4.

5d) FOURTH
FLOOR
A. Conduction Heat Gain
Hc = U x A x (CLTDcorr)
U
A(sq.ft.) CLTD (⁰F) CLTDcorr (⁰F) Hc
(Btu/hr/sq.ft/⁰F)
EXTERNAL
WALLS
N no wall no wall no wall no wall no wall
S 0.4902 605.24 29 19 5637.08
E no wall no wall no wall no wall no wall
W 0.4902 851.6 20 16 6679.27
DOORS
N no door no door no door no door no door
S 0.346 20.25 20 14 98.09
E no door no door no door no door no door
W no door no door no door no door no door
WINDOWS
N no window no window no window no window no window
S no window no window no window no window no window
E no window no window no window no window no window
W 1.13 781.63 20 14 12365.39
TOTAL 24779.83
ROOF 0.191 6100.01 78 75 87382.68

PARTITIONS
WALLS
N (building 1) 0.4902 278.00 15 9 1226.48
N (building 2) 0.4902 729.18 15 14 5004.22
S 0.4902 451.75 29 14 3100.27
E (building 1) 0.4902 1421.61 36 14 9756.23
E (building 2) 0.4902 278.00 36 9 1226.48
W (building 2) 0.4902 278.00 20 9 1226.48
DOORS
N 0.346 121.49 9 378.32
S
E 0.346 202.49 14 980.86
W no door no door no door no door no door
WINDOWS
N 1.13 5.48 14 86.69
S no window no window no window no window no window
E 1.13 9.13 14 144.44
W no window no window no window no window no window
TOTAL 23130.46
B. Convention Heat Gain
Hv = 1.1 (cfm) (∆T) + 4840 (cfm) (∆W)
Hvs Sensible = 1.1 (cfm) (∆T) Hvl Latent = 4840 (cfm) (∆W)
Hv =Total Heat Gain
(1.1)(cfm) ∆T Hvs (4840)(cfm) ∆W Hvl
1.1 x (0.38 x x (0.38 x
1001.58) = 4840 1001.58) =
WINDOW 380.6 380.6
418.7 x 14.0 5861.3 1842107.4 x 0.0112 20631.6 26492.9
1.1 x (1.05 x x (1.05 x
19.69) = 4840 19.69) =
DOOR 20.7 20.7
22.7 x 14.0 318.4 100064.6 x 0.0112 1120.7 1439.1
1.1 x (15 x x (15 x
311) = 4840 309) =
PEOPLE VENTILATION 4665 4635
5131.5 x 14.0 71841.0 22433400.0 x 0.0112 251254.1 323095.1
TOTAL HEAT GAIN Total Hvs: 78020.6 Total Hvl: 273006.4 351027.0
Computation of Moisture Content (∆W)
Wo [Outdoor (92 ⁰F db /81 ⁰F wb)] = 0.0204 lb moisture/dry air (from Psychrometric Chart)
Wi [Indoor (78 ⁰F db / 45%)] = 0.0092 lb moisture/dry air (from Psychometric Chart)
∆W = Wo - Wi = 0.0204 - 0.0092
∆W = 0.0112 lb moisture/dry air (difference between outdoor and indoor moisture contents
C. Solar Heat

D. Internal Heat Gain

Hi = His + Hil = (Sensible Load) x (CLF) + (Latent Load)

Sensible Latent
Computations HiS HiL Hi (Total)
Type Pieces Load CLF Load
( n x 3.412 Btu/hr-W ) (Btu/hr) (Btu/hr) (Btu/hr)
(Btu/hr) (Btu/hr)
Power
Description
(Watts)
Light 14 Light Emitting Diodes 7 334.4 1 334.4 0 0 334.4
8 Flourescent Lamp 36 982.7 1 982.7 0 0 982.7

Equipt./ Appliances 6 Projector 270 5527.4 1 5527.4 0 0 5527.4

Others 2 Wifi Router 5 34.1 1 34.1 0 0 34.1

18 Ceiling Fan 60 3685.0 1 3685.0 0 0 3685.0


Total 10563.6 10563.6 0.0 10563.6

E. People Heat Gain


Hp = Hsp + Hlp = No. Ps.(CLF) + No. PL

Hsp
No. or Ps PL Hlp (Latent)
(Sensible)
Group Occupants or Persons Activity Qty. (Btu/hr-person) CLF (Btu/hr-person) (Btu/hr)
(Btu/hr)

A Seated, very light work 300 245 1 73500 155 46500

B Moderately active office work 11 250 1 2250 200 2200

Total= 311 Total Hsp (Sensible) = 76250

Total Hlp (Latent) = 48700


Hp(Total=Sensible+Latent) = 124950

Reference:
Table 4.3 Heat Gain from Occupants in Conditioned Spaces

People Ventilation and Outdoor Air Requirements

Persons/ CFM/ CFM/ Length Width Area No. of


Total CFM (ft3/min)
100m2 Person ft2 (m) (m) (m2) Persons

Room 17 70 20 0 50 1000

Room 18 70 20 0 50 1000

Room 19 70 20 0 50 1000

Room 20 70 20 0 50 1000

Room 21 70 20 0 50 1000

Room 22 70 20 0 50 1000
Utility Room 3 7.5 0 1 7.5

Men's CR 15 15 0 7 105

Women's CR 15 15 0 7 105

Total 6217.5