DEFECT LIST OF UNIT#3 AS ON dt:01.04.

24
Sr. Problem Agency Remarks
No.
1. All mills feeder not run on auto mode. C&I Dust &noise
level
required for
Auto run
2. SH & RH spray valve not working on auto mode. C&I
3. HP flash tank temp. valve on CRT shows false C&I
4. Coal leakage from various coal pipe Mill Mtc.
5. Mills classifier outlet gate not open in sequence (B2, A3, Mill
C4,C2, D2,D4,E3 & F4). Mtc.&Elec
t.LT
6. Mill-3AB both reducer lube Oil pump are running. Problem Mill Mtc.&
persisting since long time. (Status problem ) C&I
7. Sox, NOx and CO parameter bad on CRT. C&I

8. Incomer ampere meter and voltage meter of compressor Elect.Mtc


room are defective.
9. IAC-1 second stage pr. Gauge defective
10. IAC-1 DMCW outlet pr.Gauge defective

11. IAC-2 stg-2 pr.gauge defective CA Mtc.

12. IAC-2 DMCW outlet pr.Gauge defective

13. SAC-1 DMCW outlet pr.Gauge defective

14. SAC-3 DMCW outlet pr.Gauge defective

15. SAC-2 stg-2 pr. gauge defective

16. Noise and dust level of Mills are showing bad on CRT. C&I

17. HPBP-1 warm up line insulation required. Boiler Will be


Mtc. attended in
short shutdown
18. Platen super heater flue gas temp. is showing bad C&I

19. CWP-1 motor winding temp reaches 134 degrees centigrade Elect.Mtc.
often (point 1 and 6 shows bad on CRT ). & C&I
20. FG temp. Before economizer not showing correct valve. C&I

21. BPE-1 &2 valves does not show percentage opening on BUP C&I Indicators
analogue meter stuck. not available
22. BPE-2 valve does not show correct position ( variation in C&I
demand and position )
23. Regular cleaning is required in Mill area, feeder floor, Mill Mtc.
lubrication pumps & seal air fan area.
24. HPBP BD valve does not close on auto when Bypass tripped C&I solenoid not
DEFECT LIST OF UNIT#3 AS ON dt:01.04.24
also does not opens when bypass are charged. available
25. BFP-3A HC journal bearing temp. at Point no-2 & thrust brg.at C&I Temp card
point no-1 indication bad on CRT not available
26. BFP-3C motor winding temp. at point no. –I,J,M,N indication C&I Temp card
bad on CRT not available
27. Viscous filter cleaning required Mill Mtc.

28. LRSB-82 not operative since long time C&I

29. Ensure healthiness of battery bank system C&I/Elect

30. DMCW Tank level high and low alarm does not appears on CA MTC
BUP
31. BFP –B most of temp points are bad on CRT. C&I DDC Temp card
not available
32. HP exhaust steam temp point no.3 at ATRS screens showing C&I ATRS Special
zero value. Module not
available
33. MAL-66 ,51,54 not operative from control room ELECT.LT

34. Most of classifier outlet gate not (open/close). Required to be Elect L.T ,
Jointly checked. C&I, Mill
Mtc.
35. Proper illumination is required in 3.5 mtr and 8.5 mtr of Elect.
turbine area and 23.5 mtr deaerator floor, turbine MOT lighting.
room, and near DM-2 and DM-4 valve at zero mtr and mill
area .
36. Coal leakage at hot air box 3A side MILL 3AB Mill Mtc.
37. Heavy coal leakage from coal pipe between corner no.1 and 2 Mill mtc.
at 30 mtr elevation, previously soot blower cables of C&I was
burnt due to accumulation of coal from these leakages.
38. Turbine Lube oil temp. control valve has tendency of getting C&I(ATRS)
stuck at any position.
39. Turbine MOT level in HMI windows showing incorrect value. C&I(ATRS
40. MAL-51 Shows open status on BUP but its closed at site C&I/LT
41. Startup vent valve S28 S29 passing observed , valve setting ELEECT
required (LT)
42. ID FAN 3A I/L AND O/L temp showing bad values C&I Temp cards
faulty spare
not available.
43. HOT gas temp before h2 cooler B & C are bad. Elect gen
mtc.
44. SAF B of Mill 3AB Not available ELECT LT Motor
rewinding
required
45. SAF B of Mill 3AB Not available Mill Mtc. Bearing
Housing
DEFECT LIST OF UNIT#3 AS ON dt:01.04.24
replacement
46. Clarifier Pump 2 motor (LT) ELECT LT
48 By pass air of Mill –AB , B side getting reverse command Mill Mtc.
while increasing and decreasing of air
49 Check back of RC Shutoff gates (Open /Closed) ) not comes Mill Mtc
properly on sequence while taking Mills
50 HP pump No 2 of MILL CD not build adequate pressure MILL Mtc.
51 CT Fan 2,7,13 not available since long time CA Mtc
52 SAC -2 not available since long time CA Mtc
53 Ash water pump No 3 not available since long time CA Mtc
54 Turbine lube oil temp before and after the cooler shows bad Tur Mtc.
55 Seal Oil pump blower is not taking command from BUP Gen Mtc.