Switchgears (India) Pvt. Ltd.

WORKS : 36,SUBHALAXMI IND. ESTATE, VILL. MORAIYA, SARKHEJ-BAVALA HIGHWAY,


TAL. SANAND, AHMEDABAD - 382210.. TELE./FAX : 02717-645195,96/251160
An ISO 9001-2015
E-MAIL : design@swatiswitchgears.com, WEB. : www.swatiswitchgears.com

19/05/2020
0 1 2 3 4 5 6 7 8 9

LEGEND DETAILS:-
A
x1
1) -H1 R-PHASE INDICATION LAMP (RED) 16) -XPT,X2,X3,X5 CONTROL TERMINALS 31) P1 DIGITAL VOLTMETER
x2
x1
2) -H2 Y-PHASE INDICATION LAMP (YELLOW) -XT1
17) C.T. SHORTING TERMINALS 32) P2 DIGITAL AMMETER
x2
x1 s1
3) -H3 B-PHASE INDICATION LAMP (BLUE) 18) -CT CURRENT TRANSFORMER 33) P3 DIGITAL MULTI FUNCTION METER
x2 s2
x1
PT
4) -H4 ON INDICATION LAMP (RED) 19) POTENTIAL TRANSFORMER 34) K51 IDMT NUMERICAL PROTECTION RELAY
B
x2
x1
5) -H5 OFF INDICATION LAMP (GREEN) 20) -H HOOTER 35) K86 MASTER TRIP RELAY
x2
x1
6) -H6 TRIP INDICATION LAMP (AMBER) R3,R94 AUXILARY RELAY 36) ANN. ANNUNCIATOR WINDOW
21)
x2
x1
7) -H7 TCH INDICATION (YELLOW) 22) -SW SWITCH 37) SA SURGE ARRESTOR
x2
x1
C 8) -H8 23) -TH THERMOSTAT 38) K631-10 TRAFO FAULT AUX. RELAY
SPRING CHARGE INDICATION LAMP (BLUE)
x2
x1
9) -H9 TEST POSITION INDICATION LAMP (WHITE) 24) -SH SPACE HAEATER
x2
x1
SERVICE POSITION INDICATION LAMP x1 x2
10) -H10 25) -PL PANEL LIGHT
x2
(YELLOW)
HTF
E1-E3 1
11) 1 2 HT FUSE 26) EARTHING

D
S6 2
T -PS
12) N TNC SWITCH 27)
POWER PACK
C
B

S5 B F2-F6
6A
DP MCB
13) L R LOCAL/REMOTE SELECTOR SWITCH 28) 1 3
A1 A2 DP MCB FOR AUX. SUPPLY
2 4
E

-FDC
10A
DP MCB
SA SURGE ARRESTOR 29) 1 3
14)
DP MCB FOR DC SUPPLY
2 4

-FAC -F1, F01


16A
DP MCB
1 3 5 7
15) 1 3
30)
DP MCB FOR AC SUPPLY FP MCB
2 4 2 4 6 8
F

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 2
ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. LEGENDS DETAILS Current Page 1
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

-Q0 -Q1
A

B1 B4 B7 B10 B13 B15 C3 C5 C6 A3 A5 A13 A1 D15 D1 D3 D5 D7 D9 D11

CLOSE IN SERVICE POSITION


S91 S93 S94
1 1 1

R Y B 4 4 4
B

S41
1
S2
1
2

2
9
S2 -V1
R3 R1
10 U1

S10 S2 -M1
M
1 3 5 1R 9R 3R 11R 5R 13R 7R 15R 9B 1B 3B 5B 7B 13
11B 1~
-Q52 R4

CLOSE IN TEST POSITION


C
33kV 2R 10R 4R 12R 6R 14R 8R 16R 10B 2B 4B 6B 8B 14 U2
VCB 2 4 6 12B
RECT
S2 S92 S95 S96
C1 4 1 1 1

F2.
C2 3 4 4 4
C1
F11.
C2 15
S2
16

D S43
R Y B 1

B2 B3 B5 B6 B8 B9 B11 B12 B14 B16 C4 A4 A6 A14 A2 D16 D2 D4 D6 D8 D10 D12

NOTE :- THIS CIRCUIT DIAGRAM SHOWS THE BASIC AND ALSO SOME OPTIONAL SWITCHGEAR LV EQUIPMENT POSSIBLE,SOME ITEM CAN BE INCLUDED
Q0 - UNITS INCORPORATED IN THE CB Q1 - UNITS INCORPORATED IN THE RACKING TROLLEY
E
RECT -RECTIFIER
M1 - MOTOR FOR ENERGY STORING DEVICE S91
S10- AUX. SWITCH POSITION INDICATOR S92
S2- MICRO SWITCH FOR MOTOR CONTROL S93 MICRO SWITCHES POSITION OF THE WITHDRAWABLE TROLLY
S41- MICRO SWITCH ACTUATED BY BOTH ON/OFF PUSH BUTTON S94 S91,S92,S93,S94,S95 & S96 OPEN IN TRANSMIT.
S43- MICRO SWITCH ACTUATED BY ONLY OFF PUSH BUTTON S95 S91,S93 & S94 CLOSE IN SERVICE POSITION.
F11- FIRST AUX. TRIPPING COIL S96 S92,S95 & S96 CLOSE IN TEST POSITION.
F12- SECOND AUX. TRIPPING COIL[OPTIONAL]
F2- AUX. CLOSING COIL
F4- UNDER VOLTAGE COIL[OPTIONAL]
F
Y1- BLOCKING MAGNET FOR ON OR OFF PUSH BUTTON OR BOTH[OPTIONAL]
KD1- ANTI PUMPING RELAY[OPTIONAL]
Y0- BLOCKING SOLENOID FOR TROLLY MOVEMENT

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 3
1 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. VCB PLUG DETAIL FOR OUTGOING-1 VCB FEEDER (FOR GRID) Current Page 2
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

33kV INCOMING SUPPLY


FROM COMMON BUS-1
R
Y
B

1 3 5
-Q52
/3.7:D
/6.2:C 2 4 6
/7.1:B
/7.7:B
/2.1:C
1250A, 33kV VCB,
26.3kA FOR 3 SEC.,
3PH. 50Hz
-XT1
B
A11 13
A12
CTR2 /
P1 s1
-CT1
/3.0:D
/4.0:A P2
s2 A10 14

A31 15
A32
CTY2 /
P1 s1
CORE-3
700/1A -CT2
CL-PS
/3.1:E
/4.1:A P2
s2 A30 16
CT INPUT
TO C&R PANEL
C
87T

A51 17
A52
CTB2 /
P1 s1
-CT3
/3.1:E
/4.1:B P2
s2 A50 18
A71
CTN2 /
1
-E2

-XT1
D C11 7
C12
CTR1 / 5.1:A
P1 s1
-CT1 -Q52
/3.0:B
/4.0:A P2
s2 C10 8 /3.0:A B4 B7

C31 9
C32
CTY1 / 5.1:A
P1 s1
CORE-2 -CT2
700/1A /3.1:C
CL-5P10, 5VA /4.1:A P2
s2 C30 10
CT INPUT
TO K51 RELAY B6 B5 B9 B8
E

C51 11
C52

X11

X12

X13

X14

X15

X16
CTB1 / 5.1:B
P1 s1
-CT3 -X6 1 -X6 2 -X6 3 -X6 4 -X6 5 -X6 6
/3.1:C
/4.1:B P2
s2 C50 12
C71
CTN1 / 5.1:B
SPARE VCB CONTACT
1
-E2

R Y B
4.0:A 4.1:A 4.1:A

TO NEXT SHEET
CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 4
2 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. POWER WIRING DIAGRAM FOR OUTGOING-1 VCB FEEDER (FOR Current Page 3
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

FROM PREVIOUS SHEET


3.0:F 3.1:F 3.1:F
R Y B
-XT1
D11 1
D12
P1 s1
A
-CT1
/3.0:B
/3.0:D P2
s2 D10 2

D31 3
D32
P1 s1
CORE-1 -CT2
700/1A /3.1:C
CL-1, 5VA /3.1:E P2
s2 D30 4

B D51 5
D52
P1 s1
E12
-CT3
/3.1:C
/3.1:E P2
s2 D50 6
D71 E32
E52

1
E72
-E2
x1 x1 x1

D13

D33

D53

E12

E32

E52

E72
-H1 -H2 -H3

D13

D33

D53
C R x2 Y x2 B x2

-P2 -P3 1 2 3 4 5 6 8 9 10 11
-P1
DA MFM DV
RS1 RS2 YS1 YS2 BS1 BS2 R Y B N R PH. Y PH. B PH.
DIGITAL AMMETER WITH INBUILT S1 S2 S1 S2 S1 S2 V1 V2 V3 VN DIGITAL VOLTMETER WITH INBUILT
SELECTOR SWITCH SELECTOR SWITCH
12 13 MULTI FUNCTION METER 12 13

