Professional Documents
Culture Documents
Ata 21 Air Condition
Ata 21 Air Condition
Illustrations
Figure Title Page
1 Engine Bleed-Air Installation ................2 18 Gasper Outlets Cabin Cooling ..............18
2 Air-Conditioning System ................... 3 19 Ram .................................19
3 Air-Conditioning Controls ...................4 20 Cold Air Scoop . . .. . ....... . ... .........19
4 Bleed-Air Shutoff Valve ....................5 21 Ram-air Scoop .........................20
5 Wing Bleed-Air Systems ...................8 22 Main Duct Fan Switch ....................20
6 De Vore Shroud Installations ................9 23 Fan Duct and Ram-Air Valve ...............21
7 Fuselage Bleed-Air Duct System ............1 O 24 Cooling System Duct .....................21
8 Hot Air Valve ...........................11 25 Gasper Outlets Cabin Cooling ..............22
9 Expansion Chamber .....................12 26 Fan Duct and Ram-Air Valve ............... 22
10 Heating System Installation ................13 27 Air-Conditioning Operation
11 Ejector and Recirculated Air (Maximum Cooling) ......................23
Illustrations
Figure Title Page
Table of Contents
T
EFFECTIVI Y: FOR TRAINING PURPOSES ONLY 21-00-00 Page i
01 FEB 06 Revision 2
�
�.. :
--::::
_
======:·����,:�·......
���·_,;!:::':• :1
••�� --;TWIN OTTER MAINTENANCETAAlNING MANUAL
SE.RIES 100/200/300
Table of Contents
21-00-00 AIR CONDITIONING Optional Freon air conditioning is a separate, add-on system
which does not use any of the ducting or components used
INTRODUCTION by the basic heating and ventilation system. It will be dis
cussed at the end of this chapter.
This chapter describes the air-conditioning and pneumatic The pneumatic power systems and subsystems of the Twin
systems installed in the DHC-6 Twin Otter Series 300 air Otter series vary somewhat according to model and modifi
planes. For descriptive purposes, air conditioning is divided cation status. Technicians are advised to compare the
into bleed air, primary heating, primary cooling, ventilation, descriptions herein with the manuals and supplements for the
and temperature control systems. Early series 100 and 200
particular aircraft model.
aircraft used bleed air for pressure instruments.
GENERAL
_ '
rr_
h _ ---=----
2, �����
I
General
Air is obtained from the engine bleed port on the gas gen
erator case of the left and right engines. Bleed air is
directed through both wings into a common manifold in
the fuselage above the ceiling (Figure 2) for distribution to
the installed pneumatic subsystems. The typical Series
300 aircraft would have standard heat with ventilation and
may include the pneumatic operated airframe deicing and
H14 autopilot systems if installed.
CABIN
DUCT
CABIN AIR
OUTLET
TEMPERATURE -.
CONTROL
UNIT
COOLING
DUCT BLEED-AIR
COOLING ANO DUCT
LIGHTING
DUCT
General
Engine P3 bleed air used for cabin heating and airframe r.Ot.FflCIO VI\ \IE
■n■
LEGEND
BLEED AIR
Air flow through the bleed-air shutoff valve cylinder is con AMBIENr PRESSVRC
trolled by the solenoid valve (Figure 4). When the sole MOVING Po\RT
NOTE
·--11 DEVORE
properities that would eventually effect the structural SHl10UD
Hot-Air Valve
Low-Limiting Orifice
Expansion Chamber
1,lfll I !1 '1•1
General
Ejector
Silencer
Ducts
Outlets
.�,
21-40-00 MAXIMUM HEATING SYSTEM
"''ti
Figure 15 illustrates automatic operation in a maximum (.)1,r1111 -,
j!oucToveRHEAT jj---i
I
heating mode.
■
□
LEGEND
\UI '"
I
O,U"IH
I •1· · .1:.-1 .j!"'
