Professional Documents
Culture Documents
WDM Section 07 Treated Effluent Systems R3
WDM Section 07 Treated Effluent Systems R3
Revision: 03
The content of this document material is a property of Haya Water. No part of this document in whole or in part,
may be reproduced in any form, by photocopy, microfilm, scanning or any other means, or incorporated into any
information retrieval system, electronic or mechanical, without the written permission of Haya water Management.
Document No: AM-ENG-WDM-07 Issue Date: 29/09/2016
Classification: Revision: 03
i Revision History
The following is a brief summary of the most recent revisions to this document. Details of all revisions
prior to these are held on file by the issuing department.
Revision
Date Scope / Remarks
No.
0 13/04/2006 Document approved and issued
01 01/06/2008 To incorporate Tender Board and Veolia comments
02 31/12/2010 To incorporate latest changes as per current International standards.
03 29/09/2016 Updated as part of the Haya Water Technical Standards Upgrading
project
HAYA Water
M/s Halcrow on Behalf of Haya Water Asset Management / Projects / O&M
Suleiman Al Qasmi
Classification: Revision: 03
TABLE OF CONTENTS
i Revision History................................................................................................................ 2
ii Current Revision: 03 dated 29/09/2016 ............................................................................ 2
iii Document Authorisation .................................................................................................. 2
1. Introduction ................................................................................................................... 6
1.1. Purpose ...................................................................................................................... 6
1.2. Scope .......................................................................................................................... 6
1.3. Objective .................................................................................................................... 6
1.4. Distribution/Target Audience .................................................................................... 6
1.5. Definitions .................................................................................................................. 7
1.6. Standards ................................................................................................................... 7
1.7. Abbreviations ............................................................................................................. 8
2. Treated Effluent System Description and Components.............................................10
2.1. General ......................................................................................................................10
2.2. Treated Effluent Supply System ..............................................................................10
2.2.1. Storage Tanks/Reservoirs.....................................................................................10
2.2.2. Pumping Stations .................................................................................................. 11
2.2.3. Transmission Mains .............................................................................................. 11
2.2.4. Distribution Mains ................................................................................................. 11
2.2.5. Sea Outfall and Groundwater Recharge .............................................................. 11
2.2.6. Tanker Filling Stations .......................................................................................... 11
2.2.7. Re-Chlorination Stations ......................................................................................12
2.2.8. Combination Air/Vacuum Valves ..........................................................................12
2.2.9. Washouts (Scour Valves) ......................................................................................12
2.2.10. Isolation Valves ..................................................................................................12
2.2.11. Chambers ...........................................................................................................12
3. Basic Design Consideration ........................................................................................13
3.1. Planning and Design Horizon ..................................................................................13
3.2. General Planning ......................................................................................................13
3.3. Data Collection ..........................................................................................................14
3.4. Pre-Design Data Collection and Review ..................................................................14
3.5. Design Phase Data Collection..................................................................................14
4. Treated Effluent Water Demand ...................................................................................16
4.1. Treated Effluent Use and Demand ...........................................................................16
Classification: Revision: 03
Classification: Revision: 03
Classification: Revision: 03
1. Introduction
1.1. Purpose
The purpose of this document is to communicate the technical requirements and preferences of
Haya Water for the Treated Effluent Systems.
1.2. Scope
i. The scope of this Manual is to provide technical guidance to the Designer regarding key system
elements for treated effluent systems. This Manual shall be applicable to all Haya Water projects,
and shall be read in conjunction with the relevant standard Specifications of all other documents
or any Contract requirements or Particular Specification, or both. Any clause in the Manual which
relates to Works or materials not required by any particular Contract shall be deemed not to
apply.
ii. The Manual address the minimum standards for each aspect of a treated effluent system and
takes into account hydraulic performance, overall civic design, and network planning philosophy.
In general, a treated effluent system acts similarly to a pressurised potable water supply network
with two notable exceptions: for an irrigation system less importance is placed on water quality
and supply reliability.
iii. The contents of this document shall be read in conjunction with all Haya Water Technical
Specifications. Compliance with the contents of Haya Water Technical Specifications shall be an
integral requirement of this document.
