Global Electrical Laboratory GEL

TC-5546

TEST REPORT Sheet 1 of 1


Name and address of customer ULR No.: TCS54623000000530F
Laxmi Associates (Hitachi Energy) Discipline & Group Electrical testing & Insulating materials
Sun Enclave, office no.13,14,15, Report Number & Date GEL/R/23112-1& 19.01.2023
Near Suncity Paradise, Customer Ref. No. and Wo/22-23/03072,
Manjalpur,Vadodara-390020 Letterdated on 17 Jan,2023
Date
Date of sample receipt 17.01.2023

Date of testing 17.01.2023


Sample description- Sample identification code GEL/23112-1
Tank oil of
Sampling:
Sr.No.:14097-003, Tag No.: ICT-3, . Oil sample drawn by customer on 16.01.2023
Location: KVTL-Adani, I. Sampling point 50KL Storage Tank
400/220kv GIS Receving Station
Top oil temperature during sampling "C: Not Available
(Near Godrej Soaps)Vikhroli, Mumbai, MH-400079
Sample Sealed & Signed By- HEIL Enginers
Sample Witness by-Mr.Sandeep Laskar(Via MS team)
Sr Clause Test Particulars Requirement as per
Obtained value Remark
No No
TestSpecification IS 1866:2017 specification
Electric Strength; kV
1) 68.0 2) 80.9 3) 81.7
5.3
Types of Electrodes: Spherical Min. 70* 4) 88.6 5) 86.0 6) 86.4 Conforms
Frequency of test voltage : 61.8Hz
Avg. 82
Stirrer:Magnetic, Oil Temp "C:26
Max. 5* Conforms
5.4
Water content; mg/kg(ppm)
Dielectric Dissipation Factor
3 5.6.1 Max. 0.0025* 0.0059 Not Conforms
(Tan Delta) at 90 *C
Specific Resistance(Resistivity) at
4 5.6 360
90 CGOhm-m
5.9 Interfacial tension; mN/m at 27°C Min. 40 45 Conforms
As per customer request(KVTPL/ICT/17,dated on 16" Jan,2023]specification requirement and remark are given.
Test Condition for Dielectric Dissipation factor & Specific Resistance:
1. Type of cell used: IS 6262-1971 (Fig 4), 4. Temperature of the room during test: 26"C,
2. Average voltage gradient in the sample while under test:250V/mm, 5. Humidity of the room during test: 41%,
3 Frequency ofapplied voltage:50 Hz
SkPovu

Tésted by Approvedby (Hardik Rana)


Note 1. This report relates only to the paticular sample received for testing in good condition at GEL
2. This report cannot be reproduced in part under any circumstances.
3. Publication of this report requires prior permission in writing from Director, GEL.
4.
5.
Only the tests asked by the customer have been carried out.
In case of any dispute, Vadodara will be the exclusive jurisdiction. ELE
6. GELis not responsible for the authenticity of photocopied or reproduced test reports. GELprovidessupportto
customersfor verification oftheauthenticity oftest reports issued by GEL.

302, Sun Enclave, Near Sun City Paradise, Manjalpur, VADODARA-390020, India
Ph. No. 7878078680 E-mail enquiry@gelab.co.in. Web-www.gelab.co.in
Global Electrical Laboratory GEL
TC-5546

Sheet 1 of 1
TEST REPORT
ULR No.: TCS54623000000531F
Name and address of customer
Electrical testing & Insulating materials
Laxmi Associates (Hitachi Energy) Discipline & Group
GEL/R/23112-2 & 19.01.2023
Sun Enclave, office no.13,14,15, Report Number & Date
Near Suncity Paradise, Customer Ref. No. and WO/22-23/03072,
Manjalpur,Vadodara-390020 Letter dated on 17" Jan,2023
Date 17.01.2023
Date of sample receipt
Date of testing 17.01.2023
identification code GEL/23112-2
Sample description Sample
Tank oil of Sampling: 16.01.2023
Sr.No.: 14097-003, Tag No.: ICT-3, Oil sample drawn by customer on
Location: KVTL-Adani, I. Sampling point: 60KL Storage Tank
"C: Not Available
400/220kv GIS Receving Station Top oil temperature during sampling
(Near Godrej Soaps)Vikhroli, Mumbai, MH-400079
Sample Sealed & Signed By- HEIL Engineers
SampleWitness by-Mr.Sandeep Laskar(Via MSteam)
Sr Clause Test Particulars Requirement as per Remark
Obtained value
No No Test Specification IS 1866:2017 specification
Electric Strength; kV 1) 64.0 2) 92.5 3) 93.7
Types of Electrodes: Spherical Min. 70* 4) 100.3 5) 100.3 6)100.3 Conforms
5.3
Frequency of test voltage: 61.8Hz
A g.
Stirrer: Magnetic, Oil Temp C:26
Max. 5* 4 Conforms
2 5.4
Water content;mg/kg (ppm)
Dielectric Dissipation Factor Max. 0.0025* 0.004 Not Conforms
3 5.6.1
(TanDelta) at 90 'C
Specific Resistance (Resistivity) at
4 5.6 720
90C;GOhm-m
Interfacial tension; mN/m at 27°C Min. 40* 44 Conforms
5 5.9
As per customer request(KVTPL/ICT/17,dated on 16" Jan, 2023)specification requirement and remark are given.

Test Condition for Dielectric Dissipation factor & Specific Resistance:


1. Type of cell used: IS 6262-1971 (Fig 4), 4. Temperature of the room during test: 27"C,
2. Average voltage gradient in the sample while under test:250V/mm, 5. Humidity of the room during test: 40%,

3 Frequency of applied voltage: 50 Hz,

Approvedby (Hardik Rana)


Note
Tested by
1. This report relates only to the particular sample received for testing in good conditior GEL
2. This report cannot be reproduced in part under any circumstances. TRICA
Publication of this report requires prior permission in writing from Director, GEL

5.
6.
Only the tests asked by the customer have been carried out.
In case of any dispute, Vadodara will be the exclusive jurisdiction.
ELE
GEL is not responsible for the authenticity of photocopied or reproduced test repprtsGÉLprovidespport to
customersfor verification oftheauthenticity of test reportsissued by GEL. ABOTBAR

302, Sun Enclave, Near Sun City Paradise, Manjalpur, VADODARA-390020, India
Ph. No. 7878078680 E-mail enquiry@gelab.co.in. Web-www.gelab.co.in

You might also like