Professional Documents
Culture Documents
Manual Controller Cascada 885HC - 62110101 - UK - 62403700
Manual Controller Cascada 885HC - 62110101 - UK - 62403700
62110101 UK
ATTENTION!!! These instructions apply only to heaters with S/N higher than 16470167.
SAFETY INSTRUCTION
ATTENTION !!!
Installer: Read the appliance Installation Manual, including this manual, before installing. Perform steps in the order
given.
User: This manual is for use only by a qualified heating installer.
ATTENTION !!!
Qualified installer: qualified installer is an individual with specific, technical training in space heating systems, domestic
hot water systems, fuel gas systems and electrical systems. This individual must have the legally required qualifications.
Failure to comply with these provisions can cause a fire or explosion causing property damage, personal injury, or death.
ATTENTION !!!
Installation and Alterations: Only a Qualified installer must carry out the installation and calibration of the heater. Never
modify the heater or its flue gas carrying components in any way. This heater must be properly vented. Failure to follow
these instructions could result in personal injury or death!
ATTENTION !!!
Prior to any maintenance, disconnect the appliance’s electrical power supply and shut off the inlet gas valve.
Failure to follow these instructions could result in severe personal injury or death!.
At the time of the installation all heaters are the same. After the installation the heater nearest the low loss header need some
hardware adjustment to become the Managing heater #1 and the other heaters need a software changement to become
dependent heaters. To do so, exactly follow next sections.
NOTICE! Figure 1-1 is only one example of a conceptual piping configuration. A lot of other configurations can be done. Ask
to your representant/Agent or to the heater manufacturer directly for any other configurations/schemes.
2 2 2 2
3
7 6 5 4
8 8 8 8 10
9
REFERENCE DESCRIPTION
1 885HC Cascade manager
2 Check valve
3 Cascade general sensor
4 Managing heater #1
5 Dependent heater #2
6 Dependent heater #3
7 Dependent heater #4 up to #8
8 Heater pump
9 Low loss header
10 Heating pump
6.- Using the 885HC cascade manager, enter the Sub Menu (see section 2.1) and set parameter “Boiler address” at 1;
7.- Leave the Sub Menu up to the main menu and wait until display shows the “Boiler address” at 1 (#1 must be displayed)
(It could take up to 2 minutes);
4
HC885 CASCADE MANAGER
1.4 - Adjust the 885HC command for boilers or for water heaters
885HC command is factory supplied with all parameters ready for boiler application but not for water heaters applications.
When your system is in place, you have to review all parameters of the Sub Menu to be in line with the list of section 2.3.
Select the column boiler settings if you are opearating on a boiler application; select the column water heater settings if you
are operating on a water heater application.
1.5 - Cascade general settings for parameters 3001, 3050, 2003 and S4 switches
B 1° DEPENDENT Heater
C 2° DEPENDENT Heater up to 7
1 = Boiler address
2 = Heating setpoint
3 = Cascade temperature
4 = Status of the cascade (when it is in stand-
by, the value disappears)
5 = OK button to confirm a changement to a
parameter
6 = Up button to scroll parameters or to
increase a value
7 = Menu button to back on normal menu
8 = Down button to scroll parameters or to
decrease a value
9 = Home button to enter the sub menù
10 = Button to change the screen
11 = outdoor temperature
12 = RESET button. Reset blocks (Loc) present
only into the master heater.
By pressing button “10” of figure 2-1 the bottom side of the display will change to show the status of the cascade. Display
will show the numbers of heaters into the cascade, numbers “1”, “2”, and “3” (they can be up to “8”) and if they are in request
for heating a flame icon appear below the number, or if they are in stand by a underscore icon appear below numers while
if there are an anomaly in the appliance a wrench icon appear below numbers .
When the appliance is working, under the flame icon appear the value of the operating power of the single appliance.
A = Heaters on cascade
B = State of the heater:
Flame: heat demand
Wrench: heater in error
A
Dash: heater in stand-by
B
C = Operating power
C
8
HC885 CASCADE MANAGER
When the parameter is selected, press the “OK” button (the dot of parameter selectioned will move on the value).
