Professional Documents
Culture Documents
Short Circuit Calc Presentation - IIEE SQC Techl Seminar 1-Apr-16
Short Circuit Calc Presentation - IIEE SQC Techl Seminar 1-Apr-16
CALCULATIONS
Sammy E. Dumaya, PEE
IIEE-SQC Technical Seminar 2016
Qatar Bowling Center (QBC),
Doha, State of Qatar
01st April, 2016
Page 1
Theme : “IIEE : Soaring High Towards Globalization” :
Index
I Objective
II Reference Standards
III Purpose of Short Circuit Studies
IV Type of Short Circuit Faults
V Electrical System Grounding
VI Symmetrical & Asymmetrical Faults
VII Method of Short Circuit Calculation
VIII Short Circuit Calculations
IX Electrical Component Sizing
Page 2
I. OBJECTIVE
Page 3
I. Objective
The objective of this seminar is to uphold the technical
know how of our Filipino Electrical Practitioners in the
State of Qatar to hone their proficiency and professional
competence to be globally competitive.
Page 4
What is Short Circuit ???
A faulty or accidental connection between two points of
different potential in an electric circuit, bypassing the
load and establishing a path of low resistance through
which an excessive current can flow. It can cause damage
to the components if the circuit is not protected.
Page 5
II. REFERENCE STANDARDS
Page 6
II. Reference Standards
• IEC 60909 : Short-circuit currents in a 3 Phase AC System
• IEC 60076 : Power Transformers
• IEC 60034 : Rotating Electrical machines
• IEC 60947 : LV Switchgear & Controlgear,
Part 2 : Circuit Breakers
• IEC 62271 : HV Switchgear & Controlgear -
Part 100 : HV Alternating Current C.B.
• IEC 60287 : Electric Cables Calc. of current rating
• IEEE 399 : Recommended Practice for Industrial
& Commercial Power Systems Analysis
• IEEE 141 : Recommended Practice for Electric Power
Distribution for Industrial Plants
Page 7
III. PURPOSE OF SHORT CIRCUIT
STUDIES
Page 8
III-a. Purpose of Short Circuit Studies
Page 9
III-b. CAUSES OF SHORT CIRCUIT
Page 10
III-b. Causes of Short Circuit
Page 11
III-c. Faults on Equipment & other elements
Faults on Transmission & Distribution Lines:
• Most common : Lines are exposed to elements of nature
• Lightning strokes : Over voltages causes insulators to flash
causing line to ground SC or L-L SC
• High winds : Topple tower, tree falls on line
• Salt spray, dirty insulation : conduction path, insulation failure
Page 12
III-d. Faults on Equipment & other elements
Short circuits in other elements:
• Cables
• Circuit breakers
• Generators, motors, transformer, etc
• Overloading for extended periods, deterioration of
insulation, mechanical contribution
Page 13
III-e. Consequences of Short Circuits
Page 14
III-f. Consequences of Short Circuits
LOAD CURRENT
• Up to 100% of full load
• 115-125% (mild overload)
OVERCURRENT
• Abnormal loading condition (locked-rotor)
FAULT CURRENT
• Fault condition
• 10x the full load current and higher
Page 16
III-h. System Components Involved
in Short Circuit Calculations
• Power Utility Company
• Plant Generators
• Transformers
• Reactors
• Feeder Cable Systems
• Synchronous Motors
• Induction Motors
• Protective Devices
Page 17
III-i. Elements that Contribute Current
to a Short Circuit
• Power Grid
• Generators
• Synchronous Motors fault
• Induction Motors
Page 18
III-j. Short Circuit Values from Power Grid
TECHNICAL QUERY
PLANT NAME
RPB-XXX SB-XXX 33
Page 19
III-k. Short Circuit Level as per Kahramaa
Regulation
Page 20
IV. TYPE OF SHORT CIRCUIT FAULTS
Page 21
IV-a. Type of Short Circuit Faults
Page 23
IV-c. Sources & Models of Fault Current
Synchronous Generators
Synchronous Generators are modeled in three stages.
Induction Machines
Treated the same as synchronous motors except they do
not contribute to the fault after 2 sec.
1 ½ to 4 Cycle Network
This network is used to calculate the interrupting short-
circuit current and protective device duties 1.5-4 cycles
after the fault.
30-Cycle Network
This is the network used to calculate the steady-state
short-circuit current and settings for over current relays
after 30 cycles.