1.3. Objective
i. The objective of this Manual is to ensure that all designs are carried out to a uniform high
standard, in line with Haya Water’s intentions and best international practices. Incorporating the
requirements and criteria of this Manual will ease Haya Water’s technical review and approval
process in the implementation of projects.
ii. The Manual is intended for use by Designers who are knowledgeable and experienced in the
design of wastewater collection, transfer, and treatment processes. The Designers need to be
fully familiar with the contents of the Manual.
iii. Requirements and criteria included in the Manual are not purported to cover all design conditions.
The Manual is a guide and not meant to preclude the use of experienced engineering judgement
for specific design situations. Designers shall address all necessary aspects for their particular
project in consultation with the Engineer, and any proposed deviations from the Manual must be
discussed and agreed upon with the Engineer prior to commencement of the Works.
Classification: Revision: 03
1.5. Definitions
i. Client/Owner: Oman Wastewater Services Company (Haya Water) for whom the Works are to
be undertaken
i. Owner Representative/Engineer: The firm or company named in the Contract as appointed by
the Client to supervise and administer the Contract
ii. Consultant: The firm or company selected by the Client to prepare the Particular Specification
(the Contract documents) for a given project
iii. Contractor: The company or organisation responsible for the construction of the Works and who
have entered into a Contract with the Client
iv. Designer: Any person carrying out design activities for or on behalf of any of the parties
mentioned previously. A person involved in any changes to existing or proposed Works shall be
deemed to be a Designer.
v. Site: The land allocated for the Works
ii. Project Documents: All documents associated with and applicable to the Contract
vi. Particular Specification: The Specification associated with the Contract and prepared at the
time of the project by the Engineer specifically for that application
vii. Technical definitions related to this Manual are to be found within the appropriate technical
clauses in the document.
1.6. Standards
CIRIA Report 128 Guide to design of thrust blocks for buried pressure pipelines
BS 4346 Joints and fittings for use with PVC-U pressure pipes
BS 5150 Specification for cast iron wedge and double disk gate valves for
general purposes
BS 5154 Specification for copper alloy globe, globe stop and check, and
check and gate valves for general purposes
BS 8007 Code of practice for design of concrete structures for retaining
aqueous liquids
Classification: Revision: 03
ASTM D1785 American standard for testing of material for PVC pipes
1.7. Abbreviations
ASTM ASTM International (formerly American Society for Testing and Materials)
BS British Standard
DI Ductile Iron
EN European Norm
TE Treated Effluent
Classification: Revision: 03
UV Ultraviolet
°C Degree Celsius
km Kilometre
kN Kilo newton
m Metre
mm Millimetre
Classification: Revision: 03
2.1. General
Treated Effluent (TE) is the water available, after the treatment of domestic wastewater, at
sewage treatment plants (STPs), generally to be used for variety of irrigation applications, such
as the irrigation of food crops and non-food crops, and watering of public parks and landscape
areas. To be suitable for re-use as irrigation water, the TE must meet the quality standards
defined in the Haya Water Concession Agreement.
a) Haya Water Treated effluent systems typically include the following:
Transmission and distribution pipelines
Storage tanks/reservoirs
Pumping stations and booster stations
Disinfection facility
Tanker filling stations
b) Where TE water is used for irrigation purposes, the treated effluent quality shall be in
accordance with the Standard A or B, stipulated in the Ministerial Decision 145/1993 dated 13
June 1993 by Ministry of Environment and Climate Affairs. For any other reuse applications
not mentioned in the Ministerial Decision 145/1993, shall be referred to the concerned
Ministry for approval.
c) In case, the TE water is to be discharged in to the marine environment, the quality standard
stipulated in Ministerial decision No. 159/2005 of MRMEWR shall be followed. (The
Ministerial Decision 145/1993 and the Ministerial Decision 159/2005 are include in the
Section 5 Sewage Treatment Plant Design Manual.
