Download as pdf or txt
Download as pdf or txt
You are on page 1of 67

SHORT CIRCUIT

CALCULATIONS
Sammy E. Dumaya, PEE
IIEE-SQC Technical Seminar 2016
Qatar Bowling Center (QBC),
Doha, State of Qatar
01st April, 2016

Page 1
Theme : “IIEE : Soaring High Towards Globalization” :
Index
I Objective
II Reference Standards
III Purpose of Short Circuit Studies
IV Type of Short Circuit Faults
V Electrical System Grounding
VI Symmetrical & Asymmetrical Faults
VII Method of Short Circuit Calculation
VIII Short Circuit Calculations
IX Electrical Component Sizing

Page 2
I. OBJECTIVE

Page 3
I. Objective
The objective of this seminar is to uphold the technical
know how of our Filipino Electrical Practitioners in the
State of Qatar to hone their proficiency and professional
competence to be globally competitive.

On completion of this seminar, the participants shall be


able to:
• Explain the significance of Short Circuit
• Explain the Cause and Consequences of Short Circuit
• Classify different types of Faults
• Know the short circuit calculation methods
• Compute currents for Symmetrical & Asymmetrical Faults
• Select suitable ratings of electrical components

Page 4
What is Short Circuit ???
A faulty or accidental connection between two points of
different potential in an electric circuit, bypassing the
load and establishing a path of low resistance through
which an excessive current can flow. It can cause damage
to the components if the circuit is not protected.

Page 5
II. REFERENCE STANDARDS

Page 6
II. Reference Standards
• IEC 60909 : Short-circuit currents in a 3 Phase AC System
• IEC 60076 : Power Transformers
• IEC 60034 : Rotating Electrical machines
• IEC 60947 : LV Switchgear & Controlgear,
Part 2 : Circuit Breakers
• IEC 62271 : HV Switchgear & Controlgear -
Part 100 : HV Alternating Current C.B.
• IEC 60287 : Electric Cables Calc. of current rating
• IEEE 399 : Recommended Practice for Industrial
& Commercial Power Systems Analysis
• IEEE 141 : Recommended Practice for Electric Power
Distribution for Industrial Plants

Page 7
III. PURPOSE OF SHORT CIRCUIT
STUDIES

Page 8
III-a. Purpose of Short Circuit Studies

The purpose of Short Circuit Studies can be used to


determine any or all of the following:

• Verify protective device close and latch capability


• Verify protective device interrupting capability
• Protect equipment from large mechanical forces
(maximum fault kA)
• Select the electrical system components to withstand
thermal stresses
• Selecting ratings or settings for relay coordination

Page 9
III-b. CAUSES OF SHORT CIRCUIT

Page 10
III-b. Causes of Short Circuit

• Over voltages : Caused by Lightning or


Switching surges
• Insulation breakdown : Overloading, high temp.
• Insulation contamination : Salt spray, pollution
• Mechanical causes : Over heating, vibration,
abrasion
• Grounding connectivity : Improper grounding
connection, high resistance
to ground

Page 11
III-c. Faults on Equipment & other elements
Faults on Transmission & Distribution Lines:
• Most common : Lines are exposed to elements of nature
• Lightning strokes : Over voltages causes insulators to flash
causing line to ground SC or L-L SC
• High winds : Topple tower, tree falls on line
• Salt spray, dirty insulation : conduction path, insulation failure

Page 12
III-d. Faults on Equipment & other elements
Short circuits in other elements:
• Cables
• Circuit breakers
• Generators, motors, transformer, etc
• Overloading for extended periods, deterioration of
insulation, mechanical contribution

Page 13
III-e. Consequences of Short Circuits

• Currents of several magnitude larger than normal


operating current
• Thermal damages to equipment
• Windings and Busbar : Mechanical damage due to
high magnet forces caused by high current.

