Professional Documents
Culture Documents
71FINAL1
71FINAL1
SYSTEMS
A Project Report Submitted in Partial Fulfillment of the Requirement for the Award of the
Degree of
Bachelor of Technology
in
Electrical and Electronics Engineering
Submitted by
CERTIFICATE
This is to certify that the project report entitled “FUZZY LOGIC CONTROL BASED
In partial fulfillment for the award of the Degree of Bachelor of Technology in Electrical and
Electronics Engineering to the Jawaharlal Nehru Technological University Gurajada, Vizianagaram is a
record of bonafide work carried out under my guidance and supervision.
The results embodied in this project report have not been submitted to any other Institute or University
for the award of any Degree.
External Examiner
LENDI INSTITUTE OF ENGINEERING AND TECHNOLOGY(A)
(Approved by A.I.C.T.E & Permanently Affiliated to JNTUGV)
Accredited by NBA &NAAC with ‘A’ Grade
Jonnada (Village), Denkada (Mandal), Vizianagaram Dist. – 535
005. Phone No. 08922-241111, 241112
E-Mail.: lendi_2008@yahoo.com Website: www.lendi.org
ACKNOWLEDGEMENT
I consider it as a privilege to thank all those people who helped us a lot for the
successful completion of this project work entitled “FUZZY LOGIC CONTROL
BASED LOAD FREQUENCY CONTROL OF MULTI AREA INTERCONNECTED
POWER SYSTEMS”.
I sincerely express our whole hearted gratitude to Mr.T.PAPI NAIDU,
Associate Professor for his technical guidance, constant encouragement and support in
carrying out the project work.
I would like to thank Dr. K. Subbaramaiah, Head of the Department of
Electrical and Electronics Engineering for his collaboration and constant
encouragement for the successful completion of this project work even though he is
busy with his hectic schedule of teaching and administration.
I Sincerely express our wholehearted thanks to Dr. V.V. Rama Reddy,
Principal for providing us all required software and working facilities in the college to
carry out the hardware setup successfully.
I avail this opportunity to express our deep sense of gratitude and hearty thanks to
management of Lendi Institute of Engineering and Technology for providing
congenial atmosphere and encouragement.
Finally, we would like to thank all the Teaching and Non-Teaching Staff who
helped using the successful completion of this project work. I also like to thank all of our
Friends & Parents helped us directly or indirectly for the successful completion of our
project work.
INSTITUTE
VISION
Producing globally competent and quality technocrats with human values for the holistic needs of
industry and society.
MISSION
To be a hub for imparting knowledge, skills, and behaviour for exemplary contributions in the field of
Electrical and Electronics Engineering.
MISSION
PEO1: Graduates shall have strong foundation in core and allied Electrical and Electronics
Engineering, in sciences and mathematics, to become globally competent in designing, modeling and
critical problem solving.
PEO2: Graduates shall involve in research activities in the field of electrical and electronics
engineering through lifelong learning and provide solutions to engineering problems for sustainable
development of society.
PEO3: Graduates shall have good communication skills and socio-ethical values for getting
employment or higher studies by excelling in competitive examinations and be able to work in
supportive and leadership roles.
LENDI INSTITUTE OF ENGINEERING AND TECHNOLOGY(A)
(Approved by A.I.C.T.E & Permanently Affiliated to JNTUGV)
Accredited by NBA & NAAC with ‘A’ Grade
Jonnada (Village), Denkada (Mandal), Vizianagaram Dist. – 535
005. Phone No. 08922-241111, 241112
E-Mail.: lendi_2008@yahoo.com Website: www.lendi.org
PSO1: Capable of design, develop, test, verify and implement electrical and electronics engineering
systems and products.
PSO2: Succeed in national and international competitive examinations for successful higher studies
and employment.
