Real and Reactive Power Control of A Three-Phase Single-Stage PV System and PV Voltage Stability
Real and Reactive Power Control of A Three-Phase Single-Stage PV System and PV Voltage Stability
1
Abstract — Grid-connected photovoltaic (PV) systems with
of the PV array to extract maximum available solar energy.
power electronic interfaces can provide both real and reactive However, PV systems may also have to follow dispatch
power to meet power system needs with appropriate control commands to output a certain amount of real power or to
algorithms. This paper presents the control algorithm design for participate in frequency regulation. In order to work in quite
a three-phase single-stage grid-connected PV inverter to achieve dynamic system conditions, PV systems need to seamlessly
either maximum power point tracking (MPPT) or a certain switch between fixed real power control mode and MPPT
amount of real power injection, as well as the voltage/var control. mode.
The switching between MPPT control mode and a certain Currently, most PV systems operate at unity power factor
amount of real power control mode is automatic and seamless. due to the IEEE Std. 1547 Guide [12]. With the fast growth of
Without the DC-to-DC booster stage, PV DC voltage stability is
an important issue in the control design especially when the PV
PV systems and the fact that some utilities are experiencing
inverter is operating at maximum power point (MPP) with high penetration levels of PV systems on distribution circuits,
voltage/var control. The PV DC voltage collapse phenomenon guidelines for voltage and reactive power (voltage/var)
and its reason are discussed. The method based on dynamic regulation from distributed energy resources (DER) are
correction of the PV inverter output is proposed to ensure PV DC underway by the IEEE 1547.8 working group of SCC 21 [13]
voltage stability. Simulation results of the single-stage PV system to identify the requirements for local voltage/var control by
during system disturbances and fast solar irradiation changes distributed generation and renewable energy. The reactive
confirm that the proposed control algorithm for single-stage PV power support or voltage regulation potential of PV inverters
inverters can provide appropriate real and reactive power could greatly benefit power system stability [2]-[5]. By
services and ensure PV DC voltage stability during dynamic
system operation and atmospheric conditions.
utilizing the remaining capacity or slightly increasing the
Index Terms—photovoltaic (PV) systems, maximum power point capacity of the inverter, PV systems can provide significant
tracking (MPPT), DC voltage stability, distributed energy resources, voltage/var support. Furthermore, the provision of reactive
single-stage PV inverter, smart inverter control, real power control, power does not require the availability of solar energy and can
voltage control, reactive power, microgrid, smart grid. be at the PV inverter’s full capacity when PV arrays are not
generating any real power at night. For instance, if the a PV
I. INTRODUCTION system is rated at 100 kVA with a 0.9 power factor, the real
978-1-4673-2729-9/12/$31.00
Authorized licensed use limited©2012
to: Konya IEEE
Teknik Universitesi. Downloaded on April 05,2024 at 07:25:30 UTC from IEEE Xplore. Restrictions apply.
2
Many control algorithms have been developed for the voltage characteristics at different solar irradiation levels and
MPPT control of PV systems. The most popular method in use temperatures are shown in Figs. 3 and 4, respectively.
is the perturb & observe (P&O) or hill climbing [8] method. A Three characteristic operation points for the PV system:
small perturbation is intentionally created by the MPPT open circuit, MPP and short circuit are shown in Fig. 1. Isc is
control. If the output power increases after this perturbation, the short circuit current; Voc is the open circuit voltage; Vmpp
the next perturbation will be in the same direction as this one. and Impp are voltage and current at the MPP, respectively. The
Otherwise, the perturbation will be in the opposite direction. corresponding mathematical equation is given in Eq. (1)
This method requires little calculation and is easy to [10][11].
implement. However, perturbations may be caused by other
events other than the P&O control, such as solar irradiation ⎡ ⎛ q (V + Rs I ) ⎞ ⎤ V + Rs I (1)
I = I pv − I 0 ⎢exp⎜⎜ ⎟⎟ − 1⎥ −
changes and voltage regulation changes on the system. The ⎣ ⎝ N s kTa ⎠ ⎦ Rsh
P&O control is unable to distinguish the difference between
all of these perturbations and therefore may make a wrong where Ipv and I0 are the PV and the diode saturation currents,
adjustment as a result. The changing rate in DC power to respectively. Ns is the number of cells connected in series for
voltage (dP/dV) or current (dP/dI) is an indicator of the PV greater output voltage, k is the Boltzmann constant
array operating point, which equals to zero at the maximum (1.3806503×10-23 J/K), T (Kelvin) is the temperature of the p-n
power point (MPP). With fast-acting microcontrollers like junction of the diode, and q (1.60217646×10-19C) is the
digital signal processors (DSP), dP/dV (or dP/dI) feedback electron charge. Rs and Rsh are the equivalent series and shunt
control for MPPT can be implemented [7]. resistances of the array, respectively, and a is the diode
MPP is a critical steady point for DC voltage stability, constant factor, which is usually chosen to be in the range of
considering the PV’s current versus voltage characteristic. In 1≤ a ≤1.5 [11].