Page 14
III-f. Consequences of Short Circuits

ABB Oryx Workshop in


Ras Laffan Industrial City
(RLIC)

Early detection of:


- Motor insulation breakdown
- NDE bearing worn out

Sea Water Pump Motor


4000 kW, 6.6kV
Page 15
III-g. Spectrum of Currents

LOAD CURRENT
• Up to 100% of full load
• 115-125% (mild overload)

OVERCURRENT
• Abnormal loading condition (locked-rotor)

FAULT CURRENT
• Fault condition
• 10x the full load current and higher

Page 16
III-h. System Components Involved
in Short Circuit Calculations
• Power Utility Company
• Plant Generators
• Transformers
• Reactors
• Feeder Cable Systems
• Synchronous Motors
• Induction Motors
• Protective Devices

Page 17
III-i. Elements that Contribute Current
to a Short Circuit

• Power Grid
• Generators
• Synchronous Motors fault
• Induction Motors

Page 18
III-j. Short Circuit Values from Power Grid

TECHNICAL QUERY

PLANT NAME

Source 3Ph Fault 3Ph Fault L-G Fault L-G Fault


Switchboard Voltage
Substation Tag Current (kA) Current (kA) Current (kA) Current (kA) X/R Ratio
Tag no. (kV)
no. Max Min Max Min

RPB-XXX SB-XXX 33

Page 19
III-k. Short Circuit Level as per Kahramaa
Regulation

Page 20
IV. TYPE OF SHORT CIRCUIT FAULTS

Page 21
IV-a. Type of Short Circuit Faults

Three Phase Fault Phase to Phase Fault

2 Phase to Earth Fault 1 Phase to Earth Fault


Page 22
IV-b. Fault Current
• IL-G can range in utility systems from a few percent
to possibly 115 % ( if Xo < X1 ) of I3-phase (85% of all
faults).

• In industrial system the situation IL-G > I3-phase is rare.


Typically IL-G = 0.87 * I3-phase.

• In an industrial system, the three-phase fault


condition is frequently the only one considered, since
this type of fault generally results in Maximum fault
current.

Page 23
IV-c. Sources & Models of Fault Current
Synchronous Generators
Synchronous Generators are modeled in three stages.

Synchronous Motors & Condensers


Act as a generator to supply fault current. This current
diminishes as the magnetic field in the machine decays.

Induction Machines
Treated the same as synchronous motors except they do
not contribute to the fault after 2 sec.

Electric Utility Systems


The fault current contribution tends to remain constant.
Page 24
IV-d. Sources & Models of Fault Current
½ Cycle Network
This is the network used to calculate momentary short-
circuit current and protective device duties at the ½
cycle after the fault.

1 ½ to 4 Cycle Network
This network is used to calculate the interrupting short-
circuit current and protective device duties 1.5-4 cycles
after the fault.

30-Cycle Network
This is the network used to calculate the steady-state
short-circuit current and settings for over current relays
after 30 cycles.
Page 25
IV-e. AC Fault Current (Symmetrical) with:

AC Fault Current without Decay

DC Current Decay

Page 26
IV-f. AC Fault Current including the DC Offset

AC Current + Idc (Offset current)


Page 27
IV-g. Short Circuit near to Generator
This is a short-circuit condition to which at least one synchronous
machine contributes a prospective initial short-circuit current
which is more than twice the generator’s rated current, or a short-
circuit condition to which synchronous and asynchronous motors
contribute more than 5% of the initial symmetrical short-circuit
current ( I"k) without motors.

Page 28
IV-h. Short Circuit far from Generator
This is a short-circuit condition during which the
magnitude of the symmetrical ac component of
available short-circuit current remains essentially
constant.

Page 29
IV-i. 3-Phase SC on Synchronous Machine

Where:
o-c = Peak value of Sub-transient SC current
o-b = Peak value of Transient SC current
o-a = Peak value of Steady State SC current
Page 30
V. ELECTRICAL SYSTEM GROUNDING

Page 31
V-a. System Grounding
In electricity supply systems, a grounding
system is circuitry which connect parts of
the electric circuit with the ground, thus
defining the electric potential of the
conductors relative to the Earth's conductive
surface.

The choice of grounding system it affects the


magnitude and distribution of short circuit
currents through the system, and the effects
it creates on equipment and people in the
proximity of the circuit.

