DESIGN APPROACHES 13–143

Density (mm/min)
2.0 4.1 6.1 8.1 10.2 12.2 14.3 16.3
5000 465
Area of sprinkler operation (ft 2 )

Area of sprinkler operation (m2)


Ex
4000 372

Ex
t
ra

t
ra
ha

ha
za

za
rd

rd
G
Ord
Ord

ro

G
3000 279

ro
up
in

up
in

1
ary
ary
Ligh

2
2500 232
2
1
t

2000 186

1500 139
0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40
Density (gpm/ft 2 )

FIGURE 11.2.3.1.1 Density/Area Curves.

Table 11.2.3.1.2 Hose Stream Allowance and Water Supply (9) Exterior columns under 10 ft2 (0.9 m2) in area formed
Duration Requirements for Hydraulically Calculated Systems by studs or wood joists, supporting exterior canopies that
are fully protected with a sprinkler system.
Total Combined (10)*Light or ordinary hazard occupancies where noncom-
Inside and Outside bustible or limited-combustible ceilings are attached to
Inside Hose Hose the bottom of composite wood joists either directly or on
Duration
Occupancy gpm L/min gpm L/min (minutes)
to metal channels not exceeding 1 in. (25 mm) in depth,
provided the adjacent joist channels are firestopped into
Light hazard 0, 50, or 0, 190, or 100 380 30 volumes not exceeding 160 ft3 (4.5 m3 ) using materials
100 380 equivalent to 1⁄2 in. (13 mm) gypsum board, and at least
Ordinary 0, 50, or 0, 190, or 250 950 60–90 31⁄2 in. (90 mm) of batt insulation is installed at the bot-
hazard 100 380 tom of the joist channels when the ceiling is attached
utilizing metal channels.
Extra hazard 0, 50, or 0, 190, or 500 1900 90–120
100 380 11.2.3.2 Density/Area Method.
11.2.3.2.1 Water Supply.

to the bottom of solid wood joists or solid limited- 11.2.3.2.1.1 The water supply requirement for sprinklers only
combustible construction or noncombustible construction shall be calculated from the density/area curves of Figure
so as to create enclosed joist spaces 160 ft3 (4.5 m3) or less 11.2.3.1.1 or from Chapter 22 where density/area criteria are
in volume, including space below insulation that is laid di- specified for special occupancy hazards.
rectly on top or within the ceiling joists in an otherwise 11.2.3.2.1.2 When using Figure 11.2.3.1.1, the calculations
sprinklered concealed space. shall satisfy any single point on the appropriate density/area
(5) Concealed spaces where rigid materials are used and the curve.
exposed surfaces have a flame spread index of 25 or less
and the materials have been demonstrated to not propa- 11.2.3.2.1.3 When using Figure 11.2.3.1.1, it shall not be nec-
gate fire more than 10.5 ft (3.2 m) when tested in accor- essary to meet all points on the selected curves.
dance with ASTM E84, Standard Test Method for Surface 11.2.3.2.2 Sprinklers.
Burning Characteristics of Building Materials, or ANSI/
11.2.3.2.2.1 The densities and areas provided in Figure
UL 723, Standard for Test for Surface Burning Characteristics
11.2.3.1.1 shall be for use only with spray sprinklers.
of Building Materials, extended for an additional 20 min-
utes in the form in which they are installed in the space. 11.2.3.2.2.2 Quick-response sprinklers shall not be permitted
(6) Concealed spaces in which the exposed materials are for use in extra hazard occupancies or other occupancies
constructed entirely of fire-retardant-treated wood as de- where there are substantial amounts of flammable liquids or
fined by NFPA 703. combustible dusts.
(7) Concealed spaces over isolated small rooms not exceed-
11.2.3.2.2.3 For extended coverage sprinklers, the minimum
ing 55 ft2 (5.1 m2) in area.
design area shall be that corresponding to the hazard in Fig-
(8) Vertical pipe chases under 10 ft2 (0.9 m2), provided
ure 11.2.3.1.1 or the area protected by five sprinklers, which-
that in multifloor buildings the chases are firestopped at
ever is greater.
each floor using materials equivalent to the floor con-
struction, and where such pipe chases contain no 11.2.3.2.2.4 Extended coverage sprinklers shall be listed with
sources of ignition, piping shall be noncombustible, and and designed for the minimum flow corresponding to the
pipe penetrations at each floor shall be properly sealed. density for the hazard as specified in Figure 11.2.3.1.1.