' ..,, I
I I
_,I
■ •'
□ •-
1,.: .. . I�� I•,•: ,;..
The hot-air modulating valve is shown fully open to allow t I :_i�,l,,-, r ,'. ; , .�1,�
bleed air enter the jet pump (ejector) plenum at a high I I ◄'':"j1�•;· 1,n
I I
'1�
velocity. The manually operated ram-air valve is shown
� If-. jn11
\
ity from the expansion chamber into the ejector also j
induces cabin air into the ejector area to mix with the hot I
I
bleed air prior to determine the final air temperature. I
I \
I
Conditioned air noise level is reduced to a minimum as it I r
'ti t�,. • I
passes through the silencer. The manually operated cabin I wi.;, ,C n:•
air control valve outboard from the silencer, below the co
I
or
I --- --1
n J:li'ILULAUID
pilot seat floor, is shown in the open condition to allow a �•-.1t111 I M,1NrAICT"
Al •
warm air flow enter the main outlet duct before branching
left and right to both sides of the cabin baseboard heater
outlets at floor level. Separate outlets from the silencer
supply air to the flight compartment. The areas serviced
are the Pilot's and Co-Pilot's conditioned-air outlets, foot
warmers and main windshield defogging system. Since
the cabin distribution ducting is larger than that of the
... ,,
·.:.\f.1111
1J"11vens
.A"
,-,;1
The Flight Compartment temperature can be increased
by altering the position of the cabin air control valve with Figure 15. Air-Conditioning Operation (Maximum Heating)
...
�
General
_I
TWIN OTTER MAINTENANCE TRAJNJNG MANUAL
SERIES 100/200/300
Fan Duct
Cool-Air Outlets
! --
BEHIND IJEAOllNEA UOHTS PANC::l
AtJTl)VAl1: loucTovERHEM
Figure 27 illustrates the operation in the maximum cool lll.\,d'lll��E
COHll'OlUA
ing mode during flight. The motorised hot-air valve is in LEGEND
I ■
•.J_
□
�OT 8LEEO AIR
the fully closed position eliminating further hot bleed air to
' I I I
□
RECIAClJLATEO o\lJ:I
the ejector chamber. The ram air and cabin air control I I .. T
I' ■
CONDlrtONEO Ai::t
valves are both in the open position permitting cool ram I I AMBIENT A,IA
air to flow through the silencer chamber to the cabin base I I }_ I .S E'-ECTRrCA.L
�ir I
'.:., MCOULftnNG 'JAL\oE
I
I
I
L-
General
Control Panel
The automatic temperature controller is located above the Figure 30. Temperature Control Panel
cabin ceiling (Figure 31 ). The controller senses tempera
ture in the automatic mode and adjusts cabin temperature
by controlling the amount of hot air flow to the cabin sys
tem through the motorized hot air valve.
OAT Sensor
!·!�r------......jlj-�
1-----...,,/ -•
FRONT OF CABIN
BEHIND HEADLINER
-- �'
"' ._
Q\o5.q4tnJW•� I
armed for automatic temperature selection (Figure 37).
I', -:-,.-
18f - '
Positioning the rheostat between COOL and WARM sup
plies the desired temperature demand signal to the con
-----------------' M'IDl!HfE'l.:J •fL",lEJI C'VTlE7i
I f- - I- - I- ?
troller. At the same time the temperature controller - --------
'::::'.�
���-�Jr,._
- ____ ,,,
receives an ambient temperature signal from the OAT \ I
sensor, an area temperature signal from the cabin tem
perature sensor and a temperature signal from the
silencer duct for comparison. When the temperature con
troller senses the signals are out of balance (Wheatstone
drcuit) the controller will send a current pulse signal to the
hot air valve to adjust the hot air valve position either in
the open or closed direction. The movement of the valve
will increase or decrease the amount of hot air supply
depending on the demand signal sent by the temperature
controller. The magnitude of the pulsating signals from the
temperature controller to the hot air valve is proportionate }._ CABIN CASI N SENSOR � ,
I)',.
