normal%
Cable Tag Number Source
Source Tag Number Load Tag Number Load Description
[13]
[20]
[23]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
[33]
[34]
[35]
(Note-8) Description Physical Location [7] Remarks
[8]
[9]
[3] [5] [6]
[2] [4]
7 36-EL-XX40 36-DB-XXX2 400V CIRCUIT #14 LED FLOOD LIGHTS - PLANT JCWF AREA 3.6 400 0.9 8 - 16 0.54 0.95 0.73 0.97 0.363 4C x 16 98 35.60 0.22 1.00 35.60 YES 0.68 0.73 - - 1.47 0.0817 0.45 1.65 - 4.0 - YES
8 36-EL-XX41 36-DB-XXX2 400V CIRCUIT #15 LED FLOOD LIGHTS - FLARE JCWF AREA 3.6 400 0.9 8 - 16 0.54 0.95 0.73 0.97 0.363 4C x 16 98 35.60 0.22 1.00 35.60 YES 0.68 0.73 - - 1.47 0.0817 0.3 1.10 - 4.0 - YES
9 36-EL-XX42 36-DB-XXX2 400V CIRCUIT #16 LED FLOOD LIGHTS - PLANT JCWF AREA 1.8 400 0.9 4 - 16 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.14 1.00 27.61 YES 0.68 0.73 - - 2.33 0.096 0.45 1.29 - 4.0 - YES
10 36-EL-XX43 36-DB-XXX2 400V CIRCUIT #17 LED FLOOD LIGHTS - FLARE FLARE AREA 2.03 400 0.9 5 - 16 0.54 0.95 0.73 0.97 0.363 4C x 16 98 35.60 0.14 1.00 35.60 YES 0.68 0.73 - - 1.47 0.0817 0.28 0.64 - 4.0 - YES
11 36-EL-XX44 36-DB-XXX2 400V CIRCUIT #18 LED FLOOD LIGHTS - FLARE FLARE AREA 2.03 400 0.9 5 - 16 0.54 0.95 0.73 0.97 0.363 4C x 16 98 35.60 0.14 1.00 35.60 YES 0.68 0.73 - - 1.47 0.0817 0.28 0.64 - 4.0 - YES
12 36-EL-XX45 36-DB-XXX2 400V CIRCUIT #19 LED FLOOD LIGHTS - FLARE FLARE AREA 2.7 400 0.9 6 - 16 0.54 0.95 0.73 0.97 0.363 4C x 16 98 35.60 0.17 1.00 35.60 YES 0.68 0.73 - - 1.47 0.0817 0.28 0.77 - 4.0 - YES
13 36-EL-XX46 36-DB-XXX2 400V CIRCUIT #20 LED FLOOD LIGHTS - FLARE FLARE AREA 2.7 400 0.9 6 - 16 0.54 0.95 0.73 0.97 0.363 4C x 16 98 35.60 0.17 1.00 35.60 YES 0.68 0.73 - - 1.47 0.0817 0.28 0.77 - 4.0 - YES
1 36-ELP-X165 36-DB-XXX4 MOV DB 36-MOV-0001 MOV - RAW CRUDE 10" LINE JCWF AREA 2 400 0.9 5 7 20 0.54 0.95 0.73 0.97 0.363 3C x 10 76 27.61 0.18 1.00 27.61 YES 0.68 0.73 0.3 0.95 2.33 0.096 0.15 0.54 1.80 4 15 YES
2 36-ELP-X166 36-DB-XXX4 MOV DB 36-MOV-XX13 MOV - DENSE PHASE CO2 16" LINE JCWF AREA 2.5 400 0.9 6 7 20 0.54 0.95 0.73 0.97 0.363 3C x 10 76 27.61 0.22 1.00 27.61 YES 0.68 0.73 0.3 0.95 2.33 0.096 0.15 0.64 2.16 4 15 YES
3 36-ELP-X167 36-DB-XXX4 MOV DB 36-MOV-XX10 MOV - DENSE PHASE CO2 16" LINE JCWF AREA 2.5 400 0.9 6 7 20 0.54 0.95 0.73 0.97 0.363 3C x 10 76 27.61 0.22 1.00 27.61 YES 0.68 0.73 0.3 0.95 2.33 0.096 0.15 0.64 2.16 4 15 YES
