Calculation of Room Pressure for CLEANROOMS

Room Dimensions in feet


Length 13.5 Feet
Width 17 Feet
Height 9 Feet

Room volume 2065.5 cu. ft.


Assuming Atmospheric pressure, Patm = 101.325 kPa
Air changes per hour ACH 40
Room pressure need to maintain 55 Pa 0.055

Supply Air SA 1377 cfm

Total pressure 101.38 kPa

Total additional room air volume requires: 2066.6211695 cu. ft.

Additional air volume requires pressurizing room up to


required pressure (without leakage): 1.1211695041 cu. ft.

With 5% leakage consider 1.1772279793 cu. ft. Additional air volum

If we require pressurizing the room within second: 1 sec


Total additional air flow (PA) / Fresh Air intake 70.63367876 cfm

Total supply Air SA 1447.63 cfm


Total Return Air RA 1377.00 cfm