Classification: Revision: 03
supply system should have a storage tanks/reservoirs of minimum 1 day average demand
storage capacity Pumping Stations
2.2.2. Pumping Stations
The purpose of the TE pump stations is to transfer TE from one location to another, distribute it
throughout the systems, boost the pressure, and feed tanker filling stations. Due to large diurnal
and monthly demand fluctuations, variable speed pumps are generally used in the distribution
system. In transmission mains and tanker filling stations, constant speed pumps are preferred
due to the constant delivery heads.
2.2.3. Transmission Mains
Transmission mains transfer treated effluent from production sources (wastewater treatment
plants) to areas of concentrated demand or zonal storage facilities, and have limited direct
consumer connections. Transmission mains are distinct from distribution mains in size
arrangement, and operation. Transmission mains should be designed such that the bulk transfer
of water to each zonal district or demand cluster can be independently controlled. During network
design, an interface between transmission and distribution mains should be made such that the
transmission mains have a single, or very few, connections to each district or demand cluster.
This allows the transfer of water to each district to be easily controlled or isolated, or both.
Similarly, a transmission main should maintain one, or very few, discrete (unmixed) connections
from each source or storage.
2.2.4. Distribution Mains
Distribution mains are defined in this Manual as a pipeline minimum 100mm (ID) in diameter.
Pipelines that are smaller than 100 mm in diameter are typically landscaping feeder lines or are
individual consumer connections. These pipelines run over short distances and can be
categorised as service laterals.
a) The interface between the distribution network and service lateral must be separated by an
isolation valve such as a small hand-operated ball valve or tap valve. The interface with
landscaping or irrigation feeder lines is called an customer connection chamber which,
among other features, contains a small hand operated tap or valve, flow meter,
b) At locations where a distribution main interfaces with a transmission main, an isolation valve
must be provided, which preferably will be automated for ease and flexibility in operational
control.
c) Distribution network pipelines are to be thoroughly looped and interconnected, providing
multiple paths of flow to every consumer connection. This will not only minimise pressure
losses but also will minimise the number of consumers disrupted during maintenance or
repairs to the distribution network. Whilst the distinction between transmission and
distribution mains may not be clear in the existing TE network, any changes, upgrades, or
new pipes must follow these guidelines to incrementally improve the TE system operations
and functionality.
2.2.5. Sea Outfall and Groundwater Recharge
Sea outfalls discharge bulk quantities of excess TSE into the sea along the coastline. Other
discharge points for the excess TSE have been located inland for the purpose of groundwater
recharge, and shall be operated as such in the future. These are to be represented in network
hydraulic assessments as open boundaries controlled by flow or pressure.
2.2.6. Tanker Filling Stations
Tanker filling stations are required to fill tankers that supply consumers outside of the distribution
network. A filling station shall comprise a holding tank and a minimum of two filling bays.
Classification: Revision: 03
Classification: Revision: 03
Classification: Revision: 03
each alternative or option shall be estimated for comparison purposes. The best overall design for
the area shall then be selected, leading to the production of the final construction drawings.
Classification: Revision: 03
requirements, and other related studies. The results of the ground investigations should be
presented in an interpretative report.
h) Environmental studies and Environmental Impact Assessment (EIA), if specified. The
environmental studies should consider all design, construction, maintenance, and demolition
of the Works.
i) Flow logging to verify previously collected data and calculations.
j) Review of services reservations to ensure economical use of space.
k) Review of planning and approvals requirements and identification of any conflicts.
Classification: Revision: 03
Classification: Revision: 03
Hedges 10 L/m/day
Ground Cover 10 L/m2/day
Grass 12 L/m2/day
i) Typical planting densities for conceptual design purposes are shown in Table 4. It is
important, however, especially when designing small distribution schemes that consultation is
carried out with a landscape architect to verify the exact plant demands, planting densities,
and other relevant factors.