LENDI INSTITUTE OF ENGINEERING AND TECHNOLOGY(A)
(Approved by A.I.C.T.E & Permanently Affiliated to JNTUGV)
Accredited by NBA & NAAC with ‘A’ Grade
Jonnada (Village), Denkada (Mandal), Vizianagaram Dist. – 535
005. Phone No. 08922-241111, 241112
E-Mail.: lendi_2008@yahoo.com Website: www.lendi.org
COs PO1 PO2 PO3 PO4 PO5 PO6 PO7 PO8 PO9 PO10 PO11 PO12 PSO1 PSO2
CO1 2 2 3 3 3 2 2 2 2 2 1 3 3 3
CO2 2 2 - 3 - - - 2 3 3 - 2 - -
CO3 2 2 2 3 3 - - - - 2 1 2 3 3
CO4 2 2 3 2 3 2 2 - 2 2 1 3 3 3
CO5 2 2 3 2 2 - 1 2 2 3 1 3 3 3
CO* 2 2 3 3 3 2 2 2 2 2 1 3 3 3
Overall Pos & PSOs
mapped:PO1,PO2,PO3,PO4,PO5,PO6,PO7,PO8,PO9,PO10,PO11,PO12,PSO1,PSO2
CONTENT
CHAPTER 2:
MATHEMATICAL MODELLING
2.1 Derivation of swing equation 13-15
2.2 Mathematical modeling of lfc systems 15-17
2.3 Mathematical Modeling Of Lfc Systems 17-24
2.3.1 Mathematical modelling of generator 18-19
2.3.2 Mathematical modelling of load 19-20
2.3.3 Mathematical modelling for prime mover 20-21
2.3.4 Mathematical modelling for governor 21-24
CHAPTER 3:
INTRODUCTION TO CONTROLLERS
6.1 Conclusion 62
6.2 FUTURE SCOPE 62
APPENDIX 63
REFERENCES 64-67
ABSTRACT
This work intends to present Load Frequency Control in a multi-area Power System by
appreciating the performance of the methods in a single area power system. PID
controller, being the most widely used controller in industrial applications, needs
efficient methods to control the different parameters of the plant. The project work
undertaken aims at investigating the load frequency control problem in a power system
consisting of two power generation unit and multiple variable load units. As reported by
several researchers, the conventional approach of PID controller is not very efficient
due to the presence of non-linearity in the system of the plant. Also, the output of the
conventional PID system has a quite high overshoot and settling time. The main focus
of this work is to design the controller to obtain good output frequency responses
Obtain Fuzzy logic. The output response of proposed Fuzzy logic controller should
show better performance and be reasonably good over the conventional controllers.
Utilizes for load frequency control. The work is intended to carried out in
Matlab/Simulink.
i
LIST OF FIGURES
FIS editioi r
4.7
File section for Export To Workspace in FIS Editor 54
4.8
Rule Viewer 54
4.9
iii
CHAPTER 1
INTRODUCTION
4
1.1 INTRODUCTION TO POWER SYSTEM CONTROL
Electrical power is supplied to consume at permissible level of
voltage and frequency around the generator. As demand changes
system voltage and frequency changes from initial operating point,
causes changes in state of system and also effects performance of the
system.
Power system control means maintaining perfect power balance [1].
The main bifurcation between frequency and voltage in power system
is on the account of active and reactive power. The dependency of
frequency is on active power where as that of voltage is on the
reactive power. In order to perform voltage and frequency control,
usually alternators will have two control loops namely
Automatic voltage regulator loop (AVR)
Automatic load frequency control loop (ALFC) [2]
1.1.1AUTOMATIC VOLTAGE REGULATOR LOOP (AVR)
Generators utilized in power stations or standby power systems are
equipped with automatic voltage regulators (AVRs) to stabilize their
voltages amidst varying loads. While early AVRs were
electromechanical, modern versions incorporate solid-state devices for
enhanced performance. Operating as a feedback control system, the
AVR measures the generator's output voltage, compares it to a set
point, and generates an error signal to adjust the generator's excitation.