PH N RS 485

12 13 7 14

(S1)

(S2)
D
-X3 1 2 3
E12
E32

-F1
-PT1-3 6A FP MCB
33kV/1.73/110V/1.73/110V/1.73 -XPT
CORE:1 CL-1, 105VA 1n 1a E10 1
E11 1 2 E12
CORE:2 CL-3P, 105VA
HTF E30 E32
1 2 A1 A2
1n 1a 2
E31 3 4

E
1n 1a E50 3
E51 5 6 E52
1 2 A1 A2

E70 4
E71 7 8 E72
1 2 A1 A2

-XPT -F01
SA 1n 1a E20 5 E21 1 2 E22
VR / 5.1:D

TO K51 RELAY
R R VR1 VY1 VB1 VN1
E40 E41 E42

FOR U/V O/V


1n 1a 6 3 4
1
VY / 5.1:D
Y Y -E1 110V AC SUPPLY
1n 1a E60 7 E61 5 6 E62
VB / 5.1:D TO BUS-1 IC-1 METERING
B B
F E80 8 E81 7 8 E82
VN / 5.1:D
6A FPMCB

R Y B

TO OUTGOING-1 FOR GRID CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 5
3 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. POWER & METERING DIAGRAM FOR K51 RELAY OF OUTGOING-1 VCB Current Page 4
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. FEEDER (FOR GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

NUMERICAL RELAY 5.6:F 5.6:F NUMERICAL RELAY


DC+ DC- (50,50N,51,51N,95,27,59,67)
(50,50N,51,51N,95,27,59,67)
K51 X2 K51
/5.8:A K1
4D02 / 6.1:E /5.1:A X3
C12 X1 K1
AC
/6.7:A IL1 -PS 3 110V DC
A
3.2:D / CTR1 /6.8:A
K2 AUX SUPPLY
6.7:A / D1
1 3
/7.5:C 1A 4D03 / 6.1:F DI1
K11
AC
/8.1:A 4 - +
TCH FUNCTION 6.7:B / D2
2 4
C32 IL2 X3 FOR TRIPPING COIL
3.2:E / CTY1 K13
3 1A B6 / 6.8:A 5
17 K12 DI2
TRIP COMMAND - +
T1 TO TRIP CKT
6.7:B / D3
CT INPUT C52 4
IL3 K1 6
3.2:E / CTB1 B5 / 6.8:A
16 X4
5
1A L12

DIGITAL INPUT
B8 / 8.1:A

CURRENT I/P
15 SPARE DI 7
DI3
6 T2 O/C & E/F TRIP -X5 4 -X5 X41 - +
I0
L11 TO ANN. CKT 3 8
B
7 5A B7 / 8.1:A
14

DIGITAL OUTPUT
L13 B2 / 8.2:A
8
I0 13 SPARE DI 9
DI4
T3 U/V / O/V TRIP -X5 6 -X5 X42 - +
9
1A L11 5
C71 B1 / 8.2:A TO ANN. CKT
10
3.2:E / CTN1 12
10
SPARE DI 11
DI5
11
-X5 8 -X5 X43 - +
T4 7 12

10
SPARE DI 13
DI6
7 -X5 10 -X5 X44 - +
C
9 14
8
A1
SPARE DI 15
DI7
9 -X5 12 -X5 X45 - +
11 16

X5 20 SPARE DI DI8
E22 U1 -X5 14 -X5 X46 - +
4.5:E / VR 19 13
20 17
SF
19 SPARE DI 18
E42 U2 18
-X5 X47 DI9
4.5:F / VY -X5 16 - +
110V AC
VOLTAGE I/P

D 18 15 19
PT SUPPLY SPARE DI DI10
17 X5 L10 -X5 18 -X5 X48 - +
E62 U3 B10 / 7.5:C 17 20
4.5:F / VB 14
X5
16 TO TCH
E82 T5 INDICATION
4.5:F / VN
L1 SPARE DI 1
DI11
15 13
B9 / 7.5:C -X5 20 -X5 X49 - +
19 2
DIGITAL OUTPUT

SPARE DI DI12
12 -X5 22 -X5 X50 - +
T6 21 3
SPARE DI DI13
-X5 24 -X5 X51 - +
E 11 23 4

10 SPARE DI 5
DI14
T7 -X5 26 -X5 X52 - +
25 6
SPARE DI DI15
9
-X5 28 -X5 X53 - +
27 7
SPARE DI DI16
-X5 30 -X5 X54 - +
(S3) 4 -X3 29 8

K1

K2
+
D+
RS485 COMM.
RS-485 (S4) 5 -X3 PORT
F
- 5.4:A 5.4:A
D-
6 -X3 DC+ DC-

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 6
4 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. K51 RELAY MACRO OF OUTGOING-1 VCB FEEDER (FOR GRID) Current Page 5
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

K1 K1 K1

S5 1

K1

K1

K1

K1
L R
A1 A2
A
-LS 9 -K51 K51
K86

K3

K4
/7.5:E /5.1:A /5.1:A
-X2 -X2 D1
S6
/10.3:B
5.7:A B5
2 -X2 5 5 3 5 1
5.4:A
T S6 1
10 12
REMOTE 10.3:D REMOTE REMOTE
N CLOSING C 5.4:A
10.3:D
TRIPPING TRIPPING -S4 4 B6
C -X2 6 N /6.1:C
6
T -X2 11 -X2 13 E.STOP

1K4
B 5.7:A 5.7:A
A
10 D2 D3
-RS

K13
K11

K11

K11

K11
K11
/7.1:E
6 2
SERVICE K5
B 10 10
-RT -RS
/7.2:E /7.1:E 13
6 2 6 2
TEST SERVICE -R94
14
1K5

1K8 K86
/10.3:B
1 1
10.3:B
-S4
9
/6.6:A 2 10.3:C
/7.4:F -R94 -R94 10
2
K6

E.STOP /6.3:B /6.3:B


5 1

K11
6 2

K10

K12
-X2
K8

K9
C
1
EXTERNAL -X2 7 -X2 9 -X2 14 -X2 16
INTERLOCK -X7 4
-Q52
-X2 2 /3.0:A A5 B13 A3 C5
+BC-1K4
1K6

+BC/39.2:E 1 1 13
INTERLOCKING S91
S11 S12
FROM BC
-X2 4 3 /7.3:C 2 14
+BC/39.2:C /7.4:C
3 9 S12
+BC-1K3
EXTERNAL S92 4
INTERLOCK
10 1
-X7 3 11
D -X2 4 R1 S92
12 4
K7

C1 C1
B14

K13
F2 F11
C2 C2
15
S2
A4 K86
16 /10.3:B
1
9
S43 10.6:C
2
10.6:D
10
A6
E

-X2 8 -X2 15
K2 K2
VCB ANTI PUMPING VCB AUX. SUPPLY
K1

K2

CLOSING COIL RELAY TRIPING COIL FOR MASTER


4D02 / 5.5:A 5 TRIP RELAY (K86)
AUX. SUPPLY
1 9 /6.2:C
4D03 / 5.5:A TO K51 RELAY 6
1 3 2 10 /6.4:C
-F2
6A 2 4
DP MCB
J3

J4

4D00 4D01
9.5:D 9.5:D

110V DC AUX SUPPLY


CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 7
5 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CLOSING & TRIPPING CONTROL WIRING DIAGRAM FOR OUTGOING-1 Current Page 6
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. VCB FEEDER (FOR GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

11

-RDLS

M1
L1 12

L1

L1

L1

L1
DOOR
LIMIT
B
SWITCH
-X2 26
-X2 17 -X2 19 -X2 21 -X2 23

-Q52
/3.0:A D5 D9 A13 B1 -Q52
/3.0:A S2 A1
1

K86 K51 2
/10.3:B /5.1:A
13 7 B9 -V1
SERVICE TEST 5.4:D
5 13 10.3:D R3 R1
POS. SW. POS. SW. S2 U1
14 S11 S11 10.3:E 5.4:D
C
/6.4:C 6 /6.4:C 14 8 B10 M
-M1
1~
R4
D6 D10 A14 B3 B2 U2
RECT