, }._ BASEBOARD CEILING FAN
to the out of balance signal. Each following pulse signal is HEATER EXHAUST
}.. OUTLETS vpi-
■
BLEED AIR 1tr1N5TAL..EDJ
is correctly positioned. ELECTRICAL FLOW
TO
LH ENGINE TO l:11"
i!!NCifT1E
If the mode selector switch is in automatic with no airflow
INTAKE
OEF\.ECTOR IICt� •
DCrl.!iCTOfll
to the cabin the temperature controller will drive the hot air
valve either fully open or closed. To prevent the condition CHECK VALVES \IQD •••e2
,,:,'' ____________....,_,
temperature control system is inhibited, and the manual I I 1,
temperature control switch is armed. Holding this switch
to the MANUAL COOL or MANUAL WARM position,
motors the valve in the selected direction until the switch
is released to the HOLD position. When using the manu ',
al temperature control switch it should be held in the
MANUAL COOL or MANUAL WARM positions for only j
I I
, , llllCI
O'l!r><!iAI
swn:•• \\:
I
I
I
I I
short periods and then released when the temperature I L.: COi>ii.on
stabilises. In Manual mode the valve will motor from one HF.�IEII
0\/1UT
extreme to the other (open to close) in 30 seconds.
Selecting the mode selector switch to the OFF position I
will power Hot Air Valve closed. I
L -
FAl'I
■■
LEGEND 1-f(/\1 I •t'.'-fAMUf P
BLEEO AIR 1,ff ltJS.lf>I lfl),
ELECTRICAL FLOW
TO YOllH
LH ENOINE
INTAKE �
DnPLKTOI! !tfTMl
DiVLfC'IQJI
8LEEO•AIR
SHUTOFF/
\
,
VALVE MOD 611'82 /
MOD .IAID
I� I
u.-,.,ui11
AIRCRAFT
[I
0!:Hl�,C H[ADLl"tEr.
136 are shown in Figure 39. Note that the external air I I '1F.Uq:::utJi .,.r .... Joi;=-
■
cc,,,:,,·1c,rJ;� \1::
AMRIP�T ,\jll
) I I
t
I
the jet pump (ejector) plenum. In this configuration cold /1 .ti t, WINDSMIE�D HEATER OUTLETS S ELECl�ICAL
ram air and cabin recirculated air can both be induced I I _ L .L J_L ./_ 1 _1_
I
I I L
with bleed air flowing under pressure through the ejector
chamber. The manually operated ram air valve controls I
I
the amount of cold airflow. As early aircraft do not have I
the ground operable duct fan the aircraft cannot be cooled I
during ground mode conditions unless modified with the j
Freon operated Air Conditioning Unit mod S.O.O.6109. I
I HOT All'
V�LVE
CHECK
�! l::JCT
An early attempt to improve on cabin cooling using larger I
v �l VE OVE�><e•-
IMOTORl�E01
----- I ---1 1 }-!�r:!,�__ .;
air scoops with small fans for ground mode conditions I �11:1 50"
I PILOT 5 r;iH1r.11UJrn COPILOT s
did not produce the expected level of passenger comfort. I
�OOT
WARMER
AIR INTAKE FOOT
WARMEA
I � 1
I
rr-----------:::.,)-_,,..___��--�
l 11.0\'All'I
I \
I
I [
I
I CABIN
1...._ BAS£90ARO
-E]
/
I"
I MEA.T[R CABIPI I
O\JTlETS T£ ... P
CAM< .....-:--
/I
SENSOR CEILING
"-- _____
....... HHAL/ST
VENT '
'
I /,
General
Heat Exchanger
Dual-Pressure Switch
Strainer
Pressure Regulator
Low�Pressure Switch
Bleed air is tapped off the common manifold and cooled r.=;:::::::::: MJlOl'ILDT
by being routed through the heat exchanger. Air exiting
the heat exchanger is directed to the strainer and dual
pressure switch. An in-line regulator then reduces bleed
air pressure to 18 psi. The regulated air pressure is then
directed to various services (airframe de-ice, etc.) and to
a low-pressure switch. The dual pressure-sensing switch
ensures that if bleed-air pressure drops to 25 psi, the hot
air valve can demand no additional air. If pressure drops
�OW PRESS
C.a.UTION LIGHT
General
/�
BREAKERS EI/APORATOfl FAN /
CONDIJlilR _,,,
Figure 44 illustrates a typical installation in Twin Otter air _,,
/ GOND�NSER
floor.