By manipulating the excitation current in the generator's field winding,
the AVR effectively controls the terminal voltage. In grid-connected
systems, changes in excitation predominantly impact the generator's
reactive power output rather than its terminal voltage, which is
primarily influenced by the power system. In parallel operation, AVRs
ensure all generators maintain consistent power factors to facilitate
seamless integration into the grid. Moreover, AVRs in power station
generators may feature additional control mechanisms to stabilize the
grid during sudden load fluctuations or faults. Strict limits are
imposed on system frequency variation due to several critical reasons.
Firstly, the speed of alternating current motors is directly proportional
5
to the power supply frequency, necessitating consistent frequency for
optimal motor performance. Secondly, synchronous electric clocks
rely on frequency stability for accurate timekeeping, with frequency
errors directly affecting clock precision. Additionally, turbine blades
in power plants are susceptible to damage if frequency falls below or
exceeds specific thresholds, highlighting the importance of
maintaining frequency within safe limits. Furthermore, prolonged
under-frequency operation can lead to reduced efficiency and
overheating in power transformers, particularly impacting thermal
power plants by diminishing fan blast and subsequently reducing
power generation. To mitigate these risks, load shedding techniques
are employed to restore frequency to desired levels by disconnecting a
portion of the load from generating units, thereby averting potential
power plant shutdowns.
6
In real power systems, there is some overlap between the
different forms of instability one phenomenon may lead to others and
as systems fail, more than one form of instability may ultimately
emerge. The change in frequency is sensed when the rotor angle delta
is changed. The error signals are transformed into real power
command signal, which is sent to prime mover to call for an increment
in the torque. The prime mover then brings change in the generator
output by an amount which will change the values within the specified
tolerance.
7
component. Thus, the steady-state frequency error in the system must
remain within acceptable values in order to maintain the equilibrium.
Possible increase in load reduces the nominal frequency of the system.
This frequency alternation is detected by a regulator in the primary
control loop. Thereafter, the speed of rotation of the turbine increases,
resulting in an increase in the power produced. Frequency deviations
can directly impact power system operation, system reliability and
efficiency. Large frequency deviations can damage equipment’s,
overload transmission lines, degrade load performance and adversely
affect the performance of system protection schemes. These large-
frequency deviation events can ultimately lead to a system collapse.
The load frequency control mainly deals with the control of the
system frequency and real power whereas the automatic Voltage
regulator loop regulates the changes in the reactive power and voltage
magnitude. Load frequency control is the basis of many advanced
concepts of the large scale control of the power system. In order to
design load frequency controllers to achieve high power quality
standards there is a need for data transmission over long distances [6].
8
where the main objective is to regulate the output power of each
generator at prescribed levels while keeping the frequency fluctuations
within pre-specified limits.
9
arbitrarily, on account of any little sudden load change in any of the
ranges, both area frequency and tie-line power stream trade
additionally shift. The fundamental objectives of Load Frequency
Control (LFC) are, to hold the frequency and the wanted power yield
in the interconnected power system at the planned qualities and to
control the adjustment in the tie-line power stream between control
ranges. Karun, D. Sindhu, T.K. [12] found that with the continually
expanding interest for force, ordinary vitality sources alone can't be
relied on for power generation. Disseminated renewable vitality power
system are recognized as a suitable option. However the irregular way
of these sources builds the frequency deviations which encourage add
to the deviations brought on by burden varieties. Consequently it is an
essential to keep the system frequency consistent. By actualizing
Load-frequency control (LFC), the frequency deviations can be
constrained. The principle point of the LFC in an interconnected force
framework is to keep the frequency deviations in the control ranges
inside of the pre-indicated limits and to keep up tie-line power streams
inside of as far as possible while obliging fluctuating burden requests.