S2

L10

L11
L4

L5

L7

L8
L3

L9
4

-X2 18 -X2 20 -X2 22 -X2 24 -X2 25


3

A2
D

-X2 27
-X7 1

M2
+BC-1K1
+BC/39.0:D

TO 1K1 CONT.
+BC/39.0:D
A1 x1 x1 A1 x1 +BC-1K2 x1 x1 x1 x1 A1 VCB SPRING

M1

M2
-RS -H9 -H10 -RT -H8 -H4 -H5 -H6 -H7 -LS CHARGE MOTOR
A2 x2 x2 A2 x2 x2 x2 x2 x2 A2
-X7 2 3A02 / 8.1:E
E
L2 L2
TOANNUNCIATOR
AUX. VCB IN VCB IN AUX. SPRING VCB ON VCB OFF VCB TRIP TRIP CKT AUX. 3A03 / 8.2:E
L1

L2

RELAY SERVICE TEST RELAY CHARGE HEALTHY RELAY 1 3

6 10 /6.1:B 6 10 /6.1:B 5 -F4


2 2 6A 2 4
1 9 /6.6:A
6 10 /6.1:B DP MCB
6
2 13
S5 1 2 10 /7.5:F

H3

H4
LS 10
1 3 -S4 14 /7.5:E
L R /6.1:C
-F3 A1 A2 E.STOP 6 2 -X2 30 EARTHING TB
6A 2 4
X65

X66

EARTHING TB
X63

X64

DP MCB
3A00 3A01
J3

J4

F -X2 28
29
1 9.1:D 9.2:D
-X4 7 8 -X4 9 10 -E1
L/R SWITCH SPARE CONTACT 230V AC
4D04 4D05 E.STOP PB LIMIT SW.
IN REMOTE MODE AUX SUPPLY
9.6:D 9.6:D OPERATED
FEEDBACK
110V DC FEEDBACK
AUX SUPPLY CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 8
6 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CONTROL WIRING DIAGRAM FOR INDICATING LAMP & SPRING Current Page 7
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. CHARGE MOTOR FOR OUTGOING-1 VCB FEEDER (FOR GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

L11
A
K51 -X4 1 -X4 3

/5.1:A
B7 B1 -R1 11 -R3 11
5.4:B 5.4:B SPARE SPARE /9.4:C /9.8:C

5.4:B 5.4:B 7 3 7 3

B8 B2 -X4 2 -X4 4

L11
L12

L13

L14

L15

L16

L17
B -AN
1 2 3 4 5 6 COM

O/C & E/F UNDER/OVER SPARE SPARE AC FAIL DC FAIL


WITH HIGHEST VOLTAGE
TRIP TRIP

POWER ON

6 WINDOW ANNUNCIATOR
TEST
C

ACCEPT

RESET
P N C NO T A R E

1
E
L33

L34

L35

L36

D
-X4 5 -X4 6
9 10
-R3 -R3
/9.8:C 5 1 /9.8:C 6 2 +BC-H1 +BC-H2
+BC/36.3:D +BC/36.3:E

TO COMMON HOOTER
L31

L32

IN BUSCOUPLER

E
1 3
-F6
6A 2 4
DP MCB
M1

M2
J3

J4

-3A02 -3A03
4D06 4D07 7.7:E 7.7:E
9.7:D 9.7:D 230V AC
110V DC AUX SUPPLY
F AUX SUPPLY

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 9
7 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CONTROL WIRING DIAGRAM OF ANN. WINDOW FOR OUTGOING-1 Current Page 8
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. VCB FEEDER (FOR GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

110V DC AUX. SUPPLY


230V AC AUX. SUPPLY
FROM FIELD
FROM FIELD
A

-XAC 1 2
-XDC 1 2

H3

H4
-XAC -XDC
/ +IC2-1ACP +IC2-1DCP /
230V AC AUX. SUPPLY 3 3 110V DC AUX. SUPPLY
FROM TO BUS-1 INCOMER -XAC FROM TO BUS-1 INCOMER
-XDC
/ +IC2-1ACN +IC2-1DCN /
4 4

B -XAC -XDC
+BC/37.3:A / +BC-2ACP +BC-2DCP / +BC/37.7:A
230V AC AUX. SUPPLY 5 5
110V DC AUX. SUPPLY
FROM BUSCOUPLER -XAC -XDC FROM BUSCOUPLER
+BC/37.3:A / +BC-2ACN +BC-2DCN / +BC/37.7:A
6 6

-R1 10
A1 5
/9.4:C
6 A1
-R1 1 9 /8.1:D
2 10 /9.5:C 6 2
A2 7 X55 X56 -R3 6
A2 2 10 /8.2:D
3 11 /8.4:A 7
AC FAIL -X5 31 3 11 /8.4:A
32
RELAY DC FAIL 8
C
230V AC SUPPLY SPARE CONTACT
RELAY 4 12 /9.8:D
FOR AC FAIL

J3

J4
110V DC SUPPLY
H3

H4

H3

H4
-R3 12

J3

J4

J3

J4

J3

J4
/9.8:C

8 4
3A00 3A01
7.7:F 7.7:F
X57 X58
1 1 4D00 4D01 4D04 4D05 4D06 4D07
D 7.0:F 7.0:F 8.0:F 8.1:F -X5 33
34
TO VCB SPRING 6.0:F 6.1:F
-F11 -F12 NL SPARE CONTACT
CHARGE MOTOR 6A 2 6A 2
TO CLOSING & TO INDICAION TO ANN. WINDOW
FOR DC FAIL
TRIPPING CIRCUIT CIRCUIT CIRCUIT
H6

H9
11
H5

-DLS
DOOR
12 -XSH 1
LIMIT 13
PS SWITCH
TH
1
3 14
H12

2
H7

E
x1 x1

-SH
-PL 80W
x2

x2 -XSH 2

PLUG PANEL SPACE


SOCKET LIGHT HEATER
HOLDER

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 10
8 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. AC & DC VOLTAGE CIRCUIT FOR OUTGOING-1 VCB FEEDER (FOR Current Page 9
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

MASTER TRIP RELAY (K86)


-K86
/6.3:B
/6.5:A
B /6.8:D
/7.4:C

K8
6.3:B / 1
1
1

TO CLOSING COIL
2
K9
6.3:C / 2
2

-X5 1 X31
C
3
3
SPARE NO CONTACT
4

-X5 2 X32 9 K13


4 9 / 6.8:D

K1 K1 10 K2
6.5:A / 5 10 / 6.8:E
5
5
TO TRIPING COIL
6
D K11
6.5:A / 6
6

L1
7.4:C / 7
7
7
TO TRIP LAMP
8
L9
7.4:C / 8
8

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 11
9 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. MACRO FOR MASTER TRIP RELAY (K86) OF OUTGOING-1 VCB Current Page 10
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. FEEDER (FOR GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG1-X2 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-S4:2 K6 1 EXTERNAL INTERLOCK

2 =

3 =
B
-X7:3 K7 4 =

-A2 5 REMOTE CLOSE CMD

-RS:10 1K4 6 =

-Q52-A5 7 CLOSING CIRCUIT K9 -K86-2 /10.3:C

-F2:3 K2 8 = -Q52-A6 /6.3:E

-Q52-B13 9 CLOSING CIRCUIT (ANTIPUMPING) K10 -R94:14 /6.3:B


C

-K86-5 K1 10 REMOTE TRIP CMD

-K86-6 K11 11 =

-S4:3 K1 12 =

-S4:4 K11 13 =

-Q52-A3 14 TRIPPING CIRCUIT K11 -K86-6 /10.3:D

D 15 = -Q52-A4 /6.4:D

-Q52-C5 16 TCH K12 -K51-6 /5.8:A

-Q52-D5 17 VCB IN SERVICE POSITION L1 -F3:1 /7.0:F

-H9:x1 18 = L3 -Q52-D6 /7.1:C

-Q52-D9 19 VCB IN TEST POSITION

-H10:x1 20 = L4 -Q52-D10 /7.2:C


E
-Q52-A13 21 VCB SPRING CHARGE INDI.