........
EXPANSI
I/AL P t6&UAI!!
SWITCtt
.. .
COMPRESSOR •� � -
MOTOR
�IA IH lfl(!.
l
ing operation of the alr conditioning unit in fllg:ht unless OFF
GENERAL (Continued) evaporator and K4 condenser fan relays are energized for
operation. With power to the evaporator and condenser
relays are located on a panel attached to the forward face fans in parallel mode both fans operate at a high speed.
of bulkhead Stn 332 below the cabin floor. The 5-amp cir
cuit breaker labelled F1 provides protection for the five CAUTION
relays and associated wiring including switch contacts.
The 120-amp circuit breaker labelled F2 protects the com When operating on the ground with one gener
pressor motor and the two 40 amp circuit breakers ator on, do not select QUICK COOL, as the
labelled F3 and F4 protect the evaporator and condenser operating generator may overheat because of
fan operations. high current demand.
NOTE When the switches are set to GROUND and FAN ONLY,
the K1 relay is de-energized to shut down the compressor
Should an engine start be attempted when the motor. The K4 relay is energized to operate the condens
air conditioning unit is operational the KS relay er and evaporator fans at moderate speed. When the
will receive power through the engine start POWER switch is set to FLIGHT, the direct ground is
switch contacts to de-energize the compressor replaced with a ground obtained through both generator
motor K1 relay to stop compressor motor oper control relays PD-K5 AND PD-K6 providing both genera
ation. If the K5 relay fails to inhibit the com tors are ON Line and operating. Loss of either generator
pressor motor operation there would not be suf will result in the loss of the refrigeration system due to the
ficient power to achieve the engine start. opening of the generator control relay contact removing
the ground.
When both switches are selected to GROUND and NOR
MAL, the K1 compressor motor and K4 condenser fan As the system requires airflow through the condenser
relays are energized for operation. With power to the core to dissipate some of the high-pressurised Freon liq
evaporator fan through the condenser fan now in series uid temperature an inlet (left) and outlet (right) air grill is
mode the two fans will operate at moderate speed. installed on each side of the fuselage below the floor area.
Recirculated cabin air is drawn through a grill on the cabin
When both switches are selected to GROUND and floor before passing through the evaporator coils to cool
QUICK COOL, the K1 compressor motor including K3 before entering the cabin.
□
LO\!,-PqESS\IAE FRE::>ll \14POP
■
l'!l�SSU'IE-""� VAPQP
Freon by the condenser unit with an external airflow pass HIGH PRE.SSURE LJdVl(.l 14H•O,J
ing over the condenser unit. The high-pressure liquid
Freon flows through a dehydrator removing water
droplets from the Freon liquid before passing through the
expansion valve. The expansion valve converts the liquid AIR �ClNDITIOl,lflG
21-00-00 COMPONENT DESCRIPTION ters increasing the compressor speed it was necessary to
replace the compressor with a new unit (lower displace
Compressor Motor ment per revolution) to maintain the same horsepower
capacity. A later rotary compressor and 1000-hour TBO
The 28-VDC-compressor motor, installed under the right motor became available from the air conditioning manu
side of the cabin floor, is secured to the forward pallet by facture with Kit No SB-34-1 (S/8 6/414). The change
a swivel front bracket and a rear bracket having two enhanced the overall operation of compressor output per
adjustable rods. Two pulleys, attached to the motor shaft, formance.
