1-2014 (R2020)
SAFETY EQUIPMENT CHECKLIST
A Quick Guide to testing Emergency Showers and Eyewashes
Haws AG www.haws.ch
Bachweg 3 CH-3400 Burgdorf / Switzerland
Phone: +41 (0)34 420 60 00 E-Mail: info@haws.ch
Weekly Testing Requirements
Haws AG www.haws.ch
Bachweg 3 CH-3400 Burgdorf / Switzerland
Phone: +41 (0)34 420 60 00 E-Mail: info@haws.ch
Annual Testing Requirements
The recommended testing flow pressure is 207 kPa (+3.4 kPa -0 kPa) [30 psi (+0.5 psi –0.0 psi)]
LOCATION
Safety stations shall be accessible within 10 seconds of
the hazard, approximately 16.8 m [55 ft].
Safety stations should be situated on the same level as
the hazard, and the path of travel should be free of
obstructions.
Emergency equipment locations should be well-lit and
identified with highly visible signs.
All employees exposed to hazardous materials should
receive instruction on the location and proper use of
emergency equipment.
In areas where freezing conditions are possible, units must
be protected from freezing or equipped with freeze
protection.
Haws AG www.haws.ch
Bachweg 3 CH-3400 Burgdorf / Switzerland
Phone: +41 (0)34 420 60 00 E-Mail: info@haws.ch
Annual Testing Requirements
EMERGENCY SHOWER
The showerhead shall be positioned 208.3 to 243.8 cm [82
to 96 in] above the surface floor of the user.
The shower shall deliver a minimum flow rate of 75.7 L/min
[20 gpm] for 15 minutes and produce a water column
50.8 cm [20 in] wide at 152.4 cm [60 in] above the
surface floor of the user, with a clearance of 41 cm [16 in]
from any obstruction.
The shower design shall allow the flushing flow to remain
ON without the need for the operator's hands.
The valve shall be easy to operate, transitioning from
“OFF" to “ON" in one second or less, with the actuator
positioned no more than 173.3 cm [69 in] from the
surface floor of the user.
Haws AG www.haws.ch
Bachweg 3 CH-3400 Burgdorf / Switzerland
Phone: +41 (0)34 420 60 00 E-Mail: info@haws.ch
Annual Testing Requirements
Haws AG www.haws.ch
Bachweg 3 CH-3400 Burgdorf / Switzerland
Phone: +41 (0)34 420 60 00 E-Mail: info@haws.ch
Annual Testing Requirements
COMBINATION UNIT
The Combination Unit must meet the requirements of an
emergency shower.
The Combination Unit must also meet the requirements of
either an eyewash or eye/face wash, depending on the
application.
Components of the Combination Unit should be capable
of operating simultaneously and positioned in a way that
allows users to utilize the components simultaneously.
Haws AG www.haws.ch
Bachweg 3 CH-3400 Burgdorf / Switzerland
Phone: +41 (0)34 420 60 00 E-Mail: info@haws.ch
Annual Testing Requirements
WATER TEMPERATURE
Units must deliver tepid flushing fluid.
The temperature range shall be above 16°C [60°F] and
below 38°C [100°F].