-H8:x1 22 = L5 -Q52-A14 /7.2:C

-Q52-B1 23 VCB ON L1 -K86-7 /10.3:D

-H4:x1 24 = L7 -Q52-B3 /7.3:C

-H5:x1 25 VCB OFF L8 -Q52-B2 /7.4:C

-Q52-A1 26 SPRING CHARGE MOTOR M1 -F4:1 /7.7:E


F

-F4:3 M2 27 = -Q52-A2 /7.8:D

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 12
10 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG1-X2 Current Page 11
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG1-X2 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

28 SPARE CONTACT LIMIT SW. -LS:10 /7.5:F

-LS:6 29

-E1:1 30 EARTHING TB
B

Strip
External targets
+OG1-X3 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 MFM RS-485 (S1) -P3-7 /4.6:D

C
2 = (S2) -P3-14 /4.6:D

3 = /4.6:D

-K51-D+ (S3) 4 K51 RELAY RS485

-K51-D- (S4) 5 =

6 =

Strip
External targets
+OG1-X4 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 SPARE ANN. WINDOW -K51-10 /5.3:C

2 = L15 -AN-4 /8.3:B


E
3 = -R3:11 /8.4:A

4 = L16 -AN-5 /8.4:B

+BC-X4:9 5 TO COMMON HOOTER IN BC

+BC-X4:10 6 =

7 L/R SWITCH IN REMOTE MODE FEEDBACK X63 -1 /7.3:F

8 = X64 -A2 /7.3:F


F

9 E.STOP PB OPERATED FEEDBACK X65 -S4:13 /7.4:F

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 13
11 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG1-X2 +OG1-X3 +OG1-X4 Current Page 12
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG1-X4 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

10 E.STOP PB OPERATED FEEDBACK X66 -S4:14 /7.4:F

Strip
+OG1-X5
B
External targets Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-K86-3 X31 1 SPARE NC CONTACT (K86 RELAY)

-K86-4 X32 2 =

3 K51 RELAY SPARE DI X41 -K51-8 /5.8:B

C
4 =

5 = X42 -K51-10 /5.8:B

6 =

7 = X43 -K51-12 /5.8:C

8 =

9 = X44 -K51-14 /5.8:C


D

10 =

11 = X45 -K51-16 /5.8:C

12 =

13 = X46 -K51-17 /5.8:D

14 =

E 15 = X47 -K51-19 /5.8:D

16 =

17 = X48 -K51-20 /5.8:D

18 =

19 = X49 -K51-2 /5.8:D

20 =
F
21 = X50 -K51-3 /5.8:E

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 14
12 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG1-X4 +OG1-X5 Current Page 13
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG1-X5 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

22 K51 RELAY SPARE DI

23 = X51 -K51-4 /5.8:E

24 =
B
25 = X52 -K51-6 /5.8:E

26 =

27 = X53 -K51-7 /5.8:E

28 =

29 = X54 -K51-8 /5.8:F

30 =
C

31 SPARE CONTACT FOR AC FAIL RELAY -R1:10 /9.5:C

-R1:6 32

33 SPARE CONTACT FOR DC FAIL RELAY -R3:12 /9.8:D

-R3:8 34

D
Strip
External targets
+OG1-X6 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 SPARE VCB C/O CONTACT X11 -Q52-B4 /3.7:D

2 = X12 -Q52-B6 /3.7:E

E 3 = X13 -Q52-B5 /3.8:E

4 = X14 -Q52-B7 /3.9:D

5 = X15 -Q52-B9 /3.9:E

6 = X16 -Q52-B8 /3.9:E

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 15
13 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG1-X5 +OG1-X6 Current Page 14
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG1-X7 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

+BC-X8:1 OG1-L7 1 TO B/C FOR INTERLOCKING -H4:x1 /7.3:E

+BC-X8:2 OG1-L2 2 = L2 -H8:x2 /7.2:E

+BC-X8:3 OG1-K7 3 = K7 -X2:4 /6.1:D


B
+BC-X8:4 OG1-K8 4 = K8 -R94:1 /6.2:C

Strip
External targets
+OG1-XAC Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement
C
-F4:2 H3 1 230V AC FROM FIELD

-F4:4 H4 2 =

-F4:2 H3 3 230V AC AUX. SUPPLY FROM TO BUS-1 INCOMER

-F4:4 H4 4 =

-F4:2 H3 5 230V AC AUX. SUPPLY FROM TO BUSCOUPLER +BC-XAC:1 +BC/35.3:B

-F4:4 H4 6 = +BC-XAC:2 +BC/35.3:B


D

Strip
External targets
+OG1-XDC Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-F6:2 J3 1 110V DC FROM FIELD


E
-F6:4 J4 2 =

-F6:2 J3 3 110V DC AUX. SUPPLY FROM TO BUS-1 INCOMER

-F6:4 J4 4 =

-F6:2 J3 5 110V DC AUX. SUPPLY FROM TO BUSCOUPLER +BC-XDC:1 +BC/35.7:B

-F6:4 J4 6 = +BC-XDC:2 +BC/35.7:B

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 16
14 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG1-X7 +OG1-XAC +OG1-XDC Current Page 15
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG1-XPT Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-PT1-3:1a E10 1 110V AC PT SUPPLY TO METERING

-PT1-3:1a E30 2 =

-PT1-3:1a E50 3 =
B
-PT1-3 E70 4 =

-PT1-3:1a E20 5 PT T.B. FOR CL-3P E21 -F01:1 /4.4:E

-PT1-3:1a E40 6 = E41 -F01:3 /4.4:E

-PT1-3:1a E60 7 = E61 -F01:5 /4.4:E

-PT1-3 E80 8 = E81 -F01:7 /4.4:E

Strip
External targets
+OG1-XSH Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-TH:13 1 SPACE HEATER T.B. H6 -F12:2 /9.4:D

-PL:x2 2 = -SH:x2 /9.4:E


D

Strip
External targets
+OG1-XT1 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 CT SHORTING T.B. FOR METERING D11 -CT1:s1 /4.0:A


E
-P2-RS1 D12 2 = -E2:1 /4.1:C

3 = D31 -CT2:s1 /4.1:A

-P2-YS1 D32 4 = D10 -CT1:s2 /4.0:A

-P3-6 D71 5 = D51 -CT3:s1 /4.1:B

-P2-BS1 D52 6 = D10 -CT1:s2 /4.0:A

7 CT SHORTING T.B. FOR PROTECTION C11 -CT1:s1 /3.0:D


F

-K51-1 C12 8 = -E2:1 /3.1:F

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 17
15 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG1-XPT +OG1-XSH +OG1-XT1 Current Page 16
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG1-XT1 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

9 CT SHORTING T.B. FOR PROTECTION C31 -CT2:s1 /3.1:E

-K51-3 C32 10 = C10 -CT1:s2 /3.0:D

-K51-10 C71 11 = C51 -CT3:s1 /3.1:E


B
-K51-5 C52 12 = C10 -CT1:s2 /3.0:D

13 CT SHORTING T.B. FOR C&R PANEL 87T A11 -CT1:s1 /3.0:B

14 = -E2:1 /3.1:D

15 = A31 -CT2:s1 /3.1:C

16 = A10 -CT1:s2 /3.0:B

17 = A51 -CT3:s1 /3.1:C


C

18 = A10 -CT1:s2 /3.0:B

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page +OG2/18
16 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG1-XT1 Current Page 17
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

33kV INCOMING SUPPLY


FROM COMMON BUS-2
R
Y
B

1 3 5
-Q52
/18.7:D
/21.2:C 2 4 6
/22.1:B
/22.7:B
1250A, 33kV VCB,
26.3kA FOR 3 SEC.,
3PH. 50Hz

B
-XT1
A11 13
A12
CTR2 /
P1 s1
-CT1
/18.0:D
/19.0:A P2
s2 A10 14

A31 15
A32
CTY2 /
P1 s1
CORE-3
700/1A -CT2
CL-PS
/18.1:E
/19.1:A P2
s2 A30 16
CT INPUT
TO C&R PANEL
C
87T

A51 17
A52
CTB2 /
P1 s1
-CT3
/18.1:E
/19.1:B P2
s2 A50 18
A71
CTN2 /
1
-E2

-XT1
D C11 7
C12
CTR1 / 20.1:A
P1 s1
-CT1
/18.0:B
/19.0:A P2
s2 C10 8

-Q52
C31 9
C32 /18.0:A B4 B7
CTY1 / 20.1:A
P1 s1
CORE-2 -CT2
700/1A /18.1:C
CL-5P10, 5VA /19.1:A P2
s2 C30 10
CT INPUT
TO K51 RELAY
E