Page 32
V-b. System Grounding

There are five (5) types of System grounding:

a) Solidly grounded neutral


b) Ungrounded neutral
c) Resistance grounded neutral
• Low resistance grounding
• High resistance grounding
d) Reactance grounded neutral
e) Grounding transformer

Page 33
V-c. System Grounding

SOLIDLY GROUNDED NEUTRAL


C
The solidly grounded system is
the most common system
arrangement and one of the A

most versatile. The most


commonly used configuration B
is the solidly grounded wye,
N
because it will support single
phase loads.

Page 34
V-d. System Grounding
UN GROUNDED NEUTRAL

In ungrounded, isolated or
floating neutral system, as in
the IT system, there is no direct
connection of the star point (or
any other point in the network)
and the ground. As a result,
ground fault currents have no
path to be closed and thus
have negligible magnitudes.

Page 35
V-e. System Grounding
RESISTANCE EARTHED NEUTRAL
C
Resistance grounding systems
are used in industrial electrical
power distribution facilities to A
limit phase-to-ground fault
currents.
The system basically utilized B
Neutral Grounding Resistor
(NGR).

• High resistance grounding : 5-10A


• Low resistance grounding : 200-400A

Page 36
V-f. System Grounding

REACTANCE GROUNDED
NEUTRAL C

Reactance grounding is
commonly used in the A

neutrals of generators. X
Grounding of the generator
neutral through an air core B

reactance is the standard


solution for lowering the
ground fault level.

Page 37
V-g. System Grounding

GROUNDING TRANSFORMER

The Zig-Zag transformer is


use to create a neutral
reference for an ungrounded
system. Most instances
involve existing ungrounded
systems which are being
upgraded to high–resistance
grounding.

Zig-Zag grounding
transformer
Page 38
VI. SYMMETRICAL AND ASYMMETRICAL
FAULTS

Page 39
VI-a. Symmetrical & Asymmetrical Faults
• Symmetrical or Balanced Fault
- Three Phase Fault

• Asymmetrical or Unbalanced Faults


- Phase to Phase Fault
- Two Phase to Ground Fault
- Single Phase to Ground Fault

Page 40
VI-b. Short Circuit Phenomenon

One Line Diagram in Power Station

Equivalent Impedance Diagram


Page 41
VI-c. Short Circuit Phenomenon

Thevenin’s Equivalent Diagram

Solving equation 1 yields the following expression:

Page 42
VI-d. Symmetrical Components

Symmetrical Components

Page 43
VI-e. Sequence Networks

Sequence Networks

Page 44
VI-f. Asymmetrical Faults

L-G Fault Sequence Network Connections

Page 45
VI-g. Asymmetrical Faults

L-L Fault Sequence Network Connections

Page 46
VI-h. Asymmetrical Faults

L-L-G Fault Sequence Network Connections

Page 47
VI-i. Transformer Zero Sequence Connections

Page 48
VII. METHOD OF SHORT CIRCUIT
CALCULATIONS

Page 49
VII-a. Per Unit Method (SC Formulas)
KVA BASE
A) I BASE 
3 x KVBASE

KV 2 BASE
B) Z BASE  x 1000
KVA BASE

KVA BASE
C ) Z PU  Z ACTUAL x
KV 2 BASE x1000

I BASE
D) I SC 
Z PU

MVA SC
E ) I SC 
3 xKV 2
2
 KV   KVABASE  NEW 
F ) Z PU  NEW  Z PU OLD x  BASE OLD  x  
 BASE  NEW  
KV KVABASE OLD 

Page 50
VIII. SHORT CIRCUIT CALCULATIONS

Page 51
VIII-a. Short Circuit Calculations

In short circuit, there is a structural change in


network – addition of an impedance (Zf = fault
impedance, zero for solid short circuit) at the point of
fault.

The change in voltage or current resulting from this


structural network change can be analyzed using
Thevenin’s theorem.

Page 52
VIII-b. Thevenin’s Theorem

The changes in network voltages and currents due to


the addition of an impedance between two point of a
network are identical with those voltages and
currents that would be caused by placing an emf,
having a magnitude and polarity equal to the pre-
fault voltage between the nodes, in series with the
impedance with all other voltage sources being
zeroed.

Post fault voltages and currents are computed by


super imposing these changes on pre-fault voltages
and currents.

