| • Single Master Application Controller (EN
It is installed on a TH35 DIN rail acc. to EN 60715, with
the bus connection made via a bus connecting terminal.
62386-103). The device may only be operated
Network and DALI cables are connected via screw termi-
For your safety in DALI lines with electronic ballasts connected
nals on the device.
and not with other DALI control units within the
line (no multi-master operation).
• The power required for up to 64 connected
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR electronic ballasts is supplied directly from the Connections, displays and operating
ARC FLASH gateway. No additional DALI power supply is elements
required, nor is this permissible.
Safe electrical installation must be carried out only by The appliance connections as well as the programming
skilled professionals. Skilled professionals must prove • The special interface for configuration of the
button and programming LEDs required for KNX com-
profound knowledge in the following areas: DALI segment is designed as a DCA (Device
missioning can only be accessed in the distribution
Control App) for the ETS5.
• Connecting to installation networks board when the cover is removed.
Note that, in addition to the product database
• Connecting several electrical devices (knxprod file), a corresponding ETS app (et- Manual mode buttons can be operated and indicator
• Laying electric cables sapp file) is also installed. Both files are availa- LEDs read with the distributor cover closed.
• Connection and setup of KNX networks ble in the KNX online catalogue and on the
• Connection and setup of DALI networks manufacturer website. F
• Connection and setup of emergency lighting sys- • DALI devices for single-battery emergency
tems lights of device type DT-1 can be read by the
gateway and switched and operated via DALI
• Safety standards, local wiring rules and regulations
telegrams if required. DALI commands for
Failure to follow these instructions will result in starting and reading test results are not sup-
death or serious injury.
L N PE
ported.
Product features
• 2 independent DALI channels E
• Addressing of 16 DALI groups per channel
5/13 6/14 7/15 8/16 Man.
• Flexible DALI commissioning concept in ETS5
• Coloured light control with the support of ballasts of G
device type 8 D1+ D1- D2+ D2- KNX / PRG
• Coloured light control depending on ballast subtype:
– Colour temperature (DT-8 subtype Tc)
– XY colour (DT-8 subtype XY)
– RGB (DT-8 subtype RGBWAF)
– HSV (DT-8 subtype RGBWAF) D C B A
– RGBW (DT-8 subtype RGBWAF) A KNX bus connecting terminal
– DT-8 subtype PrimaryN is not supported B Programming button, normal/programming mode
• Support of timer programmes for control of groups by C Programming LED, normal/programming mode
value and/or colour
D DALI output terminals: D1 (channel 1) and D2
• Various operating modes for groups such as continu- (channel 2)
ous operation, night mode, staircase mode
E Operating buttons with a status LED (red) for each
• Integrated operating hours counter for each group, group (1-8 and 9-16) for manual mode (group oper-
with alarm once the end of the service life has been ation/group status, broadcast and service func-
reached tions)
• Individual fault detection with objects for each individ- F Mains connection
ual light/electronic ballast
G Operating button with status LED (RGB) for activat-
• Complex evaluation of faults at group/device level with ing manual mode
fault number and fault rate calculation
• Fault threshold monitoring with individually adjustable
threshold values Further information on operation, operating
• Scene module for comprehensive programming of
| modes and troubleshooting can be found in the
scenes application description.
½
Double basic insulation must be used between Output voltage: typically 16 V DC, short-cir-
the KNX installation and the mains voltage! KNX
cuit proof max. 250 mA, ba-
For this purpose, additionally insulate the wires of sic insulation (no SELV)
the KNX cable as far as the bus connecting termi- Wire cross-section: min. 1.5 mm²
nal using the enclosed shrink hose. Output current: max. 250 mA, min. 128 mA
Shutdown delay: 600 ms after DALI short cir-
cuit shutdown occurs
Start-up attempt after
shutdown: 5 s after short-circuit detec-
tion
Connections:
Supply voltage: Screw terminals 1-2.5 mm2
single-core and multi-core
DALI bus: Screw terminals 1-2.5 mm2
single-core and multi-core
DALI 2 KNX: Bus connecting terminal
Ambient operating tem-
Once all connections are complete and the supply volt- perature: -5 °C to +45 °C
age has been switched on, the DALI line can be commis-
Relative humidity
sioned and programming carried out with the ETS.
(non-condensing): 5% to 93%
Degree of contamination: 2
Please refer to the application description in order Overvoltage category: III
| to perform these operations. Device width: 4 modules = approx. 72 mm
UK Representative
Schneider Electric Limited
Stafford Park 5
Telford, TF3 3 BL, UK