C51 11
C52 B6 B5 B9 B8
CTB1 / 20.1:B
P1 s1
-CT3

X11

X12

X13

X14

X15

X16
/18.1:C
/19.1:B P2
s2 C50 12
C71
CTN1 / 20.1:B
-X6 1 -X6 2 -X6 3 -X6 4 -X6 5 -X6 6
1
-E2
SPARE VCB CONTACT
F

R Y B
19.0:A 19.1:A 19.1:A

TO NEXT SHEET
CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 19
+OG1/17 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. POWER & METERING DIAGRAM FOR OUTGOING-2 VCB FEEDER (FOR Current Page 18
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

FROM PREVIOUS SHEET


18.0:F 18.1:F 18.1:F
R Y B
-XT1
D11 1
D12
P1 s1
A
-CT1
/18.0:B
/18.0:D P2
s2 D10 2

D31 3
D32
P1 s1
CORE-1 -CT2
700/1A /18.1:C
CL-1, 5VA /18.1:E P2
s2 D30 4

B D51 5
D52
P1 s1
E12
-CT3
/18.1:C
/18.1:E P2
s2 D50 6
D71 E32
E52

1
E72
-E2
x1 x1 x1

D13

D33

D53

E12

E32

E52

E72
-H1 -H2 -H3

D13

D33

D53
C R x2 Y x2 B x2

-P2 -P3 1 2 3 4 5 6 8 9 10 11
-P1
DA MFM DV
RS1 RS2 YS1 YS2 BS1 BS2 R Y B N R PH. Y PH. B PH.
DIGITAL AMMETER WITH INBUILT S1 S2 S1 S2 S1 S2 V1 V2 V3 VN DIGITAL VOLTMETER WITH INBUILT
SELECTOR SWITCH SELECTOR SWITCH
12 13 MULTI FUNCTION METER 12 13

PH N RS 485

12 13 7 14

(S1)

(S2)
D
-X3 1 2 3
E12
E32

-F1
-PT1-3 6A FP MCB
33kV/1.73/110V/1.73/110V/1.73 -XPT
CORE:1 CL-1, 105VA 1n 1a E10 1
E11 1 2 E12
CORE:2 CL-3P, 105VA
HTF E30 E32
1 2 A1 A2
1n 1a 2
E31 3 4

E
1n 1a E50 3
E51 5 6 E52
1 2 A1 A2

E70 4
E71 7 8 E72
1 2 A1 A2

-XPT -F01
SA 1n 1a E20 5 E21 1 2 E22
VR / 20.1:D

TO K51 RELAY
R R VR2 VY2 VB2 VN2
E40 E41 E42

FOR U/V O/V


1n 1a 6 3 4
1 +IC3/47.5:B
+IC3/47.6:B
+IC3/47.6:B
+IC3/47.6:B
VY / 20.1:D
Y Y -E1 110V AC SUPPLY
1n 1a E60 7 E61 5 6 E62
VB / 20.1:D TO BUS-2 IC-3 METERING
B B
F E80 8 E81 7 8 E82
VN / 20.1:D
6A FPMCB

R Y B

TO OUTGOING-2 FOR GRID CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 20
18 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. POWER & METERING WIRING DIAGRAM FOR K51 RELAY OF Current Page 19
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. OUTGOING-2 VCB FEEDER (FOR GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

NUMERICAL RELAY 20.6:F 20.6:F NUMERICAL RELAY


DC+ DC- (50,50N,51,51N,95,27,59,67)
(50,50N,51,51N,95,27,59,67)
K51 X2 K51
/20.8:A K1
4D02 / 21.1:E X3
C12 X1 K1 /20.1:A
AC
/21.7:A IL1 -PS 3 110V DC
A
18.2:D / CTR1 /21.8:A
K2 AUX SUPPLY
21.7:A / D1
1 3
/22.5:C 1A 4D03 / 21.1:F DI1
K11
AC
/23.1:A 4 - +
TCH FUNCTION 21.7:B / D2
2 4
C32 IL2 X3 FOR TRIPPING COIL
18.2:E / CTY1 K13
3 1A B6 / 21.8:A 5
17 K12 DI2
TRIP COMMAND - +
T1 TO TRIP CKT
21.7:B / D3
CT INPUT C52 4
IL3 K1 6
18.2:E / CTB1 B5 / 21.8:A
16 X4
5
1A L12

DIGITAL INPUT
B8 / 23.1:A

CURRENT I/P
15 SPARE DI 7
DI3
6 T2 O/C & E/F TRIP -X5 4 -X5 X41 - +
I0
L11 TO ANN. CKT 3 8
B
7 5A B7 / 23.1:A
14

DIGITAL OUTPUT
L13 B2 / 23.2:A
8
I0 13 SPARE DI 9
DI4
T3 U/V /OV TRIP -X5 6 -X5 X42 - +
9
1A L11 5
C71 B1 / 23.2:ATO ANN. CKT
10
18.2:E / CTN1 12
10
L14 SPARE DI 11
DI5
11
-X5 8 -X5 X43 - +
T4 7 12
L11
10
SPARE DI 13
DI6
7 -X5 10 -X5 X44 - +
C
9 14
8
A1
SPARE DI 15
DI7
9 -X5 12 -X5 X45 - +
11 16

X5 20 SPARE DI DI8
E22 U1 -X5 14 -X5 X46 - +
19.5:E / VR 19 13
20 17
SF
19 SPARE DI 18
E42 U2 18
-X5 X47 DI9
19.5:F / VY -X5 16 - +
110V AC
VOLTAGE I/P

D 18 15 19
PT SUPPLY SPARE DI DI10
17 X5 L10 -X5 18 -X5 X48 - +
E62 U3 B10 / 22.5:C 17 20
19.5:F / VB 14
X5
16 TO TCH
E82 T5 INDICATION
19.5:F / VN
L1 SPARE DI 1
DI11
15 13
B9 / 22.5:C -X5 20 -X5 X49 - +
19 2
DIGITAL OUTPUT

SPARE DI DI12
12 -X5 22 -X5 X50 - +
T6 21 3
SPARE DI DI13
-X5 24 -X5 X51 - +
E 11 23 4

10 SPARE DI 5
DI14
T7 -X5 26 -X5 X52 - +
25 6
SPARE DI DI15
9
-X5 28 -X5 X53 - +
27 7
SPARE DI DI16
-X5 30 -X5 X54 - +
(S3) 4 -X3 29 8

K1

K2
+
D+
RS485 COMM.
RS-485 (S4) 5 -X3 PORT
F
- 20.4:A 20.4:A
D-
6 -X3 DC+ DC-

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 21
19 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. K51 RELAY MACRO OF OUTGOING-2 VCB FEEDER (FOR GRID) Current Page 20
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

K1 K1 K1

S5 1

K1

K1

K1

K1
L R
A1 A2
A
-LS 9 -K51 K51
K86

K3

K4
/22.5:E /20.1:A /20.1:A
-X2 -X2 D1
S6
/25.3:B
20.7:A B5
2 -X2 5 5 3 5 1
20.4:A
T S6 1
10 12
REMOTE 25.3:D REMOTE REMOTE
N CLOSING C 20.4:A
25.3:D
TRIPPING TRIPPING -S4 4 B6
C -X2 6 N /21.1:C
6
T -X2 11 -X2 13 E.STOP

1K4
B 20.7:A 20.7:A
A
10 D2 D3
-RS

K13
K11

K11

K11

K11
K11
/22.1:E
6 2
SERVICE K5
B 10 10
-RT -RS
/22.2:E /22.1:E 13
6 2 6 2
TEST SERVICE -R94
14
1K5

1K8 K86
/25.3:B
1 1
25.3:B
-S4
9
/21.6:A 2 25.3:C
/22.4:F -R94 -R94 10
2
K6

E.STOP /21.3:B /21.3:B


5 1

K11
6 2

K10

K12
-X2
K8

K9
C
1
EXTERNAL -X2 7 -X2 9 -X2 14 -X2 16
INTERLOCK -X7 4
-Q52
-X2 2 /18.0:A A5 B13 A3 C5
+BC-2K4
1K6

+BC/39.5:E 1 1 13
INTERLOCKING S91
S11 S12
FROM BC
-X2 4 3 /22.3:C 2 14
+BC/39.5:C /22.4:C
3 9 S12
+BC-2K3
EXTERNAL S92 4
INTERLOCK
10 1
-X7 3 11
D -X2 4 R1 S92
12 4
K7