4 36-ELP-X168 36-DB-XXX4 MOV DB 36-MOV-XX11 MOV - DENSE PHASE CO2 16" LINE JCWF AREA 2.5 400 0.9 6 7 20 0.54 0.95 0.73 0.97 0.363 3C x 10 76 27.61 0.22 1.00 27.61 YES 0.68 0.73 0.3 0.95 2.33 0.096 0.15 0.64 2.16 4 15 YES
5 36-ELP-X169 36-DB-XXX4 MOV DB 36-MOV-XXX1 MOV - DENSE PHASE CO2 16" LINE JCWF AREA 2.5 400 0.9 6 7 20 0.54 0.95 0.73 0.97 0.363 3C x 10 76 27.61 0.22 1.00 27.61 YES 0.68 0.73 0.3 0.95 2.33 0.096 0.15 0.64 2.16 4 15 YES
1 31-ELP-XXX1 31-MCC-0001-A 415V MCC 31-A-0001-PM-0001A CORROSSION INHIBITOR INJECTION PUMP MOTOR-A JMDS 0.37 415 0.9 1 7 20 0.54 0.95 0.73 0.97 0.363 3C x 6 58 21.07 0.05 1.00 21.07 YES 0.68 0.73 0.3 0.95 3.93 0.09 0.24 0.27 0.89 4 15 YES DELETED
2 31-ELP-XXX2 31-MCC-0001-B 415V MCC 31-A-0001-PM-0001B CORROSSION INHIBITOR INJECTION PUMP MOTOR-B JMDS 0.37 415 0.9 1 7 20 0.54 0.95 0.73 0.97 0.363 3C x 6 58 21.07 0.05 1.00 21.07 YES 0.68 0.73 0.3 0.95 3.93 0.09 0.24 0.27 0.89 4 15 YES DELETED
3 31-ELP-XXX4 31-MCC-0001-A 415V MCC 31-AT-XXX1 GAS CHROMATOGRAPH - 240V NON-UPS SUPPLY JMDS 6 240 0.9 41 - 40 0.54 0.95 0.73 0.97 0.363 2C x 25 130 47.22 0.87 1.00 47.22 YES 0.68 0.73 0.3 0.95 0.927 0.0895 0.15 3.57 - 4 - YES
4 31-ELP-XXX3 31-MCC-0001-B 415V MCC 31-MOV-0001 MOTORIZED OPERATED VALVE JMDS 2 415 0.9 5 - 16 0.54 0.95 0.73 0.97 0.363 3C x 10 76 27.61 0.18 1.00 27.61 YES 0.68 0.73 0.3 0.95 2.33 0.096 0.2 0.69 - 4 - YES
LV SWITCHGEAR
1 72-1-ELP-XXX1 72-SBV-01-MDB-102 415V SWBD. 72-1-TRU-XX1 CP TRANSFORMER RECTIFIER 1.5 415 0.9 3 20 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.11 1.00 27.61 YES 0.85 0.53 - - 2.33 0.096 0.31 0.79 - 3 - YES
ROOM
LV SWITCHGEAR
1 72-21-ELP-XXX1 72SBV21-MDB-001 415V SWBD. 72-21-TRU-XX1 CP TRANSFORMER RECTIFIER 1.5 415 0.9 3 20 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.11 1.00 27.61 YES 0.85 0.53 - - 2.33 0.096 0.27 0.69 - 3 - YES
ROOM
LV SWITCHGEAR
1 T3-ELP-XXX1 T3-MDB-001 415V SWBD. T3-TRU-XX1 CP TRANSFORMER RECTIFIER 1.5 415 0.9 3 20 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.11 1.00 27.61 YES 0.85 0.53 - - 2.33 0.096 0.27 0.69 - 3 - YES
ROOM
LV SWITCHGEAR
1 B-ELP-XXX1 B-SB-600 415V SWBD. B-TRU-XX1 CP TRANSFORMER RECTIFIER 1.6 415 0.9 3 20 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.11 1.00 27.61 YES 0.85 0.53 - - 2.33 0.096 0.12 0.31 - 3 - YES