drive the compressor with two belts. On aircraft incorpo
rating Mod 6/1684 (S/B 6/382) at 637 the two-belt drive Condenser
concept was replaced with a single V type belt to improve
pulley retention and eliminate repetitive drive belt failure The air-cooled condenser is mounted to the left of and
problems. A later 1000-hour TSO motor became available parallel to the airplane centreline on two brackets secured
from the manufacture by Kit No SB-33-1 (SIB 6/414). to the forward pallet. Two refrigerant connections are pro
vided at the right rear of the condenser; the lower is the
Compressor inlet and the upper the outlet.
The evaporator is located under the right side of the cabin A thermostat switch is secured to the rear side of the
floor and is secured to the rear pallet by two brackets. Two evaporator duct.
connectors are provided on the evaporator: an expansion
valve connects to the front connector, and tubing routed to Relays
suction on the compressor connects to the rear.
The five relays identified K1 to KS are bolted to a panel
Receiver-Dryer installed under the right side of the cabin floor on the for
ward face of the bulkhead at Stn 332.
The receiver-dryer is secured to the right outboard side of
the compressor by a clamp. A Tee connection at the top of Circuit Breakers and Current Limiter
the dryer provides for two connections and incorporates a
sight glass. Tubing from the condenser outlet connects to Four circuit breakers identified F1 to F4 secured to the
the forward connection, and tubing from the rear connec fuselage frame Stn 332 are located outboard of the relay
tion is routed to the expansion valve. A sight glass inspec panel below the cabin floor. Access to the manually reset
tion hole by mod 6/1521 (TAB 652/2} at 460) with a circuit breakers is obtained by removing the right floor
removable snap hose plug in the seat rail immediately panel immediately forward of the bulkhead. A 150-ampere
above the receiver-dryer was adopted to improve acces current limiter, in the 28-volt power supply line to the air
sibility. conditioning system, is located adjacent to the power dis
tribution and generator control box.
Pressure Switch
Main Duct
A high-pressure cut-out switch, connected by a small
diameter tube to the compressor pressure T-connection, The main duct located from the evaporator fan outlet at
is installed on the left side of the forward pallet. Stn 321.60 is routed through the cabin floor before pass
ing through the cabin rear bulkhead Stn 332 to enter the
rear baggage compartment where it is vertically posi
tioned before being attached to a duct in line with the
cabin ceiling distribution ducts. An improved insulated
Main Duct (Continued) of the evaporator unit from beneath the cabin floor to the
rear baggage compartment against the forward upper
evaporator cold air duct is available from the manufacture bulkhead aft face. The relocation of the evaporator pre
by kit S8-032-1 (SIB 6/414) to reduce heat transfer from vents cooling air loss that occurs with the evaporator
the air conditioning cold air duct to an area of the rear beneath the cabin floor area and outlet air duct into the
baggage compartment to maintain the level of cold air rear baggage compartment. In addition two independent
temperature for passenger comfort. dual speed motors each driving a squirrel cage fan blow
ing air through the evaporator coils directly into the cabin
Distribution Ducts interior have replaced the evaporator fan. Dual fan is for
quick cabin cooling and single fan operation when the
Two distribution air ducts installed in the cabin ceiling run cabin has cooled sufficiently for passenger comfort.
from the forward bulkhead Stn 112 to the rear cabin bulk Ceiling ducts are not used for distribution as air is blown
head Stn 332 before joining a bifurcated duct passing directly into the cabin. The deletion of the condenser fan
through the bulkhead to the main evaporator duct located reduces the electrical load demand. Other changes relo
in the rear baggage compartment. The distribution ducts cated the relay and circuit breaker panel from beneath the
are secured to the ceiling panel channel on one side and cabin floor to the aft baggage compartment adjacent to
by Velcro pile and hook on the other. the evaporator unit to improve access.