C1 C1
B14

K13
F2 F11
C2 C2
15
S2
A4 K86
16 /25.3:B
1
9
S43 25.6:C
2
25.6:D
10
A6
E

-X2 8 -X2 15
K2 K2
VCB ANTI PUMPING VCB AUX. SUPPLY
K1

K2

CLOSING COIL RELAY TRIPING COIL FOR MASTER


4D02 / 20.5:A 5 TRIP RELAY (K86)
AUX. SUPPLY
1 9 /21.2:C
4D03 / 20.5:ATO K51 RELAY 6
1 3 2 10 /21.4:C
-F2
6A 2 4
DP MCB
J3

J4

4D00 4D01
24.5:D 24.5:D

110V DC AUX SUPPLY


CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 22
20 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CLOSING & TRIPPING CONTROL WIRING DIAGRAM FOR OUTGOING-2 Current Page 21
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. VCB FEEDER (FOR GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

11

M1
L1 -RDLS 12

L1

L1

L1

L1
DOOR
LIMIT
B
SWITCH
-X2 26
-X2 17 -X2 19 -X2 21 -X2 23

-Q52
/18.0:A D5 D9 A13 B1 -Q52
/18.0:A S2 A1
1

K86 K51 2
/25.3:B /20.1:A
13 7 B9 -V1
SERVICE TEST 20.4:D
5 13 25.3:D R3 R1
POS. SW. POS. SW. S2 U1

14 S11 S11 25.3:E 20.4:D


C
/21.4:C 6 /21.4:C 14 8 B10 M
-M1
1~
R4
U2
D6 D10 A14 B3 B2
RECT

S2

L10

L11
L4

L5

L7

L8
4
L3

L9
-X2 18 -X2 20 -X2 22 -X2 24 -X2 25 3

A2

-X2 27
-X7 1

M2
+BC-2K1
+BC/39.3:D

TO 2K1 CONT.
+BC/39.3:D
A1 x1 x1 A1 x1 x1 x1 x1 x1 A1 VCB SPRING
+BC-2K2

M1

M2
-RS -H9 -H10 -RT -H8 -H4 -H5 -H6 -H7 -LS CHARGE MOTOR
A2 x2 x2 A2 x2 x2 x2 x2 x2 A2
-X7 2 3A02 / 23.1:E
E
L2 L2 TOANNUNCIATOR
VCB OFF VCB TRIP TRIP CKT AUX. 3A03 / 23.2:E
AUX. VCB IN VCB IN AUX. SPRING VCB ON
L1

L2

RELAY SERVICE TEST RELAY CHARGE HEALTHY RELAY 1 3


-F4
6 10 /21.1:B 6 10 /21.1:B 5 6A 2 4
2 2 1 9 /21.6:A DP MCB
6 10 /21.1:B 13 6
2 S5 1

H3

H4
2 10 /22.5:F
-S4 LS 10
14
1 3 L R /21.1:C /22.5:E
-F3 A1 A2 E.STOP
6 2
X65

X66

6A 2 4
X63

X64

DP MCB -X2 30 EARTHING TB 3A00 3A01


J3

J4

EARTHING TB 24.1:D 24.2:D


F -X2 28
29
-X4 7 8 -X4 9 10
L/R SWITCH SPARE CONTACT 1 230V AC
4D04 4D05 E.STOP PB -E1
IN REMOTE MODE LIMIT SW. AUX SUPPLY
24.6:D 24.6:D OPERATED
FEEDBACK
110V DC FEEDBACK
AUX SUPPLY CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 23
21 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CONTROL WIRING DIAGRAM FOR INDICATING LAMP & SPRING Current Page 22
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. CHARGE MOTOR FOR OUTGOING-2 VCB FEEDER (FOR GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

L11
A
K51 -X4 1 -X4 3

/20.1:A -R1
B7 B1 11 -R3 11
/24.4:C
20.4:B 20.4:B SPARE SPARE /24.8:C
7 3 7 3
20.4:B 20.4:B
B8 B2 -X4 2 -X4 4

L11
L12

L13

L14

L15

L16

L17
B -AN
1 2 3 4 5 6 COM

O/C & E/F UNDER/OVER SPARE AC FAIL DC FAIL


SPARE
WITH HIGHEST VOLTAGE
TRIP TRIP

POWER ON

6 WINDOW ANNUNCIATOR
TEST
C

ACCEPT

RESET
P N C NO T A R E

1
E
L33

L34

L35

L36

D
-X4 5 -X4 6
9 10
-R3 -R3
/24.8:C 5 1 /24.8:C 6 2 +BC-H7 +BC-H8
+BC/36.5:D +BC/36.5:E

TO COMMON HOOTER
L31

L32

IN BUSCOUPLER

E
1 3
-F6
6A 2 4
DP MCB
M1

M2
J3

J4

-3A02 -3A03
4D06 4D07 22.7:E 22.7:E
24.7:D 24.7:D 230V AC
110V DC AUX SUPPLY
F AUX SUPPLY

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 24
22 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CONTROL WIRING DIAGRAM OF ANN. WINDOW FOR OUTGOING-2 Current Page 23
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. VCB FEEDER (FOR GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

A
230V AC AUX. SUPPLY 110V DC AUX. SUPPLY
FROM BUSCOUPLER FROM BUSCOUPLER
+BC/37.2:B +BC/37.2:B +BC/37.8:B +BC/37.8:B
2ACP1 2ACN1 2DCP1 2DCN1

-XAC 1 2
-XDC 1 2

H3

H4
-XDC
-XAC 2DCP2 / +IC3/51.7:A
B +IC3/51.3:A / 2ACP2 3 110V DC AUX. SUPPLY
3
230V AC AUX. SUPPLY TO INCOMER-3
-XDC
TO INCOMER-3 -XAC 2DCN2 / +IC3/51.7:A
+IC3/51.3:A / 2ACN2 4
4

7
A1 3 11 /23.4:A
-R1
A2
C 5
AC FAIL A1 1 9 /23.1:D

230V AC SUPPLY RELAY -R3 6


A2 2 10 /23.2:D
7
3 11 /23.4:A
DC FAIL
RELAY
H3

H4

H3

H4

J3

J4
3A00 3A01 110V DC SUPPLY
D
22.6:F 22.6:F
1 1
TO VCB SPRING -F11 -F12 NL
CHARGE MOTOR 6A 2 6A 2

J3

J4

J3

J4

J3

J4
H6

H9
11
H5

4D00 4D01 4D04 4D05 4D06 4D07


22.0:F 22.0:F 23.0:F 23.1:F
-DLS 21.0:F 21.1:F
DOOR
12 -XSH 1
LIMIT 13 TO CLOSING & TO INDICAION TO ANN. WINDOW
PS SWITCH
TH TRIPPING CIRCUIT CIRCUIT CIRCUIT
1
E
3 14
H12

2
H7

x1 x1

-SH
-PL 80W
x2

x2 -XSH 2

PLUG PANEL SPACE


SOCKET LIGHT HEATER
HOLDER
F

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 25
23 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. AC & DC VOLTAGE CIRCUIT FOR OUTGOING-2 VCB FEEDER (FOR Current Page 24
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

MASTER TRIP RELAY (K86)


-K86
/21.3:B
/21.5:A
B /21.8:D
/22.4:C

K8
21.3:B / 1
1
1

TO CLOSING COIL
2
K9
21.3:C / 2
2

-X5 1 X31
C
3
3
SPARE NO CONTACT
4

-X5 2 X32 9 K13


4 9 / 21.8:D

K1 K1 10 K2
21.5:A / 5 10 / 21.8:E
5
5
TO TRIPING COIL
6
D K11
21.5:A / 6
6

L1
22.4:C / 7
7
7
TO TRIP LAMP
8
L9
22.4:C / 8
8

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 26
24 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. MACRO FOR MASTER TRIP RELAY (K86) OF OUTGOING-2 VCB Current Page 25
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. FEEDER (FOR GRID) Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG2-X2 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-S4:2 K6 1 EXTERNAL INTERLOCK