Ravi B Kumar [13] observed that the parameters of PID controller
and inclination coefficient for Load Frequency Control (LFC) are
outlined utilizing another methodology. In the proposed technique, the
power system instabilities and nonlinear impediments of governors
and turbines, i.e. Valve Speed Limit(VSL) and Generation Rate
Constraint (GRC), are considered in planning. Varieties of
indeterminate parameters are considered between - 40% and +40% of
ostensible qualities with 5% stage to outline the proposed PID
controller, another target capacity is characterized. MATLAB codes
are produced for GA based PID controller tuning, the aftereffects of
which are utilized to think about the system step reaction. All these
are through in Simulink based foundation. YaikineKouba [14]
presented that portrays a use of Artificial Bee Colony (ABC) to load
frequency control (LFC) in single, two and multi-zone interconnected
power system. And the proposed ABC calculation is utilized to get the
ideal estimations of the corresponding fundamental inference (PID)
10
controller parameters based load frequency control (LFC). The
primary capacity of the LFC loop is to control the frequency and
reactive power. The principle point of this work is to smother every
one of the vacillations of the system because of the unsettling
influence and get back the frequency at ostensible worth. Keeping in
mind the end goal to break down the framework frequency and the tie-
line power stream with the changing of the load, the reproduction is
performed under load unsettling influences. Re-enactment results
indicated great execution as far as settling time and crest overshoot of
the proposed approach contrasted with the conventional Ziegler-
Nichols, Genetics Algorithm (GA), Particle Swarm Optimization
(PSO) and Bacterial Foraging Optimization (BFO) routines, and the
capacity of the proposed calculation to take care of burden recurrence
control issues under various aggravations is affirmed. El
KoubaYakine, Menaa,Hasni. Boudour [15] illustrated that in this
paper the ideal tuning of the Proportional Integral-Derivation (PID)
controller for both Load Frequency Control (LFC) and Automatic
Voltage Regulator (AVR) of two-range interconnected power system
utilizing Particle Swarm Optimization (PSO) calculation. The
dynamic and receptive forces are controlled independently. The LFC
loop controls the frequency and dynamic force and the AVR circle
alters the voltage and receptive force. So as to dissect the framework
recurrence, the tie line power stream, and the system voltage, the two-
range interconnected power system is mimicked for a stage load
aggravation in Area-1. Sreedhar.Allu. [16] Observed that a single
area power system is considered to investigate the better performance
of the fractional order PID (FOPID) controller compared to PID by
using root locus technique. And in the next step, the study is extended
to a three area or multi area thermal power system with non-linearity
of Generation Rate Constraint (GRC).(FOPID) controller is used to
improve the dynamic response of the system and the improved values
are tuned by using (BFOA) employing Integral Time multiplied
Absolute Error as an objective function. Then finally, the robustness
of proposed controller is investigated by introducing Transport Delay
11
(TD). J .Syaamala, I.E.S. Naidu [17] observed that Automatic
Generation Control (AGC) or Load Frequency Control is a very
important issue in power system. AGC is a feedback control system
for maintaining a generator yields power to remains defined frequency.
One of the objectives of AGC is to maintain the system frequency at
desired value and in the steady state performance of power system .An
extended power system can be divided into a number of load
frequency control areas interconnected by means of tie lines. Without
loss of generality one can consider a three- area case connected by tie
line. Here we are considering system, which is integration of two
thermal power systems with hydropower system.
12
system
13
In this case of two area powers system an assumption is taken that the
individual areas are strong and the tie line which connects the two
areas is weak. Here a single frequency is characterized throughout a
single area; means the network area is ‘strong’ or ‘rigid’. There may
be any numbers of control areas in an interconnected power system.
1.4 AIM AND OBJECTIVES
14
Chapter 5
This chapter deals with simulation and results of two area
interconnected power system with different controllers.
Chapter 6
15
CHAPTER 2
MATHEMATICAL MODELLING
16
2.1 LOAD FREQUENCY CONTROLAND MATHEMATICAL
MODELLING OF VARIOUS COMPONENTS
Suppose there are two generating stations that are connected to each
other by tie line. If the change in load is either at A or at B and the
generation of A is alone asked to regulate so as to have constant
frequency then this kind of regulation is called Flat Frequency
Regulation.