Table 4. Planting Density
Plant Spacing
Trees 15 m
Shrubs 3m
j) Roads and Junctions Landscaping: Different degrees of landscaping along a service corridor
may be considered depending on the width of the right-of-way (ROW), the availability of TSE,
and available space within a road service corridor.
In the absence of specific vegetation type information and subject to the concerned
Municipality approval, a TE demand of 10 L/m2/day can be used for roads and junctions
considering mixed vegetation type.
Classification: Revision: 03
Percentage
Month
Demand (%)
January 50
February 50
March 75
April 75
May 75
June 100
July 100
August 100
September 75
October 75
November 75
December 50
a) The TE system shall be sized to accommodate the peak demand experienced during the
summer months. The actual water requirements must be strictly monitored so that the TE
amounts can be adjusted to reflect the seasonal changes. This practice will save water,
decrease energy costs, and promote healthy growth of landscaping.
b) The diurnal variation of TE demands during a 24-hour cycle will exhibit a strong confluence of
demands during optimum landscaping irrigation times.
c) Large consumers and their irrigation timings have a strong influence on network hydraulic
assessment results. Any consumer with an average daily demand larger than 500 m3/day is
to be studied individually, and an irrigation timing pattern shall be applied that reflects its
actual settings.
d) For consumers with large internal storage tanks, demand is to be distributed evenly for the
number of hours storage is provided relative to the consumer’s total average demand.
e) TE demand fluctuation is to be represented in a hydraulic model using diurnal patterns which
shall be obtained from the concerned authority and/or private customers for individual
demands. Samples of diurnal patterns are given in Figures 1 and 2 as a reference only.
Classification: Revision: 03
Classification: Revision: 03
5. Design Considerations
5.1. Disinfection
TE water is often used in close proximity to the general public, therefore, requiring the disinfection
of TE. There are two options: chemical disinfection or the use of ultraviolet light.
5.1.1. Chemical Disinfection
Chemical disinfection of TE water shall consist of a duty/standby system dosing chlorine gas,
sodium hypochlorite or calcium hypochlorite. The system shall be installed on the inlet to the TE
storage tanks/reservoirs and shall be sized to dose the maximum flow entering the tank. Chlorine
monitors shall be installed on the outlet of the storage tanks/reservoirs, and an alarm shall be
raised if the chlorine level drops below 0.5 mg/L.
a) In addition, secondary chlorination would also be required to ensure a residual chlorine of 0.5
mg/L at the point of transfer. A similar monitoring system as the previous should also be
installed at the point of transfer. As per the Haya Water Concession Agreement, the residual
chlorine of TE water at point of End-users shall be between 0.3 to 1.0 mg/L.
5.1.2. Ultraviolet Disinfection
Ultraviolet (UV) disinfection is not suitable for applications that require 100 percent pathogen kill
and is therefore of limited application for recycled water disinfection. Furthermore, UV disinfection
does not provide protection against pathogens in the pipeline. If used, the UV plant should meet
the following specifications:
a) The UV disinfection phase should consist of at least two units arranged in a duty/standby
configuration.
b) On-line monitoring of the upstream suspended solids/turbidity content of the influent shall be
carried out.
c) Continuous monitoring of the UV dose supplied shall be installed.
d) In addition chlorine dosing is required to maintain the minimum residual chlorine
requirements in the TE water.
Classification: Revision: 03
d) All chambers shall be constructed with dismantling joints to transmit the axial thrusts along
the pipelines. Chambers shall also be designed to restrain axial thrust loads through their
walls (by using puddle flanges or thrust flanges, or both) in case internal fittings are removed
and blank flanges fitted.
e) The minimum working pressure available at any connection point in the TE network should
not be less than 1.5 bars, considering downstream valves, strainer, piping, and irrigation
devices (that is, sprinklers and similar components) head losses. The maximum pressure in
the transmission and distribution network shall be limited to 7.0 bar.
f) No TE transmission or distribution mains shall be laid below 2.5 m depth unless approved by
the Client.
