Product Overview Design Guide

does not eliminate all potential differences due to the

130BB465.10
ground and shield connected in the PC USB port.

2 2

130BT308.10
Status 1(1)
1234rpm 10,4A 43,5Hz

a
43,5Hz

Run OK

Quick Main Alarm


b Status
Menu Menu Log

Illustration 2.25 USB Connection


Ca
ck

nc
Ba

el

2.8.2.1 MCT 10 Set-up Software


Info

c On OK
The MCT 10 Set-up Software is designed for commis-
sioning and servicing the frequency converter including
Warn.
guided programming of cascade controller, real-time clock,
Alarm smart logic controller, and preventive maintenance.
This software provides easy control of details as well as a
general overview of systems, large or small. The tool
Hand Auto
d
on Off on Reset handles all frequency converter series, VLT® advanced
active filters and VLT® soft starter related data.

Illustration 2.24 Local Control Panel


Example 1: Data storage in PC via MCT 10 Set-up
Software
1. Connect a PC to the unit via USB or via the
RS485 interface.
2.8.2 PC Software
2. Open MCT 10 Set-up Software.
The PC is connected via a standard (host/device) USB 3. Select the USB port or the RS485 interface.
cable, or via the RS485 interface.
4. Select copy.
5. Select the project section.
USB is a serial bus utilising 4 shielded wires with ground
pin 4 connected to the shield in the PC USB port. By 6. Select paste.
connecting the PC to a frequency converter through the 7. Select save as.
USB cable, there is a potential risk of damaging the PC USB
host controller. All standard PCs are manufactured without All parameters are now stored.
galvanic isolation in the USB port. Example 2: Data transfer from PC to frequency
Any ground potential difference caused by not following converter via MCT 10 Set-up Software
the recommendations described in the operating 1. Connect a PC to the unit via USB port or via the
instructions, can damage the USB host controller through RS485 interface.
the shield of the USB cable.
2. Open MCT 10 Set-up Software.
It is recommended to use a USB isolator with galvanic
isolation to protect the PC USB host controller from 3. Select Open – stored files are shown.
ground potential differences, when connecting the PC to a 4. Open the appropriate file.
frequency converter through a USB cable.
5. Select Write to drive.
Do not to use a PC power cable with a ground plug when
the PC is connected to the frequency converter through a All parameters are now transferred to the frequency
USB cable. It reduces the ground potential difference, but converter.

MG20N602 Danfoss A/S © 09/2014 All rights reserved. 35