2 =

3 =
B
-X7:3 K7 4 =

-A2 5 REMOTE CLOSE CMD

-RS:10 1K4 6 =

-Q52-A5 7 CLOSING CIRCUIT K9 -K86-2 /24.3:C

-F2:3 K2 8 = -Q52-A6 /20.3:E

-Q52-B13 9 CLOSING CIRCUIT (ANTIPUMPING) K10 -R94:14 /20.3:B


C

-K86-5 K1 10 REMOTE TRIP CMD

-K86-6 K11 11 =

-S4:3 K1 12 =

-S4:4 K11 13 =

-Q52-A3 14 TRIPPING CIRCUIT K11 -K86-6 /24.3:D

D 15 = -Q52-A4 /20.4:D

-Q52-C5 16 TCH K12 -K51-6 /19.8:A

-Q52-D5 17 VCB IN SERVICE POSITION L1 -F3:1 /21.0:F

-H9:x1 18 = L3 -Q52-D6 /21.1:C

-Q52-D9 19 VCB IN TEST POSITION

-H10:x1 20 = L4 -Q52-D10 /21.2:C


E
-Q52-A13 21 VCB SPRING CHARGE INDI.

-H8:x1 22 = L5 -Q52-A14 /21.2:C

-Q52-B1 23 VCB ON L1 -K86-7 /24.3:D

-H4:x1 24 = L7 -Q52-B3 /21.3:C

-H5:x1 25 VCB OFF L8 -Q52-B2 /21.4:C

-Q52-A1 26 SPRING CHARGE MOTOR M1 -F4:1 /21.6:E


F

-F4:3 M2 27 = -Q52-A2 /21.8:D

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 27
25 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG2-X2 Current Page 26
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG2-X2 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

28 SPARE CONTACT LIMIT SW. -LS:10 /21.5:F

-LS:6 29

-E1:1 30 EARTHING TB
B

Strip
External targets
+OG2-X3 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 MFM RS-485 (S1) -P3-7 /18.6:D

C
2 = (S2) -P3-14 /18.6:D

3 = /18.6:D

-K51-D+ (S3) 4 K51 RELAY RS485

-K51-D- (S4) 5 =

6 =

Strip
External targets
+OG2-X4 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 SPARE ANN. WINDOW -K51-10 /19.3:C

2 = L15 -AN-4 /22.3:B


E
3 = -R3:11 /22.4:A

4 = L16 -AN-5 /22.4:B

+BC-X4:15 5 TO COMMON HOOTER IN BC

+BC-X4:16 6 =

7 L/R SWITCH IN REMOTE MODE FEEDBACK X63 -1 /21.3:F

8 = X64 -A2 /21.3:F


F

9 E.STOP PB OPERATED FEEDBACK X65 -S4:13 /21.4:F

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 28
26 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG2-X2 +OG2-X3 +OG2-X4 Current Page 27
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG2-X4 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

10 E.STOP PB OPERATED FEEDBACK X66 -S4:14 /21.4:F

Strip
+OG2-X5
B
External targets Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-K86-3 X31 1 SPARE NC CONTACT (K86 RELAY)

-K86-4 X32 2 =

3 K51 RELAY SPARE DI X41 -K51-8 /19.8:B

C
4 =

5 = X42 -K51-10 /19.8:B

6 =

7 = X43 -K51-12 /19.8:C

8 =

9 = X44 -K51-14 /19.8:C


D

10 =

11 = X45 -K51-16 /19.8:C

12 =

13 = X46 -K51-17 /19.8:D

14 =

E 15 = X47 -K51-19 /19.8:D

16 =

17 = X48 -K51-20 /19.8:D

18 =

19 = X49 -K51-2 /19.8:D

20 =
F
21 = X50 -K51-3 /19.8:E

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 29
27 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG2-X4 +OG2-X5 Current Page 28
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG2-X5 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

22 K51 RELAY SPARE DI

23 = X51 -K51-4 /19.8:E

24 =
B
25 = X52 -K51-6 /19.8:E

26 =

27 = X53 -K51-7 /19.8:E

28 =

29 = X54 -K51-8 /19.8:F

30 =
C

Strip
External targets
+OG2-X6 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 SPARE VCB C/O CONTACT X11 -Q52-B4 /17.8:D


D

2 = X12 -Q52-B6 /17.8:E

3 = X13 -Q52-B5 /17.8:E

4 = X14 -Q52-B7 /17.9:D

5 = X15 -Q52-B9 /17.9:E

6 = X16 -Q52-B8 /17.9:E

Strip
External targets
+OG2-X7 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

+BC-X8:5 OG2-L7 1 TO B/C FOR INTERLOCKING -H4:x1 /21.3:E

+BC-X8:6 OG2-L2 2 = L2 -H8:x2 /21.2:E


F

+BC-X8:7 OG2-K7 3 = K7 -X2:4 /20.1:D

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 30
28 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG2-X5 +OG2-X6 +OG2-X7 Current Page 29
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG2-X7 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

+BC-X8:8 OG2-K8 4 TO B/C FOR INTERLOCKING K8 -R94:1 /20.2:C

Strip
+OG2-XAC
B
External targets Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-F4:2 H3 1 230V AC FROM BUSCOUPLER +BC-XAC:3 +BC/35.2:B

-F4:4 H4 2 = +BC-XAC:4 +BC/35.2:B

-F4:2 H3 3 230V AC AUX. SUPPLY TO INCOMER-3 +IC3-XAC:1 +IC3/49.3:B

C
-F4:4 H4 4 = +IC3-XAC:2 +IC3/49.3:B

Strip
External targets
+OG2-XDC Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

D -F6:2 J3 1 110V DC FROM BUSCOUPLER +BC-XDC:3 +BC/35.7:B

-F6:4 J4 2 = +BC-XDC:4 +BC/35.7:B

-F6:2 J3 3 110V DC AUX. SUPPLY TO INCOMER-3 +IC3-XDC:1 +IC3/49.7:B

-F6:4 J4 4 = +IC3-XDC:2 +IC3/49.7:B

Strip
+OG2-XPT
E
External targets Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-PT1-3:1a E10 1 110V AC PT SUPPLY TO METERING +IC3-XPT:1 +IC3/45.5:B

-PT1-3:1a E30 2 = +IC3-XPT:2 +IC3/45.6:B

-PT1-3:1a E50 3 = +IC3-XPT:3 +IC3/45.6:B


F
-PT1-3 E70 4 = +IC3-XPT:4 +IC3/45.6:B

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 31
29 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG2-X7 +OG2-XAC +OG2-XDC +OG2-XPT Current Page 30
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG2-XPT Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-PT1-3:1a E20 5 PT T.B. FOR CL-3P E21 -F01:1 /18.4:E

-PT1-3:1a E40 6 = E41 -F01:3 /18.4:E

-PT1-3:1a E60 7 = E61 -F01:5 /18.4:E


B
-PT1-3 E80 8 = E81 -F01:7 /18.4:E

Strip
External targets
+OG2-XSH Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement
C
-TH:13 1 SPACE HEATER T.B. H6 -F12:2 /23.4:D

-PL:x2 2 = -SH:x2 /23.4:E

Strip
External targets
+OG2-XT1 Internal targets

D
Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 CT SHORTING T.B. FOR METERING D11 -CT1:s1 /18.0:A

-P2-RS1 D12 2 = -E2:1 /18.1:C

3 = D31 -CT2:s1 /18.1:A

-P2-YS1 D32 4 = D10 -CT1:s2 /18.0:A

-P3-6 D71 5 = D51 -CT3:s1 /18.1:B


E
-P2-BS1 D52 6 = D10 -CT1:s2 /18.0:A

7 CT SHORTING T.B. FOR PROTECTION C11 -CT1:s1 /17.0:D

-K51-1 C12 8 = -E2:1 /17.1:F

9 = C31 -CT2:s1 /17.1:E

-K51-3 C32 10 = C10 -CT1:s2 /17.0:D

-K51-10 C71 11 = C51 -CT3:s1 /17.1:E


F

-K51-5 C52 12 = C10 -CT1:s2 /17.0:D

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 32
30 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG2-XPT +OG2-XSH +OG2-XT1 Current Page 31
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG2-XT1 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