ROOM
1 DK969-ELP-X01 DK969-MJB-X31 400V SWBD. DK969-MDB-XX1 WELLHEAD MAIN DB DK969 34.08 400 1 55 - 100 0.54 0.95 0.73 0.97 0.363 4C x 95 265 96.26 0.57 1.00 96.26 YES 0.9 0.44 - - 0.248 0.0733 0.02 0.12 - 0.15 - YES
2 DK969-ELP-XX1 DK969-MDB-XX1 400V MDB. DK969-DB-XX1 INJECTION WELLHEAD DB WELLHEAD AREA 17.8 400 0.9 32 - 63 0.54 0.95 0.73 0.97 0.363 4C x 35 158 57.39 0.56 1.00 57.39 YES 0.9 0.44 - - 0.669 0.0823 0.22 1.95 - 2 - YES
3 DK969-ELP-XX2 DK969-MDB-XX1 400V MDB. DK970-DB-XX1 PRODUCTION WELLHEAD DB WELLHEAD AREA 18.5 400 0.9 33 - 63 0.54 0.95 0.73 0.97 0.363 4C x 120 305 110.79 0.30 1.00 110.79 YES 0.9 0.44 - - 0.197 0.0707 0.22 0.66 - 2 - YES
4 DK969-ELP-XX3 DK969-MDB-XX1 400V MDB. DK971-DB-XX1 PRODUCTION WELLHEAD DB WELLHEAD AREA 18.5 400 0.9 33 - 63 0.54 0.95 0.73 0.97 0.363 4C x 120 305 110.79 0.30 1.00 110.79 YES 0.9 0.44 - - 0.197 0.0707 0.48 1.43 - 2 - YES
5 DK969-ELP-XX4 DK969-MDB-XX1 400V MDB. DK972-DB-XX1 PRODUCTION WELLHEAD DB WELLHEAD AREA 17.8 400 0.9 32 - 63 0.54 0.95 0.73 0.97 0.363 4C x 95 265 96.26 0.33 1.00 96.26 YES 0.9 0.44 - - 0.248 0.0733 0.36 1.27 - 2 - YES
6 DK965-ELP-X01 DK965-MJB-X32 400V SWBD. DK965-MDB-XX1 WELLHEAD MAIN DB DK965 40.4 400 1 65 - 100 0.54 0.95 0.73 0.97 0.363 4C x 95 265 96.26 0.68 1.00 96.26 YES 0.9 0.44 - - 0.248 0.0733 0.02 0.14 - 0.15 - YES
7 DK965-ELP-XX1 DK965-MDB-XX1 400V MDB. DK964-DB-XX1 INJECTION WELLHEAD DB WELLHEAD AREA 23.5 400 0.9 42 - 63 0.54 0.95 0.73 0.97 0.363 4C x 150 335 121.69 0.35 1.00 121.69 YES 0.9 0.44 - - 0.16 0.0741 0.24 0.77 - 1.5 - YES
8 DK965-ELP-XX2 DK965-MDB-XX1 400V MDB. DK965-DB-XX1 PRODUCTION WELLHEAD DB WELLHEAD AREA 18.5 400 0.9 33 - 63 0.54 0.95 0.73 0.97 0.363 4C x 35 158 57.39 0.57 1.00 57.39 YES 0.9 0.44 - - 0.669 0.0823 0.02 0.18 - 1.5 - YES
9 DK965-ELP-XX3 DK965-MDB-XX1 400V MDB. DK966-DB-XX1 PRODUCTION WELLHEAD DB WELLHEAD AREA 18.5 400 0.9 33 - 63 0.54 0.95 0.73 0.97 0.363 4C x 240 435 158.02 0.21 2.00 316.03 YES 0.9 0.44 - - 0.099 0.0709 1.55 1.33 - 1.5 - YES 2R x4C x 240 sq.mm.
10 DK965-ELP-XX4 DK965-MDB-XX1 400V MDB. DK967-DB-XX1 PRODUCTION WELLHEAD DB WELLHEAD AREA 18.5 400 0.9 33 - 63 0.54 0.95 0.73 0.97 0.363 4C x 185 375 136.22 0.24 2.00 272.44 YES 0.9 0.44 - - 0.129 0.072 1.15 1.21 - 1.5 - YES 2R x4C x 185 sq.mm.