g) Air/vacuum valves shall be placed at all highpoints.
h) Washouts shall be placed at all low points.
i) Isolation valves shall be installed in the TE network at all key strategic locations and
connections between primary and secondary mains, secondary and distribution mains, and
connections to local irrigation systems.
j) During the hydraulic design of the system, consideration must be given to maximum and
minimum water levels in pump station wet wells and storage tanks/reservoirs. Minimum flow
and head requirements must be meet throughout the system under all conditions.
k) Pipelines shall be designed to be fully primed at all times to avoid surge problems.
l) Dead legs in pipelines shall be avoided, if possible, to reduce the risk of stagnation of TE and
deposition of sediment.
m) Ring type distribution mains are preferable to single lines to allow uninterrupted supply during
maintenance.
n) Distribution networks shall be set up in discreet zones, where possible, with closed valves at
the boundaries to make flow monitoring, leak detection, and pressure regulation easier and to
allow flexibility of supply in the event of routine maintenance or a burst.
Classification: Revision: 03
5.5. Highways
The laying of pipes in the highways shall be accordance with the Omani Highways Design
Standards 2010, or latest edition, in consultation with the Highways Authority.
Classification: Revision: 03
6. Design Parameters
Transmissions
16 bar
mains Mechanical coupler
GRP All
Distribution / Laminated joints
16 bar
systems
Mechanical
DI All 16 bar All restraint or thrust
blocks
Classification: Revision: 03
where:
V = Full bore velocity (m/s) 𝑖 = Hydraulic gradient (m/m)
𝑔 = acceleration due to gravity (m 2/s) 𝑘𝑠 = Roughness coefficient (mm)
D = diameter (m) 𝑣= Kinematic viscosity of water (m 2/s)
where:
i = Hydraulic gradient (m/m) L = Pipe length (m)
H = Friction head loss (m)
g) The calculation of friction head loss using the Darcy-Weisbach formula is shown in Equation
3. The Darcy’s coefficient (f) shall be derived from tables or software.
Equation 3 – Head Loss (Darcy-Weisbach)
fLV 2
H=
2gd
where:
H = Friction head loss (m) g = acceleration due to gravity (m2/s)
f = Darcy’s coefficient (dimensionless) d = diameter (m)
Classification: Revision: 03
15 1.141
25 0.897
35 0.727
where:
hL = Head loss (m) V = Velocity (m/s)
k= Head loss coefficient (dimensionless) g = acceleration due to gravity (m2/s)
Classification: Revision: 03
13 Exit 1.0
Classification: Revision: 03
Classification: Revision: 03
a) In addition to the protection to the pipelines, the banks of the Wadi shall be provided with
protection, as shown in the standard detail drawings, to stabilise the bank and allow for easy
future identification of the crossing point.
b) For pipes running in close parallel with or in the Wadi bed, protection shall be applied per
Table 12, suitably modified to the specific installation and subject to the Engineer’s approval.
c) The Designer shall endeavour to avoid locating chambers in or close to a Wadi. Any chamber
that is required to be constructed in a Wadi shall be designed as a water retaining structure
capable of withstanding external water pressure to at least 5 m above the maximum Wadi
flow depth. Due consideration shall be given to proper water stops in the structural design
and flotation risk. The chamber shall be provided with sealed bolt down covers designed to
withstand the greater of 10 m positive and negative pressure, or the maximum Wadi flow
depth plus 5 m.
d) If an air valve or wash-out is required in a Wadi, the same basic design parameters shall be
adopted as per a chamber. An air valve chamber shall require a vent pipe extending from the
manhole to a suitable point outside the maximum water level.
e) For any construction in or close to a Wadi, the Engineer should be consulted and shall be
responsible for approving all proposed pipeline and chamber designs.
Classification: Revision: 03
a) Air Valves: The size of the air valve will normally be from 50 to 200 mm, depending on the
pipe diameter, the predicted flow rate of air, and the configuration of the system. Typical
double orifice air valve selection is shown in Table 11.