the current source region, a small current increase will very
likely cause a DC voltage collapse [9]. As a result, the PV
system running near the MPP operating point is more sensitive
to disturbances. Thus, maintaining the DC voltage stability is
very important for a single-stage inverter implemented with
voltage/var control function.
Basically, the control algorithm of grid-interfaced PV
system needs to achieve these functions: (1) generate a grid-
compatible sinusoidal waveform; (2) perform maximum Fig. 1. Current-Voltage (I-V) characteristic curve of a PV array. [10]
power point tracking (MPPT) or follow a real power output
reference; (3) if permitted such as per a finalized IEEE 1547.8
std., provide voltage regulation or follow a reactive power
+
75oC
introduced in this section. 100
A PV array is composed of PV cells connected in series
50
and in parallel to achieve the desired DC power and DC
voltage input for an inverter system. Fig. 1 shows the current- 0
0 10 20 30 40
voltage (I-V) curve of a PV array. The single-diode equivalent V (V)
circuit of a PV array is shown in Fig. 2. The PV DC power vs. Fig. 4. PV DC power output vs. voltage at different temperatures.
Authorized licensed use limited to: Konya Teknik Universitesi. Downloaded on April 05,2024 at 07:25:30 UTC from IEEE Xplore. Restrictions apply.
3
Authorized licensed use limited to: Konya Teknik Universitesi. Downloaded on April 05,2024 at 07:25:30 UTC from IEEE Xplore. Restrictions apply.
4
achieve the fixed real power and reactive power control of the
PV inverter, which is expressed in Eqs. (11) and (12).
The PI1 controller is used to control the real power while
the PI2 controller is used to control the reactive power. The
Δp pv
instantaneous real power and reactive power are calculated
Δv pv
using Eqs. (5)-(8) and compared with a real power reference,
Pref, and reactive power reference, Qref, respectively. The Fig. 8. MPPT control
errors in the power output are fed into their respective PI
In the voltage source region, dppv/dvpv < 0 and according
controllers to minimize the error between the actual and
reference values. The signal generated by the real power PI to Eq. (14), ∗ increases, causing PV inverter to increase real
controller regulates the phase angle of the inverter output power output and the capacitor of the DC link will discharge.
voltage (vc) while the signal from the reactive power PI As a result, the DC voltage will decrease and the PV array
controller adjusts the amplitude of vc. operating point moves to the MPP. If the PV array moves
beyond the MPP and into the current source region, dppv/dvpv >
∗
= − + − . (11) 0 and ∗ decreases, causing PV inverter to decrease real power
output. When the PV inverter real power output is less than
∗
= 1+ − + − the PV array output power, the capacitor will be charged. As a
(12) result, the DC voltage will increase and the PV array operating
point will move toward the MPP. However, in the current
The local PCC voltage control is implemented by replacing source region, the DC voltage keeps decreasing until the PV
the reactive power reference signal, Qref , of the control logic inverter real power output decrease to less than the PV array
in Fig. 6 with the PCC voltage reference signal, Vref. The output power. In some cases, the PV DC voltage may decrease
control logic for the fixed real power and voltage control is to an unacceptable low level. Additional correction measures
shown Fig. 7. Eq. (13) gives the corresponding expression. are introduced to address this issue, which is discussed in
∗
= 1+ _ − + _ − Section IV.
Authorized licensed use limited to: Konya Teknik Universitesi. Downloaded on April 05,2024 at 07:25:30 UTC from IEEE Xplore. Restrictions apply.