11 DK965-ELP-XX5 DK965-MDB-XX1 400V MDB. DK968-DB-XX1 PRODUCTION WELLHEAD DB WELLHEAD AREA 18.5 400 0.9 33 - 63 0.54 0.95 0.73 0.97 0.363 4C x 150 335 121.69 0.27 1.00 121.69 YES 0.9 0.44 - - 0.16 0.0741 0.39 0.98 - 1.5 - YES
ATTACHMENT - 2 LV CABLE SIZING CALCULATIONS
Source Data Load Data Cable De-Rating factor (Attachment-6) Voltage drop Criterion:
[11]=[8]/ {√3x[9]x[10]x[26]x1000}
SinØ (Calculated)
Load Rating (kW)
For Temperature
ACB/MCCB (A)
Efficiency [10]
deration factor
(sq.mm.) [19]
(Note-1) [14]
(Note-2) [15]
(Note-x) [16]
(Note-x) [17]
SI. No. [1]
starting%
Normal%
Cable Tag Number Source
Source Tag Number Load Tag Number Load Description
[13]
[20]
[23]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
[33]
[34]
[35]
(Note-8) Description Physical Location [7] Remarks
[8]
[9]
[3] [5] [6]
[2] [4]
12 DK960-ELP-XX2 DK960-MDB-XX1 400V MDB. DK962-DB-XX1 OBSEVATION WELLHEAD DB DK962 5.1 400 0.9 9 - 40 0.54 0.95 0.73 0.97 0.363 4C x 25 130 47.22 0.19 1.00 47.22 YES 0.9 0.44 - - 0.927 0.0895 0.21 0.72 - 2.5 - YES
1 36-ELP-XX68 36-DB-XXX1A UPS MDB DK960-MDB-XX2 DK960-MDB-XX2 UPS SUPPLY-1 DK960 2.78 230.0 1 15 - 40 0.54 0.95 0.73 0.97 0.363 2C x 70 220 79.92 0.19 1.00 79.92 YES 0.8 0.6 - - 0.343 0.08 0.68 2.86 - 4.00 - YES
2 36-ELP-XX90 36-DB-XXX1B UPS MDB DK960-MDB-XX2 DK960-MDB-XX2 UPS SUPPLY-2 DK960 2.78 230.0 1 15 - 40 0.54 0.95 0.73 0.97 0.363 2C x 70 220 79.92 0.19 1.00 79.92 YES 0.8 0.6 - - 0.343 0.08 0.68 2.86 - 4.00 - YES
3 DK960-ELP-X22 DK960-MDB-XX2 UPS MDB DK962-DB-XX2 DK962-DB-XX2 UPS SUPPLY-1 DK962 1.39 230.0 1 8 - 25 0.54 0.95 0.73 0.97 0.363 2C x 50 185 67.20 0.12 1.00 67.20 YES 0.8 0.6 - - 0.494 0.08 0.21 0.65 - 1.00 - YES
4 DK960-ELP-X25 DK960-MDB-XX2 UPS MDB DK962-DB-XX2 DK962-DB-XX2 UPS SUPPLY-2 DK962 1.39 230.0 1 8 - 25 0.54 0.95 0.73 0.97 0.363 2C x 50 185 67.20 0.12 1.00 67.20 YES 0.8 0.6 - - 0.494 0.08 0.21 0.65 - 1.00 - YES
5 36-ELP-XX69 36-DB-XXX1A UPS MDB DK964-MDB-XX2 DK964-MDB-XX2 UPS SUPPLY-1 DK964 6.29 230 1 34 - 80 0.54 0.95 0.73 0.97 0.363 2C x 240 435 158.02 0.22 2.00 316.03 YES 0.8 0.6 - - 0.099 0.0709 1.95 3.51 - 3.7 - YES 2R x2C x 240 sq.mm.
6 36-ELP-XX91 36-DB-XXX1B UPS MDB DK964-MDB-XX2 DK964-MDB-XX2 UPS SUPPLY-2 DK964 6.29 230 1 34 - 80 0.54 0.95 0.73 0.97 0.363 2C x 240 435 158.02 0.22 2.00 316.03 YES 0.8 0.6 - - 0.099 0.0709 1.95 3.51 - 3.7 - YES 2R x2C x 240 sq.mm.
7 DK964-ELP-X20 DK964-MDB-XX2 UPS MDB DK965-DB-XX2 DK965-DB-XX2 UPS SUPPLY-1 DK965 1.25 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 95 265 96.26 0.07 1.00 96.26 YES 0.8 0.6 - - 0.248 0.0733 0.22 0.32 - 0.5 - YES
8 DK964-ELP-X27 DK964-MDB-XX2 UPS MDB DK965-DB-XX2 DK965-DB-XX2 UPS SUPPLY-2 DK965 1.25 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 95 265 96.26 0.07 1.00 96.26 YES 0.8 0.6 - - 0.248 0.0733 0.22 0.32 - 0.5 - YES
9 DK964-ELP-X21 DK964-MDB-XX2 UPS MDB DK966-DB-XX2 DK966-DB-XX2 UPS SUPPLY-1 DK966 1.25 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 185 375 136.22 0.05 2.00 272.44 YES 0.8 0.6 - - 0.129 0.072 1.3 0.58 - 1.0 - YES 2R x2C x 185 sq.mm.
10 DK964-ELP-X28 DK964-MDB-XX2 UPS MDB DK966-DB-XX2 DK966-DB-XX2 UPS SUPPLY-2 DK966 1.25 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 185 375 136.22 0.05 2.00 272.44 YES 0.8 0.6 - - 0.129 0.072 1.3 0.58 - 1.0 - YES 2R x2C x 185 sq.mm.
11 DK964-ELP-X22 DK964-MDB-XX2 UPS MDB DK967-DB-XX2 DK967-DB-XX2 UPS SUPPLY-1 DK967 1.25 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 150 335 121.69 0.06 2.00 243.38 YES 0.8 0.6 - - 0.16 0.0741 0.95 0.50 - 1.0 - YES 2R x2C x 150 sq.mm.