Table 11. Typical Double Orifice Air Valve Selection
≤100 50
150- 250 80
b) The maximum distance between the air-release valves should not exceed 800 m, or 1,000 m
along flat runs.
c) Washouts: Washouts shall be provided to facilitate drainage of pipeline segments for
maintenance and repairs. Washout valves shall generally be installed at all low points in the
pipeline profile and on uphill sides of mainline valves. The minimum diameter of washout
valves and associated piping shall be 100 mm. The following guidelines shall be used for the
sizing of washout pipe as a minimum requirement:
Up to 400 mm: 100 mm washout pipe
500 to 800 mm: 150 mm washout pipe
900 to 1200 mm: 200 mm washout pipe
1,200 mm and above: 300 mm washout pipe
d) Washouts shall be located inside the concrete chambers. All chambers shall be large enough
to allow access for maintenance. Where possible, valve chambers shall be located to allow
vehicular access. Proper ventilation should be provided for the washout chamber.
Classification: Revision: 03
7. Storage Tanks/Reservoirs
7.1. General
Covered reservoirs are to be provided to store TE at STPs and transmission and distribution
stations. The capacity of transmission reservoirs shall be 35 to 65 percentage of daily demand,
depending on operational and surplus storage requirements. Distribution reservoirs shall be sized
for a minimum of 1 day of summer demand.
a) Reservoirs shall be operated by telemetry with all key valves actuated, unless otherwise
stated in the Particular Specification. All M&E equipment shall be protected against leakage
or flooding and suitably rated for the application and installed location.
b) Treated effluent storage reservoirs shall be of reinforced concrete construction, unless
otherwise stated in the Particular Specification. The design of concrete reservoirs shall be in
compliance with the relevant British Standards and best international practices, and all metal
fittings must be suitably finished to resist corrosion.
c) Due to the risk of high sulphate content ground conditions, the Specification may call for
sulphate-resistant Portland cement or super sulphate cement. All external surfaces exposed
to the soil shall be protected per the Specification. Internal linings such as cement based
waterproofing coating, rubber based coating/membrane, or epoxy resin based paint shall also
be used.
d) The reservoirs shall be protected against exposure to sun. Temperature variations within the
structure should be kept to a minimum, and the roof must be protected against direct sun
exposure. The walls can be protected by burying the reservoir.
7.2. Configuration
The reservoirs shall have the following configuration:
a) Rectangular, square, or circular depending on the plan area of the allocated site
b) Two equal compartments (to facilitate periodic cleaning)
c) Internal height 3 to 6 m
d) Internal baffle walls to avoid short circuiting
e) Roof supported on columns to suit structural design
Classification: Revision: 03
8. Pump Stations
As the suction head of the pumps is directly related to the reservoir level, the feeder reservoir
level switches shall be included in the pump control system. In the case of a booster pump
station, the suction pipes may be part of the TE transmission or distribution piping system. In this
case, the upstream pressure of the network shall be included in the pump control system. The
control of pump stations is addressed in detail in the Instrumentation, Control, and Automation
(ICA) Design Manual.
a) Pressure sensors/relays or level sensors/relays are required on the suction side of the pumps
to signal the pumps to trip in the event of a set maximum negative pressure being exceeded
or the set values of maximum or minimum levels being reached. Pumping station operation
shall be by telemetry (that is, all relevant valves shall be motorised and remote controlled,
and all pumps shall be remote controlled), unless specified otherwise. All electrical and
mechanical installations shall be protected against flooding from leakage.
b) Pressure sensing/relays shall be installed on the delivery main.
Classification: Revision: 03
Provision of adequate lighting and electrical power points for portable lights and tools.
g) Pumping station types have been categorised according to their design flow:
Type 1: Design flow up to 100 L/s
Type 2: Design flow greater than 100 to 500 L/s
Type 3: Design flow greater than 500 L/s
h) The requirements for each type of TE pumping station are provided in Table 12.