Alternative Air Conditioning Unit Two select switches are located on the flight compartment
overhead console switch panel. One switch is labelled
An alternative air conditioning unit, previously available FANS - OFF -AIR CONDITIONER and the other switch is
from Metro Airlines Texas, is now supplied by Pace labelled HI - LOW. The system is designed to operate with
Aviation, Reno, Nevada U.S.A. with STC approval. The ground power supply and prevent compressor motor
system is lighter by approximately 51 lbs. has a load rat operation during flight should one generator go off line.
ing between 95 to 110 amps to cover all aspects of oper With evaporator fans operational once DC power is avail
ation and capable of cooling the cabin quickly. able additional cabin airflow may be obtained from the
rear baggage compartment area to supplement the nor
To achieve the level performance major changes were mal airflow through passenger Gaspers during flight with
incorporated such as adopting the latest Zee Company out the air conditioner unit being operational. As each
compressor and evaporator units including the relocation
Alternative Air Conditioning Unit (Continued} compartment behind the instrument panel where the pres
sure is directed to twin ejectors to create a vacuum con
evaporator fan is protected by a 10-amp circuit breaker dition to operate the attitude and directional indicators for
failure of one fan will not restrict operation of the other fan. both crew instruments. The system consists of a by-pass
Compressor motor protection is by a 150-amp circuit valve, suction relief valve, air ejectors, low suction warn
breaker and high-pressure switch. ing switch including an emergency instrument vacuum
valve with relative piping and associate pressure and vac
SERIES 100/200 AIRCRAFT uum gauges. For the system to operate correctly a pres
sure between 4.5 to 5.5 inches Hg is required.
21-00-00 PNEUMATIC SUB-SYSTEMS
FOR GYROSCOPIC FLIGHT INSTRUMENTS Should the pneumatic system supply drop to a deter
mined minimum level the bypass valve solenoid will be
On early series aircraft the Pilot's and Co-Pilot's attitude energized to open by a signal from the low suction warn
and directional indicators were pneumatically operated Ing switch to permit bleed alr to flow directly to the ejec
either by \lacuum, bleed alr or dry air pump systems. Each tors A pressure gauge located on the pedestal in the fllght
system was initially available for single Pilot operation compartment indlcates system pressure. If the bypass
although the Installation could be modified by optiona11 valve fa1ts to open an alternative supply of air pressure
mod S.O.O.6075 to Include Co-Pilot Instrumentation. can be used by opening the manually operated emer
gency instrument vacuum valve located on the lower left
The following descriptions clarify the various pneumatic of the instrument panel. The valve, which can also be
systems prior to Series 300 aircraft for pilot and Co-Pilot used to increase the vacuum pressure supply, should
flight instrument operation. always be adjusted to indicate 4.5 to 4.7 inches Hg on the
instrument suction gauge to maintain the required ejector
21-00-00 FLIGHT INSTRUMENT VACUUM SYSTEM pressure flow.
PRE MOD 6/1046 AIRCRAFT 6 TO 57
For pre mod 6/1046 aircraft operating with the H14
The flight instrument vacuum system pressure is tapped Autopilot the system will include a dual pressure switch
directly from the 18-psi pneumatic reduction package in also connected to the automatic temperature controller.
the cabin roof, which receives bleed air from both Should the pneumatic system pressure supply fall to a
engines. Regulated pressure is sent forward to the flight determined minimum level the bypass valve is energized
]�.
�IAIIFH1$
continues to deteriorate an annunciator caution light
labelled LOW SUCTION will illuminate advising of the 5lJCl
condition. Should the cabin temperature controller be in GE )LOW SUCTION SUCTION
.