12 DK964-ELP-X29 DK964-MDB-XX2 UPS MDB DK967-DB-XX2 DK967-DB-XX2 UPS SUPPLY-2 DK967 1.25 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 150 335 121.69 0.06 2.00 243.38 YES 0.8 0.6 - - 0.16 0.0741 0.95 0.50 - 1.0 - YES 2R x2C x 150 sq.mm.
13 DK964-ELP-X23 DK964-MDB-XX2 UPS MDB DK968-DB-XX2 DK968-DB-XX2 UPS SUPPLY-1 DK968 1.25 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 95 265 96.26 0.07 1.00 96.26 YES 0.8 0.6 - - 0.248 0.0733 0.2 0.30 - 1.0 - YES
14 DK964-ELP-X30 DK964-MDB-XX2 UPS MDB DK968-DB-XX2 DK968-DB-XX2 UPS SUPPLY-2 DK968 1.25 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 95 265 96.26 0.07 1.00 96.26 YES 0.8 0.6 - - 0.248 0.0733 0.2 0.30 - 1.0 - YES
15 36-ELP-XX70 36-DB-XXX1A UPS MDB DK969-MDB-XX2 DK969-MDB-XX2 UPS SUPPLY-1 DK969 5.13 230 1 28 - 80 0.54 0.95 0.73 0.97 0.363 2C x 150 335 121.69 0.23 2.00 243.38 YES 0.8 0.6 - - 0.16 0.0741 1.5 3.15 - 3.5 - YES 2R x2C x 150 sq.mm.
16 36-ELP-XX92 36-DB-XXX1B UPS MDB DK969-MDB-XX2 DK969-MDB-XX2 UPS SUPPLY-2 DK969 5.13 230 1 28 - 80 0.54 0.95 0.73 0.97 0.363 2C x 150 335 121.69 0.23 2.00 243.38 YES 0.8 0.6 - - 0.16 0.0741 1.5 3.15 - 3.5 - YES 2R x2C x 150 sq.mm.
17 DK969-ELP-X20 DK969-MDB-XX2 UPS MDB DK970-DB-XX2 DK970-DB-XX2 UPS SUPPLY-1 DK970 1.25 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 95 265 96.26 0.07 1.00 96.26 YES 0.8 0.6 - - 0.248 0.0733 0.22 0.32 - 1 - YES
18 DK969-ELP-X26 DK969-MDB-XX2 UPS MDB DK970-DB-XX2 DK970-DB-XX2 UPS SUPPLY-2 DK970 1.25 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 95 265 96.26 0.07 1.00 96.26 YES 0.8 0.6 - - 0.248 0.0733 0.22 0.32 - 1 - YES
19 DK969-ELP-X21 DK969-MDB-XX2 UPS DB DK971-DB-XX2 DK971-DB-XX2 UPS SUPPLY-1 DK971 1.25 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 120 305 110.79 0.06 1.00 110.79 YES 0.8 0.6 - - 0.197 0.0707 0.36 0.44 - 1 - YES
20 DK969-ELP-X27 DK969-MDB-XX2 UPS DB DK971-DB-XX2 DK971-DB-XX2 UPS SUPPLY-2 DK971 1.25 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 120 305 110.79 0.06 1.00 110.79 YES 0.8 0.6 - - 0.197 0.0707 0.36 0.44 - 1 - YES
21 DK969-ELP-X22 DK969-MDB-XX2 UPS DB DK972-DB-XX2 DK972-DB-XX2 UPS SUPPLY-1 DK972 1.37 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 95 265 96.26 0.07 1.00 96.26 YES 0.8 0.6 - - 0.248 0.0733 0.22 0.32 - 1 - YES
22 DK969-ELP-X28 DK969-MDB-XX2 UPS DB DK972-DB-XX2 DK972-DB-XX2 UPS SUPPLY-2 DK972 1.37 230 1 7 - 25 0.54 0.95 0.73 0.97 0.363 2C x 95 265 96.26 0.07 1.00 96.26 YES 0.8 0.6 - - 0.248 0.0733 0.22 0.32 - 1 - YES
Notes:
5 Cable ampacity is based on Multi core cables with Three Loaded conductors,refer current rating table of Doha cables in Attachment-6.
6 Allowable voltage drop for LV cables between LV Switchboards to equipment shall be as per Section 4.5 of Cable Sizing document 4172-GENON-2-12-0006.
7 Only Main interconnecting cables between LV Switchboard and distribution boards/ equipements are listed in this attachments.