5
100
MPP with the output power pm and voltage vm, respectively, as 500
pv
450 0
pv
p1
If some correction measures are taken right after the
p2 disturbance to reduce PV inverter real power output less than
current voltage pm, the capacitor will be charged and as a result, the DC
source source voltage will increases to v2 in Fig. 10 and PV array operating
dp/dv > 0 dp/dv < 0 point moves to voltage source region. Then, MPPT control
logic will increase PV inverter output real power and
eventually the PV array operating point will return to MPP.
v1 vm v2
The value of dppv/dvpv indicates the status of the PV array
V (V)
DC voltage stability. A large positive value of dppv/dvpv results
Fig. 10. PV array operation regions.
in a DC voltage collapse. Therefore, the objective is to keep
the dppv/dvpv from increasing to a large positive value or to be
change. Usually, the changing rate of sun irradiation and able to quickly push it back to a small positive or negative
ambient temperature is in the range of a few seconds, while value in order to prevent a DC voltage collapse. The simple PI
the PI controller speed is in milliseconds or even feedback MPPT control presented in the previous section can
Authorized licensed use limited to: Konya Teknik Universitesi. Downloaded on April 05,2024 at 07:25:30 UTC from IEEE Xplore. Restrictions apply.
6
LF Load
+
disturbances, the speed of the PI controller with fixed gains
0.275/0.48
may not be fast enough to avoid DC voltage collapse. Hence,
2
DD_1
p5
m4
1
additional control logic providing fast correction of dppv/dvpv vpv
v
+A
>i
v (t) v_pos
?ip>ip
Gain8
A+
m5
DEV1 pos m3
+
dpdv +
dpdv ac A
+
DEV2
cI2 C1
vpv >v >i
ipv 0/100 neg
Eq. (16). PV
ipv
p6 Inverter
v (t) v_neg
∗ ∗
= − ∑ (16)
Where αcorrected*is the overall phase angle shift; α0* is the phase Fig. 13 Simulation model in EMTP-RV.
angle shift generated by the real power control; βk is the phase Table II. Gains for PI controllers
angle correction shift increment at the kth time step; the total KP KI
phase angle shift correction is the accumulation of all the MPPT control 1×10-9 1×10-8
increments over the control time. βk is a linear function of Fixed amount of P control 5×10-8 5×10-7
Fixed amount of Q control 1×10-6 1×10-5
dppv/dvpv, as shown in Fig. 12. The threshold, μ, at which this
Voltage control 1×10-2 1×10-1
function engages is also shown. When dppv/dvpv is less than μ,
there is no correction increment at this step; otherwise, a
A. Fixed Real Power and Reactive Power/Voltage Control
correction increment proportional to dppv/dvpv is applied.
35 35
βk
30
26
25
20
Q (k V A r)
P (k W )
15
15
10
5 PV inverter P injection PV inverter Q injection
μ dppv/dvpv 0 P reference 5
Q reference
Fig. 12 Correction increment vs. dppv/dvpv. 5 10 15 20 5 10 15 20
time(s) time(s)
The dppv/dvpv correction logic is a supplement to the fixed- (a). PV inverter real power (b). PV inverter reactive power
gain PI controller based MPPT control, and it accelerates the
Fig. 14 Fixed real and reactive power control.
control speed of reducing PV inverter real power output to a
safe range to prevent a DC voltage collapse. Figs. 14(a) and (b) show the simulation results for the fixed
real power and reactive power output control of the PV array.
V. SIMULATION RESULTS As shown in Fig. 14(a), at 10 s, a 16 kW step change is
The simulations of the real and reactive power control of applied to the real power reference. The PV array real power
the PV system under atmospheric condition changes are output tracks this change and increases to 26 kW. The PV
demonstrated in this section. The configuration of the reactive power output also tracks its reference change, as
simulation system is shown in Fig. 5. The PCC line-to-line shown in Fig. 14(b), which has been increase by 10 kVAr at
voltage is 480 V and the load is 87 kVA (78 kW, 39 kVAr). 15 s.
The PV system is composed of solar arrays with 8 parallel
connections and 18 serial connections. Table I shows the 30 275
V (V )
20
overview of the simulation model is shown in Fig.13. The 272
controllers’ parameters used in the simulations are listed in PV inverter P injection
15 PCC voltage
Table II. P reference 271
Voltage reference
10 270
Table I Parameters of the solar module at 25oC, A.M 1.5, 1000 W/m 5 10 15 20 5 10 15 20
time(s) time(s)
Imp (current at MPP) 7.61 A
Vmp (voltage at MPP) 26.3 V (a). PV inverter real power (b). PCC voltage RMS
Pmax,e (maximum electrical power) 200.143 W
Voc (open circuit voltage) 32.9 V Fig. 15 Fixed real power and PCC voltage control.
