TYPE CM2 VACUUM

ON-­LOAD TAP CHANGER


FOR OIL-­IMMERSED TRANSFORMER
How  to  reduce  maintenance?
How  to  improve  reliability  of  tap  
changers  in  operation?
How  to  apply  vacuum  technique  
on  traditional  tap  changers?    
Huaming's  solution......  
TYPE CM2 OIL-­IMMERSED
ON LOAD TAP CHANGER
CM2  type  vacuum  on-­load  tap  changer  contains  a  diverter  switch  
and  a  tap   selector.   It   adopts   vacuum   switching   technology   in   the  
transition  circuits  of  the  diverter  switch.  And  the  tap  selector  is  of  a  
reliable   structure   continuously   improved   by   Huaming   and   proven  
in   long   term   operation.  This   tap   changer   is   applicable   to   power  
transformers   or   industrial   transformers   with   highest   equipment  
voltage  of  40.5kV~252kV,  max.  rated  through  current  three  phase  
600A,   single   phase   1500A,   and   frequency   of   50Hz/60Hz.  Three  
phases  CM2  will  be  put  at  the  neutral  point  of  star  connection,  and  
single  phase  is  applicable  in  any  connection.

CM2  type  vacuum  on-­load  tap  changer  has  three  voltage  regulating  
PRGHVOLQHDUUHYHUVLQJDQGFRDUVH¿QH

CM2  type  vacuum  on-­load  tap  changer  not  only  can  be  applied  in  
new  transformers,  but  also  interchangeable  with  the  conventional  
type   CM   and   CMD   of   Huaming,   type   M   and   type   ZY1   of   other  
suppliers   at   site.  This   unique   interchange   technology   marks   tap  
changers'  new  vacuum  era.

CM2   type   vacuum   on-­load   tap   changer   will   strongly   stimulate  


applications   of   vacuum   on-­load   tap   changers   all   over   the   world,  
thus   improve   the   reliable   performance   of   power   network   and  
greatly  reduce  the  maintenance  cost.
Comparison  between  CM2  type  vacuum  on-­load  tap  changer  and  traditional  type  on-­load  tap  changer  (CM  type,  M  type)

Performance Vacuum tap change Traditional tap changer

Arc  extinguishing  method

Vacuum  interrupter Arcing  contact


Arcing  extinguished  in   Arcing  extinguished  in  oil
vacuum  interrupter
Mechanical  life 1,500,000  operations 800,000  operations
Must  maintain  about  every  50,000  to  
RSHUDWLRQVLIZLWKRXWRLO¿OWHU
operations.  May  require  maintenance  at  
any  time  depending  on  the  load  and  oil  
Maintenance  period 300,000  operations  maintenance  free conditions.  Contact  burning  loss  would  
increase  dramatically  with  long  term  
operation.  Maintenance  interval  would  
be  shortened  by  10,000  operations  
after  that.
Function  of  Oil Insulating Insulating;;  arc  extinguishing;;  cooling
Oil  in  diverter  switch  won't  be   Need  to  change  oil  whenever  lifting  out  
carbonized  because  arc  extinguishes  in   diverter  switch  for  inspection.  Should  
Oil  replacement
vacuum  interrupter.  Hence,  it  is  seldom   strictly  monitor  the  oil  condition  in  
to  change  the  oil. operation.
1HHGWRLQVWDOO7KH¿OWHUQHHGVWREH
2QOLQHRLO¿OWHUSODQW Not  necessary
changed  after  5  years  operation.
Flange  installation  dimension     Same

Overall  dimension  

Same  height

Motor  drive  unit Same


5HSODFHLQ¿HOG

Remove  top  
Drain  oil
cover

CM

Install  lifting  device


Clean  oil  compartment

Remove  lifting  
device

Mount  the  top  


cover

Fill  oil

Lift   out   the   original   CM   Install  the  CM2  diverter  switch  


diverter  switch

The  above  process  can  be  


¿QLVKHGZLWKLQRQHKRXU
Note: Due to production date difference, the tap changers structure
might have minor difference. So, In order to guarantee a better
UHSODFHLQÀHOGSOHDVHFRQWDFWXVEHIRUH\RXWU\WRUHSODFHZHZLOO
SURYLGHWKHEHVWVROXWLRQIRU\RX
TYPE CM2 OIL-­IMMERSED
ON LOAD TAP CHANGER
CM2  on-­load  tap  changer  technical  data

CM2  III500 CM2  III600


Mode CM2  I800 CM2  I1200 CM2  I1500
CM2  I500 CM2  I600
Max.  rated  through-­current  (A) 500 600 800 1200 1500
Rated  frequency(Hz)   50  or  60
Three  phases  for  Y  connection;;
Connection  mode  
Single  phase  for  any    connections
Max.  step  voltage  (V) 3300
Rated  step  capacity  (kVA) 1400 1500 2000 3100 3500
Short-­circuit   Thermal  (3s) 8 8 16 24 24
current  
test  (kA) Dynamic  (peak) 20 20 40 60 60

18,  without  change-­over  selector


Max.  Operating  Positions
35,  with  change-­over  selector
Highest  equipment  voltage 72.5                                126                                    170                                  252
Rated  separate  source  
Insulation  to 140                                  230                                    35                                    460
AC  withstand  voltage  (50Hz,1min)
 ground  (kV)
Rated  lightning  impulse  withstand  
350                                  550                                    750                              1050
voltage  (1.2/50µs)
Tap  selector Size  B,  C,  D,DE  depending  on  different  insulation  level
Mechanical  life 1,500,000  operations
Operating  pressure 3ġ104Pa
Diverter Sealing No  leakage  under  8ġ104Pa  for  24  hours
switch  oil
 compartment Over  pressure  protection Rupture  disk  opens  at  300±20%kPa
Protection  relay 6HWWLQJRLOÀRZVSHHGDWPV“
Motor  drive SHM  or  CMA7

6KDQJKDL+XDPLQJ3RZHU(TXLSPHQW&R/WG
Address:   No  977  Tong  Pu  Road,  Shanghai  200333,  P.R.China
Tel:   +86  21  5270  3965  (direct)    
                  +86  21  5270  8966    Ext.  8688  /  8123  /  8698  /  8158  /  8110  /  8658
Fax:     +86  21  5270  2715
Web:   www.huaming.com                              E-­mail:                  export@huaming.com

Printing:  November  2010

You might also like