8 For cable sizing of outgoing cables from distribution boards (Normal lighting, Emergency lighting ,Small power,MOV DB,UPS DBs, Wellhead Normal & UPS DBs) please refer Attachment-3
Source Data Load Data Cable De-Rating factor (Attachment-6) Voltage drop Criterion:
Is voltage drop
Full load Total De- No. of parallel No. of parallel Ampacity after Can selected
Load Circuit For Group of For Thermal Cable size Cable Ampacity after Power SinØ Cable Cable Cable Length within
SI. Cable Tag Number Source Tag Source Voltage current (A) For Temperature For Laying Depth rating factor cable runs cable runs applying overall cable carry % Voltage
Load Tag Number Load Description Physical Location Rating EFFICIE Protection Cables Resistivity considered ampacity applying overall factor (Calculate Resistance Reactance Considered permissible
No. (Note-9) Number Description (V) A.C [9]=[7]/ (Note-2) (Note-4) [14] = [10] x required - by required - deration factor & rated full load drop Remarks
[5] [6A] [6B] (kW) NCY ACB/MCCB (A) (Note-1) (Note-3) (sq.mm.) (Note-5) deration factor (CosØ) d) (Ω/km) (Ω/km) (km) limit? (4%)
[1] [2] [3] [4] [8] {√3x[8]x[22]x [11] [13] [11] x [12] x calculation whole number runs current? [27]
[7] [9A] [10] [12] [15] [16] [17] = [14] x [15] [22] [23] [24] [25] [26] Note-9
1000} [13] [18] = [9] / [17] [19] [20] = [17] x [19] [21]
[28]
1 A6 ELP XX2 A6 SB XX1 400V SWBD. A6SBXX1-XX-WSKT WELDING OUTLET STATION A6 35 400 59 125.0 0.54 0.95 0.73 0.97 0.363 2C x 16 185 67.20 0.88 1.00 67.20 YES 0.85 0.53 #N/A #N/A 0.04 #N/A #N/A
2 A6 ELP XX3 A6 SB XX1 400V SWBD. A6 TRU XX1 CPTR FOR BURIED PIPELINE STATION A6 1.6 400 3 20.0 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.11 1.00 27.61 YES 0.8 0.6 2.33 0.096 0.09 0.22 YES
CP TRANSFORMER
1 36-ELP-XXX6 30-SB-XXX1 400V SWBD. 36-TRU-XXX1 JCWF AREA 1.6 400 0.9 3 20.0 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.11 1.00 27.61 YES 0.8 0.6 2.33 0.096 0.09 0.22 YES
RECTIFIER
CP TRANSFORMER
2 36-ELP-XXX7 30-SB-XXX1 400V SWBD. 36-TRU-XXX2 JCWF AREA 1.6 400 0.9 3 20.0 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.11 1.00 27.61 YES 0.8 0.6 2.33 0.096 0.09 0.22 YES
RECTIFIER
3 36-ELP-XXX8 30-SB-XXX1 400V SWBD. 30-SB-XXX1-WSKT2 WELDING SOCKET 2 JCWF AREA 35 400 0.9 59 125.0 0.54 0.95 0.73 0.97 0.363 4C x 50 185 67.20 0.88 1.00 67.20 YES 0.85 0.53 0.494 0.08 0.09 1.06 YES
4 36-ELP-XXX9 30-SB-XXX1 400V SWBD. 30-SB-XXX1-WSKT1 WELDING SOCKET 1 JCWF AREA 35 400 0.9 59 125.0 0.54 0.95 0.73 0.97 0.363 4C x 50 185 67.20 0.88 1.00 67.20 YES 0.85 0.53 0.494 0.08 0.05 0.59 YES
5 36-ELP-XXX14 30-SB-XXX1 400V SWBD. 36-A-0003-PM-01A DEMULSIFIER PUMP MOTOR A JCWF AREA 0.37 400 0.9 1 20.0 0.54 0.95 0.73 0.97 0.363 3C x 4 46 16.71 0.06 1.00 16.71 YES 0.8 0.6 5.88 0.0933 0.09 0.19 YES
5 36-ELP-XXX15 30-SB-XXX1 400V SWBD. 36-A-0003-PM-01B DEMULSIFIER PUMP MOTOR B JCWF AREA 0.37 400 0.9 1 20.0 0.54 0.95 0.73 0.97 0.363 3C x 4 46 16.71 0.06 1.00 16.71 YES 0.8 0.6 5.88 0.0933 0.09 0.19 YES
8 36-ELP-XXX30 30-SB-XXX1 400V SWBD. 36-PM-0002 WASH WATER PUMP JCWF AREA 0.37 400 0.9 1 20.0 0.54 0.95 0.73 0.97 0.363 3C x 4 46 16.71 0.06 1.00 16.71 YES 0.8 0.6 5.88 0.0933 0.09 0.19 YES
WELLHEAD DB AT EAST OF
11 36-ELP-XXX33 30-SB-XXX1 400V SWBD. DK960-MDB-XX1 WELLHEAD AREA 8.5 400 0.9 15 63.0 0.54 0.95 0.73 0.97 0.363 4C x 35 158 57.39 0.26 1.00 57.39 YES 0.8 0.6 0.669 0.0823 0.55 2.09 YES