Page 25
IV-e. AC Fault Current (Symmetrical) with:
DC Current Decay
Page 26
IV-f. AC Fault Current including the DC Offset
Page 28
IV-h. Short Circuit far from Generator
This is a short-circuit condition during which the
magnitude of the symmetrical ac component of
available short-circuit current remains essentially
constant.
Page 29
IV-i. 3-Phase SC on Synchronous Machine
Where:
o-c = Peak value of Sub-transient SC current
o-b = Peak value of Transient SC current
o-a = Peak value of Steady State SC current
Page 30
V. ELECTRICAL SYSTEM GROUNDING
Page 31
V-a. System Grounding
In electricity supply systems, a grounding
system is circuitry which connect parts of
the electric circuit with the ground, thus
defining the electric potential of the
conductors relative to the Earth's conductive
surface.
Page 32
V-b. System Grounding
Page 33
V-c. System Grounding
Page 34
V-d. System Grounding
UN GROUNDED NEUTRAL
In ungrounded, isolated or
floating neutral system, as in
the IT system, there is no direct
connection of the star point (or
any other point in the network)
and the ground. As a result,
ground fault currents have no
path to be closed and thus
have negligible magnitudes.
Page 35
V-e. System Grounding
RESISTANCE EARTHED NEUTRAL
C
Resistance grounding systems
are used in industrial electrical
power distribution facilities to A
limit phase-to-ground fault
currents.
The system basically utilized B
Neutral Grounding Resistor
(NGR).
Page 36
V-f. System Grounding
REACTANCE GROUNDED
NEUTRAL C
Reactance grounding is
commonly used in the A
neutrals of generators. X
Grounding of the generator
neutral through an air core B
Page 37
V-g. System Grounding
GROUNDING TRANSFORMER
Zig-Zag grounding
transformer
Page 38
VI. SYMMETRICAL AND ASYMMETRICAL
FAULTS
Page 39
VI-a. Symmetrical & Asymmetrical Faults
• Symmetrical or Balanced Fault
- Three Phase Fault
Page 40
VI-b. Short Circuit Phenomenon
Page 42
VI-d. Symmetrical Components
Symmetrical Components
Page 43
VI-e. Sequence Networks
Sequence Networks
Page 44
VI-f. Asymmetrical Faults
Page 45
VI-g. Asymmetrical Faults
Page 46
VI-h. Asymmetrical Faults
Page 47
VI-i. Transformer Zero Sequence Connections
Page 48
VII. METHOD OF SHORT CIRCUIT
CALCULATIONS
Page 49
VII-a. Per Unit Method (SC Formulas)
KVA BASE
A) I BASE
3 x KVBASE
KV 2 BASE
B) Z BASE x 1000
KVA BASE
KVA BASE
C ) Z PU Z ACTUAL x
KV 2 BASE x1000
I BASE
D) I SC
Z PU
MVA SC
E ) I SC
3 xKV 2
2
KV KVABASE NEW
F ) Z PU NEW Z PU OLD x BASE OLD x
BASE NEW
KV KVABASE OLD
Page 50
VIII. SHORT CIRCUIT CALCULATIONS
Page 51
VIII-a. Short Circuit Calculations
Page 52
VIII-b. Thevenin’s Theorem
Page 53
VIII-c. Thevenin’s Theorem
Page 56
VIII-f. Short Circuit Calculations
Vf
Two Phase Fault I a1
Z1 Z 2
Vf
Two Phase to Ground Fault I a1
Z1 Z 2 Z 0 / ( Z 2 Z 0 )
Page 58
VIII-h. Short Circuit Calculations
Page 60
IX. CIRCUIT BREAKER SIZING
Page 61
IX-a. Circuit Breaker (CB) Sizing
Page 62
IX-b. Selection of CB Breaking Capacity (Ib)
I b I "k x m
Where :
Ib : CB Breaking Capacity (kA)
I”k : Sub-transient fault current (kA)
m : CB interrupting speed factor
Page 63
IX-c. Selection of CB Breaking Capacity (Ib)
Page 64
IX-d. Selection of CB Making Capacity (Im)
I m I "k x n
Where :
Im : CB Making Capacity (kA)
I”k : Sub-transient fault current (kA)
n : Value of coefficient “n”
Page 65
IX-e. Selection of CB Making Capacity (Im)
Page 66
Thank You..
Page 67