Table 12. Type of TE Pumping Stations
Classification: Revision: 03
Classification: Revision: 03
ii. When selecting the pumping equipment, the following must also be considered:
a) Pumps with impeller combinations that will allow for the greatest flexibility in increasing
capacity as flows increase over the years.
b) Split casing type with double entry impellers are preferred for TE transmission End suction
centrifugal pumps and vertical multistage pumps are preferred for lower flow or distribution,
c) Construction material for the parts in contact with the TSE must be resistant to corrosion from
the chlorine content.
d) Trouble-free operation of equipment.
e) Availability of spare parts and easy maintenance of equipment by operators.
Classification: Revision: 03
Factor FOS
Friction 1.5
Sliding 2.0
Classification: Revision: 03
Overturning 2.0
b) All thrust block calculations and designs are to be submitted to the Engineer for approval. It is
the Designer’s responsibility to ensure that all thrust blocks are properly designed, taking into
account soil conditions, groundwater levels, and other factors that may influence the design
or performance of the blocks. This should include consideration of the risks of subsequent
excavations around the blocks.
c) It is recommended the Designer to consult the CIRIA Report 128 – Guide to the Design of
Thrust Blocks for Buried Pressure Pipelines for detailed guidance on thrust block design.
Typical thrust block configurations are shown in the standard detailed drawings for guidance
purposes only.
Below table refers to the Table 5 of CIRIA report 128 for reduction factors, reproduced here to
use appropriately with FOS defined above.
Classification: Revision: 03
joints are specified. All pipe restraint calculations and designs are to be submitted to the Engineer
for approval.
a) Where there are twin pipelines, each pipeline shall be designed to be mechanically restrained
independently of the other.
b) Literature such as the ‘Thrust Restraint Design for Ductile Iron Pipe’, 2660, Ductile Iron Pipe
Research Association (DIPRA), and other such publications may provide useful guidance to
the Designer.
where:
“c” is the variable which is dependent on the physical properties of the pipe, and the liquid
being conveyed
f) The Designer shall study the potential for surge affects in all pipelines and provide
calculations to justify his/her decisions. Where there is concern over surge, or at the request
of the Engineer, the Designer shall carry out a detailed surge analysis using propriety
third-party software such as Bentley Hammer, InfoSurge, Flowmaster, Hammer, Surge 2000,
or Mike Urban. Where large or complex mains and pumps stations are being designed, the
Engineer may request a surge analysis to be carried out by a third party.
g) The primary output from the surge analysis model is the predicted changes in pressure and
flow at any point in the system as a result of a transient event. The operation limits for the
system are as follows:
Classification: Revision: 03
Vapour cavities and column separation shall not occur in the system. A combination air
release / air vacuum valve shall be considered in such cases,
Minimum pressure in the system shall not exceed the allowable limit specified by the pipe
manufacturer or a maximum negative pressure of 0.5 bar below atmospheric pressure,
whichever is highest.
Maximum pressure shall not exceed the hydraulic test pressure of the pipeline or rated
maximum pressure of any of the components, such as valve fittings and similar items, in
the system, whichever is lowest.
h) The Designer shall endeavour to minimise by good hydraulic design surge, or transient,
effects caused by changes in the velocity of the water column in the pipelines. Any residual
surge affects that cannot be designed out shall be accommodated in the system by measures
that may include but are not limited to the following:
Slow or soft start/stop pumps
Slow operating valves
Balancing tank
Fly wheels
Installation of bypass with check valve from the suction side to the delivery side
Air valves and vents
Pressure relief valves
Surge vessels
Surge anticipation valves
i) Pressurised surge arresting vessels shall be connected to the pumping main to force water
into the pressure main in the event of pump shutdown to convert a rapid fluid transient event
into a controlled mass oscillation. Adequate balancing pressure shall be achieved in the
vessels either by pressurised membrane bladder or by compressors. The total volume of the
vessel is determined by the extent to which the air expands as the pressure falls plus a
minimum allowance of 20 percent or more to ensure that the vessel does not drain down
completely.
Classification: Revision: 03