The other possibility of sharing the load the load is that both A and B
would regulate their generations to maintain the constant frequency.
This is called parallel frequency regulation.
17
frequency controller and a tie line recorder measuring the power input
on the tie as for the selective frequency control.
The error signal i.e. Δf and ΔPttie are amplified, mixed and
transformed to real power command signal ΔPV which is sent to the
prime mover to call for an increase in the torque. The prime mover
shall bring about a1 change in the generator output by an amount
ΔPgwhich will change the values of Δf and ΔP tie within the specified
tolerance. The first step to the analysis of the control system is the
mathematical modeling of the system’s various components and
control system techniques.
N-m (2.1)
Where
is the total moment of inertia of the rotor mass in kg-m2
18
is time in seconds s
(2.3)
The above equations show that the rotor angular speed is equal to the
synchronous speed only when dδm/dt is equal to zero. Therefore, the
term dδm/dt represents the deviation of the rotor speed from
synchronism in rad/s.
(2.4)
Substituting the above equation in the equation of rotor motion gives
19
N-m
(2.5)
Introducing the angular velocity ωm of the rotor for the notational
(2.6)
Normalizing it as
H= =
Where Srated is the two phase rating of the machine in MVA.
Substituting in the above equation
(2.7)
(2.8)
20
The above equation describes the behavior of the rotor dynamics and
hence is known as the swing equation. The angle δ is the angle of the
internal emf of the generator and it dictates the amount of power that
can be transferred. This angle is therefore called the load angle.
(2.9)
Where 'H' is the inertia constant in MJ/MVA, 'G' is the rating of the
machine in MVA ωsis the synchronous angular speed in rad/sec, ∆δ is
change in the rotor angle in rad, ∆PMand ∆PEare the change in
mechanical input power and electrical output power in MW
respectively
(2.10)
(2.11)
21
(2.12)
(2.13)
Where ΔPL is the non-frequency sensitive load change,
DΔω is the frequency sensitive load change.
D is expressed as per cent change in load by per cent change in
frequency measured in Watt/(rad/sec). Using equations (2.12) & (2.13),
transfer function model of load and generator can be formed and are
shown in Figures 2.2, 2.3 Figure 2.4 shows the simplified transfer
function model of combination of alternator and load.
22
Figure 2.2 Block diagram of load
23
(2.14)
Where τT, the turbine constant is, in the range of 0.2 to 2.0 seconds
24
The above speed governing system shown in Figure 2.6 consists of the
following essential parts as discussed below:
i. Speed governor: The main part of speed governing system is
centrifugal fly-ball that is driven directly or through gearing system
employed in the turbine shaft. Downward and upward motion of speed
governing system is directly proportional to change in speed of the
turbine.
ii. Linkage mechanism: As shown in Figure 7 there are four linkage
arms l1, l2, l3&l4and five linkage points A , B , C , D &E . l1&l2linkage
arms are stiffly coupled and also arms l3and l4. By the help of
hydraulic amplifier, linkage arms and linkage points the linkage
mechanism system gives movement to the turbine valve position
which is directly proportional to change in turbine shaft speed and
also that provides feedback through the turbine valve movement.
iii. Hydraulic amplifier: Large mechanical forces are necessary to
drive the water/steam valve against high water/steam pressure. These
forces are obtained in the process of various stages of hydraulic
amplifier.
iv. Speed changer: It comprises of vertical screw arrangement which
is driven by a servo motor and helps to move the linkage point ' A'
either up or down as per the requirement to supply electrical power at
nominal frequency.
Let small displacement of link point ' A' be ∆YA in downward
direction. This creates an upward movement of link point 'C' by ∆YC &
point 'D' by ∆YD and a downward movement of point 'E' by ' ∆YE.