JCWF
12 36-ELP-XXX34 30-SB-XXX1 400V SWBD. 36-ECP-XXX2 FLARE CONTROL PANEL JCWF AREA 7 400 0.9 12 32.0 0.54 0.95 0.73 0.97 0.363 4C x 16 98 35.60 0.34 1.00 35.60 YES 0.85 0.53 1.47 0.0817 0.32 2.15 YES
CP TRANSFORMER LV SWITCHGEAR
1 T3-ELP-XXX1 T3-MDB-001 415V SWBD. T3-TRU-XX1 1.6 415 3 16.0 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.11 1.00 27.61 YES 0.8 0.6 2.33 0.096 0.2 0.48 YES
RECTIFIER ROOM
CP TRANSFORMER LV SWITCHGEAR
1 B-ELP-XXX1 B-SB-600 415V SWBD. B-TRU-XX1 1.6 415 3 16.0 0.54 0.95 0.73 0.97 0.363 4C x 10 76 27.61 0.11 1.00 27.61 YES 0.8 0.6 2.33 0.096 0.2 0.48 YES
RECTIFIER ROOM
Notes:
1 Reduction factor for grouping of cables is based on Table 7 , Doha Cables of Page no:130
2 Reduction factor for temperature is based on Table-2 , Doha Cables of Page no:128
3 Reduction factor for soil thermal resistivity is based on Table-5 , Doha Cables of Page no:129
4 Reduction factor for depth of laying is based on Table 4 , Doha Cables of Page no:129
5 Cable ampacity is based on Doha cables page no:146 , Multi core cables with Three Loaded conductors,
6 Please refer Station A6 Electrical Cable schedule, MGDA6-2-37-0001 for details of cables.
7 Please refer Station JCWF Electrical Cable schedule, JCWF-2-37-0001 for details of cables.
8 Please refer Electrical Cable Schedule (Station Block Valves 72-SBV1, 72-SBV21, Station T3 & Station B)
9 Allowable voltage drop for LV cables between LV Switchboards to equipment shall be as per Section 5.3 of Cable Sizing document 4172-GENON-2-12-0006.
10 For Cable tag numbers, refer Electrical Cable schedule.
Motor
Circuit Total De- No. of parallel Selected Starting Starting Is voltage drop
Load starting Cable size Cable Ampacity after SinØ Cable Cable Cable Length
SI. Cable Tag Number Source Tag Load Tag Voltage Protection rating factor cable runs No. of parallel Power current % Voltage within
Source Description Load Description Rating current (A) considered ampacity applying overall (Calculate Resistance Reactance Considered
No. (Note-1) Number Number Physical Location [6B] (V) A.C ACB/MCCB [14] = [10] x required - by cable runs - factor multiplying drop permissible Remarks
[4] [6A] (kW) [9]=[7]/ (sq.mm.) (Note-5) deration factor d) (Ω/km) (Ω/km) (km)
[1] [2] [3] [5] [8] (A) [11] x [12] x calculation whole number (CosØ) factor [28] limit? (20%)
[7] {√3x[8]x[22]x [15] [16] [17] = [14] x [15] [23] [24] [25] [26]
[9A] [13] [18] = [9] / [17] [19] [22] [27] [29]
1000}
INSTRUMENT AIR
1 E1-ELP-029 E1 SB 001 415V SWBD. KM E1 01 CNG AREA - OUTDOOR 22 415 102 63 0.658 4C x 25 127 83.57 1.22 1.00 0.3 0.95 0.926 0.08 0.25 4 15.06 YES
COMPRESSOR PACKAGE - 1
INSTRUMENT AIR
1 E1-ELP-038 E1 SB 002 415V SWBD. KM E1 02 CNG AREA - OUTDOOR 22 415 102 63 0.658 4C x 25 127 83.57 1.22 1.00 0.3 0.95 0.926 0.08 0.25 4 15.06 YES
COMPRESSOR PACKAGE - 2
III E1 ECP 001: ELECTRICAL CONTROL PANEL (CNG K-001) [From SAFE drawings] NOTE-6
1 E1-ELP-044 E1 ECP 001 ELEC. CTRL. PANEL TBA WATER PUMP MOTOR CNG AREA - OUTDOOR 5.5 415 32 13 0.658 3C x 6 54 35.54 0.90 1.00 0.3 0.95 3.92 0.09 0.25 4 16.85 YES
2 E1-ELP-045 E1 ECP 001 ELEC. CTRL. PANEL TBA OIL PUMP MOTOR CNG AREA - OUTDOOR 2.2 415 13 6 0.658 3C x 2.5 32 21.06 0.62 1.00 0.3 0.95 9.44 0.1 0.25 4 15.88 YES
EXTRACTOR MOTOR COMP.