Isc(short circuit current) 8.21 A
Figs. 15(a) and (b) show the fixed real power control of the
PV system and the PCC voltage control. The references for
real power and PCC voltage change simultaneously at time 5s.
The real power reference is increased by 12 kW while the
Authorized licensed use limited to: Konya Teknik Universitesi. Downloaded on April 05,2024 at 07:25:30 UTC from IEEE Xplore. Restrictions apply.
7
273
B. MPPT and Reactive Power/Voltage Control
V(V)
272
1200 35 PCC voltage
271 Voltage reference
1100
30
1000 270
5 10 15 20 25 30 35 40 45 50 55
G(W/m2)
P (k W )
time(s)
900 25
(c). PCC voltage RMS
800
20
700 Fig. 17. PV array MPPT and PCC voltage control under solar irradiance
change.
600 15
10 15 20 25 30 35 40 45 50 55 60 10 15 20 25 30 35 40 45 50 55 60
time(s) time(s) Figs. 17(a), (b) and (c) show the simulation results of the
(a). Solar irradiance (b). PV inverter real power
700
PV array MPPT control and the PCC voltage control. In the
650 previous case, the irradiance varies the same as well as the real
P V array DC v oltage(V )
500 20
power under atmospheric condition changes, and the PCC
450
PV inverter Q injection voltage can follow the reference change. A sudden PCC
400 15
350
Q reference
voltage reference change is applied at 8 s, as shown in Fig.
300 1
17(c), which imposes a large disturbance on the MPPT
10 20 30
time(s)
40 50 60 10 20 30
time(s)
40 50
control. It can be seen from the real power output spike in
(c). PV output DC voltage (d). PV inverter reactive power Fig. 17(b). The DC voltage experiences a small dip following
the sudden PCC voltage reference change; however, it is
Fig. 16. PV array MPPT and reactive power control under solar quickly brought back to a high level by the controller. These
irradiance change. results show that the PV DC voltage stability is ensured by the
controls during large disturbances.
Figs. 16(a), (b), (c) and (d) show the simulation results of
the MPPT and fixed reactive power control of the PV system. C. Switching between Fixed Real Power Control and MPPT
Solar irradiance is constant at 1000 W/m2 prior to 20 s. As 35
shown in Fig. 16(d), at 10 s, a 10 kVAr step change is applied
to the reactive power reference, and the reactive power control 30
real power and reactive power output of the PV system thus Fig. 18. Switching between fixed real power control and MPPT control.
remain constant. From 40 s to 45 s, solar irradiance increases
back to 1000 W/m2, and the PV array real power output also Fig. 18 shows the simulation results of the PV system
restores to its original 28.8 kW output level. The PV array DC control when it switches between fixed real power control and
voltage, as shown in Fig. 16(c), experiences small variations MPPT control. The PV system is initially operating in fixed
but is still stable during the two transitions. The reactive real power control mode with the real power reference set to
power experiences variations during both transitions because it 26 kW. From 20 s to 25 s, the solar irradiance reduces from
is not fully decoupled from the impacts of real power control. 1000 W/m2 to 800 W/m2, the same as that shown in Fig. 16(a).
700 35 The real power output is maintained at 26 kW when the
650 available maximum power is larger than this amount prior to
21.5 s. After the solar irradiance decreases and the maximum
PV array DC voltage(V)
600 30
550
power declines below 26 kW, the control switches to MPPT
P(kW)
500 25
control to maintain output until the solar irradiance level
450
returns to 1000 W/m2. From 40 s to 45 s, the solar irradiance
400 20
350
increases from 800 W/m2 to 1000 W/m2, so the control
300 15
switches back to fixed real power control and the real power
5 10 15 20 25 30 35 40 45 50 5 10 15 20 25 30 35 40 45 50 55
time(s) time(s) output restores to 26 kW at 43.5 s.
(a). PV output DC voltage (b). PV inverter real power
VI. CONCLUSIONS
This paper presents control algorithms for real power,
reactive power and local voltage control of a grid-connected
Authorized licensed use limited to: Konya Teknik Universitesi. Downloaded on April 05,2024 at 07:25:30 UTC from IEEE Xplore. Restrictions apply.