Page 53
VIII-c. Thevenin’s Theorem

Single Line Diagram

Before the Fault After the Fault


Page 54
VIII-d. Thevenin’s Theorem

Thevenin’s Equivalent Circuit


Page 55
VIII-e. Per Unit Method –
Sequence of Fault Current Calculations

Step 1 : Draw the Single Line Diagram


Step 2 : Select suitable KVA and KV bases
Step 3 : Calculate the base quantities for Current (I)
and Impedance (Z)
Step 4 : Draw the equivalent Impedance Diagram or
Positive Reactance Diagram
Step 5 : Define the Fault locations
Step 6 : Perform Short Circuit Calculations
(with Symmetrical and Asymmetrical faults)

Page 56
VIII-f. Short Circuit Calculations

Single Line Diagram

Positive Sequence Reactance Diagram


Page 57
VIII-g. Asymmetrical Faults

Single Phase to Ground Fault Vf


I a1 
Z1  Z 2  Z 0

Vf
Two Phase Fault I a1 
Z1  Z 2

Vf
Two Phase to Ground Fault I a1 
Z1  Z 2 Z 0 / ( Z 2  Z 0 )

Page 58
VIII-h. Short Circuit Calculations

• Initial Symmetrical Short Circuit Current (I”k)


c x Un
I "k 
3 x Z "k
• Peak Short Circuit Current (I’k)
c x Un
I 'k 
3 x Z 'k
• Steady State Short Circuit Current (Ik)
c x Un
Ik 
3 x Zk
Where :
C : Voltage Factor (refer to IEC-60909 - Table 1)
Un : Line to Line Voltage (V)
Zk : Short Circuit Impedance (Ohms)
Page 59
VIII-i. IEC-60909 : Table 1 Voltage Factor C
Nominal Voltage Factor C for calculating
Per UnitVoltage
Method:
The max. SC The min. SC
current [Cmax] current [Cmin]
LOW VOLTAGE
100V to 1000V
(see IEC 60038, Table I)
a) Voltage tolerance +6% 1.05 0.95
b) Voltage tolerance +10% 1.10 0.95
MEDIUM VOLTAGE
>1 kV to 35 kV 1.10 1.00
(see IEC 60038, Table III)
HIGH VOLTAGE
>35 kV 1.10 1.00
(see IEC 60038, Table IV)

Page 60
IX. CIRCUIT BREAKER SIZING

Page 61
IX-a. Circuit Breaker (CB) Sizing

From the view point of current under steady state


and short circuit condition, the following factors
shall be considered in selecting circuit breaker size:

• CB Breaking Capacity (Ib)


- The total current when the breaker contacts
open to interrupt the circuit.

• CB Making Capacity (Im)


- The maximum instantaneous current which the
breaker must withstand.

Page 62
IX-b. Selection of CB Breaking Capacity (Ib)

The circuit breaker interrupting current depends


on the interruption time of the circuit breakers
and is obtained by multiplying the sub-transient
AC short circuit current (I”k) by the multiplying
factors given in Table 2.

I b  I "k x m
Where :
Ib : CB Breaking Capacity (kA)
I”k : Sub-transient fault current (kA)
m : CB interrupting speed factor

Page 63
IX-c. Selection of CB Breaking Capacity (Ib)

Table 2: CB interrupting speed between 2-8 cycles to


take care the relay and CB opening time (IEC).

CB speed Multiplying factor (m)


8 cycles or slower 1.1
5 cycles 1.1
3 cycles 1.2
2 cycles 1.4

For CB’s having short circuit MVA greater than


500MVA the multiplying factors are increased by 0.1.

Page 64
IX-d. Selection of CB Making Capacity (Im)

The maximum momentary current is found by


calculating the AC short circuit current using the
sub-transient impedances of the generators and
motors and then multiplying it by the coefficient “n”
factor given in Table 1 as referred from IEC 60947-2.

I m  I "k x n
Where :
Im : CB Making Capacity (kA)
I”k : Sub-transient fault current (kA)
n : Value of coefficient “n”

Page 65
IX-e. Selection of CB Making Capacity (Im)

Page 66
Thank You..

Page 67

You might also like