3 E1-ELP-046 E1 ECP 001 ELEC. CTRL. PANEL TBA CNG AREA - OUTDOOR 0.55 415 3 2 0.658 3C x 2.5 32 21.06 0.14 1.00 0.3 0.95 9.44 0.1 0.25 4 3.66 YES
ROOM
4 E1-ELP-048 E1 ECP 001 ELEC. CTRL. PANEL TBA FAN 1 MOTOR CNG AREA - OUTDOOR 1.8 415 10 5 0.658 3C x 2.5 32 21.06 0.47 1.00 0.3 0.95 9.44 0.1 0.25 4 12.22 YES
5 E1-ELP-049 E1 ECP 001 ELEC. CTRL. PANEL TBA FAN 2 MOTOR CNG AREA - OUTDOOR 1.8 415 10 5 0.658 3C x 2.5 32 21.06 0.47 1.00 0.3 0.95 9.44 0.1 0.25 4 12.22 YES
6 E1-ELP-050 E1 ECP 001 ELEC. CTRL. PANEL TBA FAN 3 MOTOR CNG AREA - OUTDOOR 1.8 415 10 5 0.658 3C x 2.5 32 21.06 0.47 1.00 0.3 0.95 9.44 0.1 0.25 4 12.22 YES
7 E1-ELP-051 E1 ECP 001 ELEC. CTRL. PANEL TBA FAN 4 MOTOR CNG AREA - OUTDOOR 1.8 415 10 5 0.658 3C x 2.5 32 21.06 0.47 1.00 0.3 0.95 9.44 0.1 0.25 4 12.22 YES
8 E1-ELP-052 E1 ECP 001 ELEC. CTRL. PANEL TBA FAN 5 MOTOR CNG AREA - OUTDOOR 1.8 415 10 5 0.658 3C x 2.5 32 21.06 0.47 1.00 0.3 0.95 9.44 0.1 0.25 4 12.22 YES
9 E1-ELP-053 E1 ECP 001 ELEC. CTRL. PANEL TBA FAN 6 MOTOR CNG AREA - OUTDOOR 1.8 415 10 5 0.658 3C x 2.5 32 21.06 0.47 1.00 0.3 0.95 9.44 0.1 0.25 4 12.22 YES
10 E1-ELP-054 E1 ECP 001 ELEC. CTRL. PANEL TBA FAN 7 MOTOR CNG AREA - OUTDOOR 1.8 415 10 5 0.658 3C x 2.5 32 21.06 0.47 1.00 0.3 0.95 9.44 0.1 0.25 4 12.22 YES
11 E1-ELP-055 E1 ECP 001 ELEC. CTRL. PANEL TBA FAN 8 MOTOR CNG AREA - OUTDOOR 1.8 415 10 5 0.658 3C x 2.5 32 21.06 0.47 1.00 0.3 0.95 9.44 0.1 0.25 4 12.22 YES
12 E1-ELP-056 E1 ECP 001 ELEC. CTRL. PANEL TBA FAN 9 MOTOR CNG AREA - OUTDOOR 1.8 415 10 5 0.658 3C x 2.5 32 21.06 0.47 1.00 0.3 0.95 9.44 0.1 0.25 4 12.22 YES
13 E1-ELP-057 E1 ECP 001 ELEC. CTRL. PANEL TBA FAN 10 MOTOR CNG AREA - OUTDOOR 1.8 415 10 5 0.658 3C x 2.5 32 21.06 0.47 1.00 0.3 0.95 9.44 0.1 0.25 4 12.22 YES
CNG GAS COMPRESSOR
14 E1-ELP-200 E1 ECP 001 ELEC. CTRL. PANEL TBA CNG AREA - OUTDOOR 400 415 1085 800 0.658 3C x 240 538 354.04 3.06 2.00 0.53 0.85 0.0961 0.08 0.13 1.5 5.25 YES 2R x3C x 240 sq.mm.
MOTOR (VSD Driven)
Notes:
1 For Cable tag numbers, refer Electrical Cable schedule Doc. No. 3892-CNGARRS1-2-37-0001.