Downward movement of link point 'E' causes the steam valve to open
which in turn increases the mechanical power output of the turbine as
a result electrical power output of alternator increases by an amount
∆PC. Now due to rise in ∆PC, speed and hence the frequency of
generator increases by an amount ∆f . Hence, it can be written as ∆YA=
kc∆PC where kc is proportionality constant.
25
Net upward movement of link point C is due to i. Initial downward
movement of link point ' A' by ∆YA and is given by ∆YC= -k1 ∆YA =-
k1kC ∆PC (Upward)
ii. Due to increase in speed, the link point 'B' moves downward and
hence link point C by k2∆f.
Therefore, net movement of link point C can be expressed as
∆YC =-k1kC∆PC+k2∆f (2.15)
Resultant movement of link point D depends on movement of link
points 'C'&'E' and is expressed as
∆YD=k3∆YC+k4∆YE (2.16)
The movement of link point E depends on quantity of pressurized oil
through pilot valve which is given by
(2.17)
Where,k1,k2,k3,k4&k5are proportionality constants.
Taking Laplace transform of both sides of equations (2.15-2.17)
and after simplifying for ∆YE we have
(2.18)
(2.19)
Where
26
characteristics. The transfer function model of speed governing
system is shown in Figure 2.7
Combining all the block diagrams from earlier block diagrams for a
single area system we get the following as shown in Figure 2.8
27
CHAPTER 3
INTRODUCTION TO
CONTROLLER
28
3.1 INTRODUCTION
Proportional controllers.
Integral controllers.
Derivative controller.
Proportional plus Integral controllers.
Proportional plus Derivative controllers.
Proportional plus Integral plus Derivative controllers.
Fuzzy logic controller
Sliding mode controller
ANFIS - Adaptive Neuro-Fuzzy Inference Systems
3.1.1 P CONTROLLER
29
We can use this controller only when our system is tolerable
to a constant steady state error. In addition, it can be easily concluded
that applying P controller decreases the rise time and after a certain
value of reduction on the steady state error, increasing K only leads to
overshoot of the system response. P control also causes oscillation if
sufficiently aggressive in the presence of lags and/or dead time. The
more lags (higher order), the more problem it leads. Plus, it directly
amplifies process noise.
Where is the adjustable controller gain and is the normal value of the
control signal, which is also be adjustable. In principle, is selected to
make the control error (t) = 0 at the nominal operation point.
3.1.2 PI CONTROLLER
30
error, it may lead to oscillatory response of slowly decreasing
amplitude or even increasing amplitude, both of which is usually
undesirable.
Where the gain and the integral time are adjustable parameters; 𝑢0 is
less important due to the integral.
3.1.3 PD CONTROLLER
31
of the output variable to prevent the sudden changes occurring in the
control output resulting from sudden changes in the error signal. In
addition D directly amplifies process noise therefore D-only control is
not used.
Where, the gain and the derivative time are adjustable parameters 𝑢0
is chosen as for a P controller
32
calculating and then outputting a corrective action that can adjust the
process accordingly .The PID controller calculation involves three
separate parameters the Proportional, the Integral and Derivative
values[19]. The Proportional value determines the reaction to the
current error, the Integral determines the reaction based on the sum of
recent errors and the Derivative determines the reaction to the rate at
which the error has been changing. In today’s control engineering
world and P-I-D is used over 95% of the control loops. Actually if
there is control, there is P-I-D, in analogue or digital forms. In order to
achieve optimum solutions Kp, Ki and Kd gains are arranged according
to the system characteristics. Conventional PID controllers are
characterized with simple structure and simple design procedures.
They enable good control performance and are therefore widely
applied in industry. However, in a number of cases, such as those
when parameter variations take place and/or when disturbances are
present, control system based on a fuzzy logic controller (FLC) may
be a better choice. The PID controller is a universal controller which
is used particularly in the field of material processing. Practical
controllers are usually assembled with one or more operational
amplifiers, whereby the PID behaviour is realized by suitable
feedbacks.