SUCTION 1.0Wo\lCtlUH
WARNING RELIEF
the automatic mode the dual pressure switch will also sig $WITCH VALVE
RELIEF WARNING
,..,.�
VALVE SWITCH
21-00-00 FLIGHT INSTRUMENT BLEED AIR MOD 21-00-00 FLIGHT INSTRUMENTS ORY AIR. PUMPS
6/1046 AIRCRAFT 58 TO 149 MOD 6/1166 AIRCRAFT 150 TO 230
Pressure air for pneumatJc powered instruments 1s The Dry Air Pump system was adopted as a method to
obtained from lhe engine compressor P2.5 bleed port on overcome instrument problems, which were attnbuted to
each engine casing to flow direcUy through the wing moisture from Lhe bleed air supply. A,r pressure from the
before joining into a common duct line on the left side of dry air pumps is provided at a lower temperature and
the fuselage wall lo the instrument pressure reduction moisture content with remaining moisture level removed
regulator. The regulator package 1s installed on the aft using filters and automatic water drains.
face of bulkhead Stn 60 behind lhe instrument panel for
short nose pre mod 6/1077 aircraft. For post mod 6/1077
aircraft with a long nose baggage compartment com Eacn independent system consists of a dry air pump
mencmg at aircraft 136 the regulator package is localed Installed on the engine accessory gearcase wilh an air
on a mounting plate installed forward of bulkhead Stn 60 inlet filter installed aft of the nacelle engine firewall. Other
components include pressure regulator, filter. automatic
The pneumatic system consists of pressure regulators, water drain, pressure relief valve and associated
strainers. automatic water drains, filler, relief valves and pipelines. Each dry air pump 1s capable of suppl,ying suf
associated pipes. Engine supplied pressurised air ranging ficient af r pressure to operate both pilot and Co-Pilot
from 10 lo 80 psi is regulated to 2.4 psi before passing instruments.
through check valves into the pilot and Co-Pilot manifolds.
The check valves In the mantfolds isolating the pilot and Each dry air pump supplies air pressure to the pneumatic
Co-PIiot supply pressure in lhe event of an inoperative system between 1 0 lo 80 psi before Initial reduction to 8
supply source. psi by a pressure regulator located on the aft face of the
engine firewall adjacent to the inlet filter. Air pressure
A twin red ball pressure Indicator located on the pilot passes through each wing to the left side of the fuselage
instrument panel fndicates manifold pressures both corre where the pipelines run in parallel to the night compart
sponding to within 0.3 inch Hg with the pressure gauge ment before further filtering and pressure reduction to 2.5
Installed on the Co-Pilot Instrument panel psi before entering the pilot and Co-Pilot instrument man
Ifolds. For short nose pre mod 6/1077 aircraft before 136
the second pressure regulator with filter and automatic
water drains are located aft of bulkhead Stn 60. For long
nose baggage compartment post mod 6/1077 aircraft at
136 the pressure reduction and filtering package is locat
ed forward of bulkhead Stn 60.
i
I W,ClE I �OICAl'OI< 1Ntll0.QlllR
The supply for the heat and vent system is from a manifold I
,_
I
,· _..J
supplied by both engines. Isolation is provided by check
I
I
I
■
■
PUMP INLET AIR
either air pump can supply both manifolds during engine-out PUMP OUTLET PRESSURE
■
■
PAEs.&Ull!,.
REGULATING REGULATED PRESSURE
�J:1_1.G,
VALVE VALi/ii WATER
AMBIEl'IT
--r ELECTRICAL
I
RIGHT ENGINE DRIVEN
AIR PUMP
ILTl!'1
GENERAL NOTE
Various adjustment and test procedures are outlined in The removal and installation of the system
the Maintenance Manual. There is a pressure regulator components is self-evident. With the exception
valve procedure for crack and re-seat pressure test along of the compressor motor, drive belts, and
with a test set-up diagram. The same information for func receiver dryer, it is advisable to remove the
tional test is also supplied. appropriate pallet before attempting to remove
a component.
The adjustment/test sequence for the dual-pressure
switch lists required equipment and supplies a wiring 21-00-00 LIMITATIONS
schematic for the pressure switch.
The limitations outlined in Section 1 of the approved AFM
Refrigeration System must be complied with regardless of the type of operation.
Servicing
NOTE