The parameter value will start to blinking. Now you can change the parameter value by using the “UP” and “DOWN” button.
When the desired value is reached you can save it by pressing the “OK” button.
Set all the parameter following figure 2-3 (°C).
To leave the Sub Menu, press the “Menu” button (detail “7” of figure 2-1).
CAUTION! After any change, wait 40 seconds before turn the power off.
Parameters displayed in this Sub Menu are showed in figure 2-3.
2.2 - Troubleshooting
DESCRIPTION SOLUTION
Display of the 885HC command does not light on Check switch S4 on the 885 IF board is in ON position
(see Figure 2-2)
“Boiler address” parameter is correctly set in all heaters Check that communication wires are correctly in place
but the same heaters reference is not shown on display (see figure 1-2 terminals 30 and 31 on manager heaters
(see figure below). and 28 and 29 on corresponding dependents.
One of the SLAVE diveces works continuously also if I Communication of that heater is lost. Check on the right
bring to OFF the heat demand. screen if the quantity of heaters reflect the real state. (see
figure below)
Changing the logic address on the heater, as per section After changing the logic address, display can wait up to
1.4, I’m unable to see the update on the screen 180 seconds to show the address on the screen (see
figure below).
9
HC885 CASCADE MANAGER
S4 switch
020009.01.019
OFF
ON position
position
(Must be in “ON” position)
Figure 2-2 885IF board and S4 Switch
Parameter M.U. Range Factory Boiler settings Water Heater settings Customized value
settings
Boiler address / 0..16 0 0 - Stand Alone heater 0 - Stand Alone heater
1 - for Managing 1 - for Managing
2 - for first dependent 2 - for first dependent
3 - for second dependent 3 - for second dependent
4 - ...etc 4 - ...etc
Temperature unit / °C..°F / / /
Heating setpoint °C 20..90 80 / /
"Heating setpoint" = Selection of the cascade supply temperature. The same selection can be done alternatively on the heater keys;
"Start delay time" = Delay to switch on a heater on the cascade. This timing start when the General cascade sensor temperature is
lower than “Cascade Setpoint” - “Start boiler diff”;
"Stop delay time" = Delay to switch off a heater on the cascade. This timing start when the General cascade sensor temperature is
higher than “Cascade Setpoint” + “Stop boiler diff”;
"Start boiler diff" = Switch on differential of the heaters into the cascade. It works as described on parameter “Start delay time”;
"Stop boiler diff" = Switch off differential of the heaters into the cascade. It works as described on parameter “Stop delay time”;
"Stop All boiler diff" = Switch off differential of the last heater (or lasts heaters, if the case), into the cascade. When cascade general
sensor temeprature drops over “Cascade Setpoint” + “Stop All boiler diff” the last heater of the cascade (or lasts heaters, if the case),
will switch off;
"Max offset up" = Increasing temperature that can be added to heach heater on the cascade to satisfy the cascade generale sensor;
"Max offset down" = Decreasing temperature that can be added to heach heater on the cascade to satisfy the cascade generale sen-
sor;
"P Value" = Proportional parameter to calculate the setpoint of each heater into the cascade. Suggested to maintain values from facto-
ry;
"I Value" = Integral parameter to calculate the setpoint of each heater into the cascade. Suggested to maintain values from factory;
"D Value" = Derivative parameter to calculate the setpoint of each heater into the cascade. Suggested to maintain values from factory;
"Slew rate" = Multiplier parameter to calculate the setpoint of each heater into the cascade. Suggested to maintain values from factory;
"System correction" = Correction temperature for the cascade general sensor in case it is not correctly positioned;
"Mod delay factor" = Delay to the effects of “Max offset up” and “Max offset down” parameters on the setpoint of each heater into the
cascade.
11
HC885 CASCADE MANAGER
INSTALLATION AND USE INSTRUCTIONS
62110101 UK