33
There are many tuning methods, but most common methods are as
follows:
34
An integral control () will have the effect of eliminating the steady-
state error, but it may make the transient response worse.
35
possible by pure proportional control. But one must be careful while
using derivative action in control of very fast processes, or if the
measurement is noisy (e.g. flow measurement).
36
loop system is also called automatic control system. The general block
diagram of an automatic control system is shown in Fig.3.5
37
The end device must be properly sized for the process. This implies all
parts of the system must be linearized to minimize variation in process
gain over the normal operating range of the process.
For our purposes, the synthesis method is best, we will briefly outline
by compare with the common trial-and-error method, Zeigler-Nichols
continuous cycling method, Cohen-Coon method, these approaches to
a process reaction method for PI control loop tuning methods, with
following demerits.
Continuous cycling is often objectionable because the process is
pushed to the limits of its stability. As such, if any external
disturbance enters the process while it is being tuned, the process
could run away with a highly unstable response. Also, it is possible to
damage equipment in some processes when operating at the stability
limits.
If you do not take the time to ensure all elements of the process and
control loop are properly configured, the time taken to tune the loop
will likely be wasted.
Given the transfer function of the components of a feedback
loop, synthesis the controller required to produce a specified closed-
loop components other than the controller have been lumped into
single block, G p(s).From the Fig 3.6 the transfer function of the closed
loop can be written as
39
40
CHAPTER 4
INTRODUCTION TO TWO AREA
INTERCONNECTED POWER
SYSTEM AND FUZZY LOGIC
CONTROLLER
41
4.1 INTRODUCTION TO TWO AREA INTERCONNECTED
POWER SYSTEM
42
by the primary speed control. Reaction period can be very low like 1
minute.
43
Ptie(1,2):Tie Line Power Deviation in Two Areas
a12 : Ratio of Rated Powers of a Pair of Areas in the Two Area System
44
intelligence systems specially to control complex aircraft engines and
control surfaces, helicopter control, missile guidance, automatic
transmission, wheel slip control, auto focus cameras and washing
machines ,railway engines for smoother drive and fuel consumption
and many industrial processes. Fuzzy logic provide better results if we
compared it with PID controller[21].Fuzzy set of theory represent the
human reasoning with knowledge that is almost impossible to
represent in quantitative measures or for that control plants that are
hard to control or ill defined .Fuzzy inference system model the
system using if-then rules. Fuzzy controller is an innovative
technology that modifies the design of systems with engineering
expertise.
45
high accuracy. As mentioned before fuzzy logic control is based on
linguistic definition of the system. These membership functions
convert the crisp values such as error value and changing of error
value into linguistic forms. So two input each with seven membership
function will make 7 multiply 7 = 49 rules in order to get accurate
value and efficiency. The gain coefficients were used in order to scale
the desired inputs and outputs within the range of membership
function’s range. According to the specification provided in fuzzy
controller as membership function range is between -1 to 1.
46
There are two famous type of system currently used in fuzzy logic
4.5.1 FUZZIFICATION
48
A collection of the expert control rules (knowledge) needed to
achieve the control goal. This process will perform fuzzy logic
operations and result the control action according to the fuzzy inputs.
4.5.3 DEFUZZIFICATION
49
The required algorithm for load frequency fuzzy control can be
summarized as follows.
ACE/ LN MN SN Z SP MP LP
ACE*
LN LP LP LP MP MP SP Z
MN LP MP MP MP SP Z SN
SN LP MP SP SP Z SN MN
Z MP MP SP Z SN MN MN
SP MP SP Z SN SN MN LN
MP SP Z SN MN MN MN LN
LP Z SN MN MN LN LN LN
50
For the case of two-input and one output, the control rules can be
shown graphically in a table when every cell shows the output
membership functions of a control rule with the relationship between
input 1 and 2. The control rules build from the if-then statement (if
input 1 and input 2 then output 1). Table 4.1 indicates the appropriate
rule bases in this study. Let us consider the third row and fourth
column in Table 4.1, that means, if ACE is SN and ACE * is Z then y is
SP
There are five primary graphical user interface (GUI) tools for
building, editing and observing fuzzy inference systems in the toolbox:
i. Fuzzy Inference System (FIS) editor
ii. Membership Function editor
iii. Rule Editor
iv. Rule Viewer
v. Surface Viewer
These GUI are dynamically linked and if the changes make to the FIS
to one of the toolbox, the effect can be seen in other GUIs.