8
three-phase single-stage photovoltaic (PV) system. The real Procedures that Provide Supplemental Support for Implementation
Strategies for Expanded Use of IEEE Standard 1547.
power can be controlled either in the fixed real power mode or
MPPT control mode, and the controller automatically switches
between the two modes according to the system operator
control commands or grid conditions. The potential DC
voltage collapse problem associated with PV systems
operating at MPP and being subject to large disturbances is
addressed, and an effective prevention method is proposed and
demonstrated. Simulation results of the fixed real power
control, MPPT control, and switching between the two
different operating modes confirm that the proposed control
algorithm for the single-stage PV inverter has great scalability,
adaptability, and can accommodate a wide range of
atmospheric conditions and dynamic PV system operations as
well. The developed control algorithms demonstrate that
inverter-based PV systems can provide fast, local reactive
power or voltage regulation support of distribution systems
with a high PV penetration. Also the ability to switch between
different operation modes automatically and seamlessly
provides a means for the distribution system operator to
deliver control schedules or commands to coordinate multiple
PV systems.
VII. REFERENCES
[1] “U.S solar market trends 2010,” Available online:
http://www.irecusa.org/wp-content/uploads/2011/06/IREC-Solar-
Market-Trends-Report-June-2011-web.pdf, Retrieved: Month, Year.
[2] H. Li, F. Li, Y. Xu, D. T. Rizy and J. D. Kueck, “Adaptive voltage
control with distributed energy resources: algorithm, theoretical analysis,
simulation, and field test verification”, IEEE Transactions on Power
Systems, vol.25, no.3, pp.1638-1647, Aug. 2010.
[3] Yan Xu, L. M. Tolbert, F. Z. Peng, J. N. Chiasson, and J. Chen,
“Compensation-based non-active power definition,” IEEE Power
Electronics Letters, vol. 1, no. 2, June 2003, pp. 45-50, June 2003
[4] Sarina Adhikari, Yan Xu, Fangxing Li, Huijuan Li, John D. Kueck,
Isabelle B. Snyder, Thomas J. Barker and Ronald Hite, “Utility-Side
Voltage and PQ Control with Inverter-based Photovoltaic Systems,”
Proc., the 18th IFAC World Congress, Milano, Italy, 2011.
[5] D.T. Rizy, Huijuan Li, Fangxing Li, Yan Xu; S. Adhikari and P.
Irminger, “Impacts of varying penetration of distributed resources with
& without volt/var control: case study of varying load types,” Proc.,
IEEE Power and Energy Society General Meeting, Detroit, MI, 2011
[6] H. Ribeiro, F. Silva, S. Pinto and B. Borges, “Single-stage inverter for
PV applications with one cycle sampling technique in MPPT algorithm,”
in Proc., 35th Annual IEEE Cof. on Industrial Electronics (IECON),
Porto, Portugal, 2009.
[7] Riad Kadri, Jean-Paul Gaubert, “An improved maximum power point
tracking for photovoltaic grid-connected inverter based on voltage
oriented control,” IEEE Transactions on Industrial Electronics, vol.58,
no.1, pp.66-75, Jan. 2011.
[8] Trisham Esram and Patrick L. Chapman, “Comparison of photovoltaic
array maximum power point tracking techniques,” IEEE Transactions
on Energy Conversion, vol.22, no,2, pp.439-449, June 2007.
[9] Libo Wu, Zhengming Zhao and Jianzheng Liu, “A single-stage three-
phase grid-connected photovoltaic system with modified MPPT method
and reactive power compensation,” IEEE Transactions on Energy
Conversion, vol. 22, no. 4, pp.881-886, December 2007.
[10] Felix A Farret and M. Godoy Simoes, “Integration of alternative sources
of energy,” A Wiley- Interscience Publication.
[11] Marcelo Gradella Villalva, Jonas Rafael Gazoli and Ernesto Ruppert
Filho, “Comprehensive approach to modeling and simulation of
photovoltaic arrays,” IEEE Transactions on Power Electronics, vol.24,
no.5, pp.1198-1208, May. 2009.
[12] http://grouper.ieee.org/groups/scc21/1547/1547_index.html, IEEE 1547
Standard for Interconnecting Distributed Resources with Electric Power
Systems.
[13] http://grouper.ieee.org/groups/scc21/1547.8/1547.8_index.html, IEEE
P1547.8 Recommended Practice for Establishing Methods and