The FIS editor handles the high level issues of the system.
Fuzzy Logic toolbox does not limit the FIS editor displays general
51
information about fuzzy inference system. FIS editor can be open as
steps shown below:
Step 1: Type fuzzy at MATLAB prompts and enters.
52
Step 5: Click output (green box and highlighted with red outline)
53
Figure 4.9 Surface viewer
54
CHAPTER 5
55
5.1 POWER SYSTEM MODEL USING DIFFERENT
CONTROLLERS
Figure 5.1 Simulink model of two area power system using PID
controller
The gain value of different type of controllers using in two area power
systems is given in table 5.1
56
Table 5.1: Different values of gain for different controllers
Controll KP Ki Kd Settlin
er Area1 Area2 Area1 Area2 Area1 Area g time
2 (sec)
I - - 0.274 0.468 - - 35
2 0
PI 0.110 0.012 0.274 0.201 - - 25
9 1 2 9
PID 0.110 0.012 0.274 0.201 0.111 0.003 10
9 1 2 9 0
57
Figure 5.4 Output response of tie line power system with I
58
Figure 5.7 Output response of tie line power system with PI
59
Figure 5.10 Output response of tie line power system with PID
of
60
5.12 Combined output response of tie line power system
61
Figure 5.14 Output response of area 1 with fuzzy controller
62
Figure 5.17 Output response of tie line power system
with fuzzy controller
63
CHAPTER 6
CONCLUSION AND
FUTURE SCOPE
64
6.1 CONCLUSION
65
APPENDIX
In the following, most of the parameters of the two-area
interconnected power system in Fig. 4.1 are from Refs [12,13] and
some parameters have been modifiedR1 = R2 = 2.4 Hz/p.u. Tp1 = Tp2
= 20s, K p1 = K p2 =120 Hz/p.u., a12 = −1 , B1 = B2 = 0.425 ,
T12=0.086 , Tt1=Tt2=0.3s.
66
REFERENCES
[1] Kundur, P.:'Power system stability and control',McGraw Hill, New
York, 1994.
[7] Pan,C. T. and liaw, C. M., "An adaptive controller for power
system load-frequency control", IEEE Trans.on Power Systems, Vol.
4, No. 1, pp. 122-128, 1989.
67
[10] Abdel-Magid, Y.L. and Dawoud, M.M., "Genetic Algorithms
Applications In Load Frequency Control", Genetic algorithms in
engineering systems: innovations and applications, 12-14 September
1995, conference publications No. 414, IEE, 1995.
[11]YakineKouba, N.E.L. ;Menaa, M. ; Hasni, M. ; Boudour, M. Load
Frequency Control in multi-area power system based on Fuzzy Logic-
PID Controller Published in: Smart Energy Grid Engineering (SEGE),
2015 IEEE International Publication on Date of Publication:17-19
Aug. 2015 Page(s):1 – 6.
[12] Karun, D. Sindhu, T.K. Fuzzy logic based load frequency control
of grid connected distributed generator Published in: Advancements in
Power and Energy (TAP Energy), 2015 International Publication on
Date of Publication: 24-26 June 2015 Page(s): 432 – 437.
68
[17] J .Syamala, I.E.S. Naidu “Load Frequency Control of MultiArea
Power Systems Using PI, PID, and Fuzzy Logic Controlling
Techniques” IJIRSET volume 3,ICETS'14 published on February 2014
69