13 CT SHORTING T.B. FOR C&R PANEL 87T A11 -CT1:s1 /17.0:B

14 = -E2:1 /17.1:D

15 = A31 -CT2:s1 /17.1:C


B
16 = A10 -CT1:s2 /17.0:B

17 = A51 -CT3:s1 /17.1:C

18 = A10 -CT1:s2 /17.0:B

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page +BC/33
31 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG2-XT1 Current Page 32
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

33kV INCOMING SUPPLY


FROM COMMON BUS-1
R
Y
B

1 3 5
-Q52
/33.7:D NUMERICAL RELAY
/34.2:C
/35.1:B
2 4 6 (50,50N,51,51N,95) 33.3:F 33.3:F
/35.7:B DC+ DC-
1250A, 33kV VCB,
-K51
26.3kA FOR 3 SEC., /34.8:A
3PH. 50Hz /34.9:A -PS K1
/35.5:C
-XT1 AC
4D02 / 34.1:E
/36.1:A 110V DC
C11 1
C12 2 Ia 4
A1

B
K2 AUX SUPPLY
P1 s1 C5 AC
4D03 / 34.1:F
A2
1 3
-CT1
P2
s2 C10 2 C6
Ib A4
WD
2 4 A1 A3
C31 3
C32 C7 RL0
P1 s1 1 3 A2
CORE-1 -CT2
C8 A5

700/1A Ic
CL-5P10, 5VA P2
s2 C30 4
2 4
C9
A7
K13
B6 / 34.9:A
1 3 A1 A6
C TRIP COMMAND
C51 5
C52 C10 RL1 TO TRIP CKT
IN A2 K1
P1 s1 B5 / 34.9:A
2 4 A8
-CT3 C11

P2
s2 C50 6
C71 1 3
A10
C12
L12
B8 / 36.1:A
A1 A9
1 L1 O/C & E/F TRIP
-E2 K11 - +
RL2
34.8:B / D2 TO ANN. CKT
A14 A2
L11
L2 B7 / 36.1:A
TCH FUNCTION K12 - + A11

FOR TRIPPING COIL


34.8:B / D3
A15 L10
D K1 A12
B10 / 35.5:C
34.8:A / D1 A1
A16 TO TCH
RL3 INDICATION
L3 L1
-X5 4 -X5 X41 - + A2
B9 / 35.5:C
3 A13 -Q52
SPARE DI C1
/33.0:A B4 B7
A1 B1
C2
L4 RL4
-X5 6 -X5 X42 - + A2
5
SPARE DI C3 B2

C4 A1 B3
L5
E -X5 8 -X5 X43 - + RL5 B6 B5 B9 B8
7 A2
SPARE DI B5
L6 B4
-X5 10 -X5 X44 - +

X11

X12

X13

X14

X15

X16
9
SPARE DI B6

(S3) 4 -X3 -X6 1 -X6 2 -X6 3 -X6 4 -X6 5 -X6 6


B7 L7 +
-X5 12 -X5 X45 - + D+
RS485 COMM.
SPARE DI
-X5
11

X46
B8
L8
RS-485
-
(S4) 5 -X3 PORT SPARE VCB CONTACT
-X5 14 - +
D-
13
SPARE DI B9 6 -X3
R
F Y B10
B
K2

K1

33.5:B 33.5:B
TO COMMON BUS-2 DC- DC+
CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 34
+OG2/32 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. POWER & CONTROL WIRING DIAGRAM FOR BUSCOUPLER VCB Current Page 33
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

K1 K1 K1

S5 1

K1

K1

K1

K1
L R
A1 A2
A
-LS 9 -K51 K51
K86

K3

K4
/35.5:E /33.3:A /33.3:A
-X2 -X2 D1
S6
/38.3:B
33.3:D B5
2 -X2 5 5 3 5 1
33.5:C
T S6 1
10 12
REMOTE 38.3:D REMOTE REMOTE
N CLOSING C 33.5:C
38.3:D
TRIPPING TRIPPING -S4 4 B6
C -X2 6 N /34.1:C
6
T -X2 11 -X2 13 E.STOP

1K4
B 33.3:D 33.3:D
A
10 D2 D3
-RS

K13
K11

K11

K11

K11
K11
/35.1:E
6 2
SERVICE K5
B 10 10
-RT -RS
/35.2:E /35.1:E 13
6 2 6 2
TEST SERVICE -R94
14
1K5

1K8 K86
/38.3:B
1 1
38.3:B
-S4
9
/34.6:A 2 38.3:C
/35.4:F -R94 -R94 10
2
K6

E.STOP /34.3:B /34.3:B


5 1

K11
6 2

K10

K12
-X2
K8

K9
C
1
EXTERNAL -X2 7 -X2 9 -X2 14 -X2 16
INTERLOCK -X7 4
-Q52
-X2 2 /33.0:A A5 B13 A3 C5
3K4
1K6

39.8:E 1 1 13
INTERLOCKING S91
S11 S12
FROM BC
-X2 4 3 /35.3:C 2 14
39.8:C /35.4:C
3 9 S12
3K3
EXTERNAL S92 4
INTERLOCK
10 1
-X7 3 11
D -X2 4 R1 S92
12 4
K7

C1 C1
B14

K13
F2 F11
C2 C2
15
S2
A4 K86
16 /38.3:B
1
9
S43 38.6:C
2
38.6:D
10
A6
E

-X2 8 -X2 15
K2 K2
VCB ANTI PUMPING VCB AUX. SUPPLY
K1

K2

CLOSING COIL RELAY TRIPING COIL FOR MASTER


4D02 / 33.6:B 5 TRIP RELAY (K86)
AUX. SUPPLY
1 9 /34.2:C
4D03 / 33.6:BTO K51 RELAY 6
1 3 2 10 /34.4:C
-F2
6A 2 4
DP MCB
J3

J4

4D00 4D01
37.5:D 37.5:D

110V DC AUX SUPPLY


CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 35
33 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CLOSING & TRIPPING CONTROL WIRING DIAGRAM FOR BUSCOUPLER Current Page 34
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. VCB FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

11

-RDLS

M1
L1 12

L1

L1

L1

L1
DOOR
LIMIT
B
SWITCH
-X2 26
-X2 17 -X2 19 -X2 21 -X2 23

-Q52
/33.0:A D5 D9 A13 B1 -Q52
/33.0:A S2 A1
1

K86 K51 2
/38.3:B /33.3:A
13 7 B9 -V1
SERVICE TEST 33.5:D
5 13 38.3:D R3 R1
POS. SW. POS. SW. S2 U1
14 S11 S11 38.3:E 33.5:D
C
/34.4:C 6 /34.4:C 14 8 B10 M
-M1
1~
R4
D6 D10 A14 B3 B2 U2
RECT

S2

L10

L11
L4

L5

L7

L8
L3

L9
4

-X2 18 -X2 20 -X2 22 -X2 24 -X2 25


3

A2
D

-X2 27
-X7 1

M2
3K1
39.7:D

TO 3K1 CONT.
39.7:D
A1 x1 x1 A1 x1 3K2 x1 x1 x1 x1 A1 VCB SPRING

M1

M2
-RS -H9 -H10 -RT -H8 -H4 -H5 -H6 -H7 -LS CHARGE MOTOR
A2 x2 x2 A2 x2 x2 x2 x2 x2 A2
-X7 2 3A02 / 36.1:E
E
L2 L2
TOANNUNCIATOR
AUX. VCB IN VCB IN AUX. SPRING VCB ON VCB OFF VCB TRIP TRIP CKT AUX. 3A03 / 36.2:E
L1

L2

RELAY SERVICE TEST RELAY CHARGE HEALTHY RELAY 1 3

6 10 /34.1:B 6 10 /34.1:B 5 -F4


2 2 6A 2 4
1 9 /34.7:A
6 10 /34.1:B DP MCB
6
2 13
S5 1 2 10 /35.5:F

H3

H4
LS 10
1 3 -S4 14 /35.5:E
L R /34.1:C
-F3 A1 A2 E.STOP 6 2
6A EARTHING TB
2 4 -X2 30
X65

X66
X63

X64

DP MCB
EARTHING TB 3A00 3A01
J3

J4

F -X2 28
29
37.1:D 37.2:D
1
-X4 25 26 -X4 27 28 SPARE CONTACT
L/R SWITCH -E1 230V AC
4D04 4D05 E.STOP PB LIMIT SW.
IN REMOTE MODE AUX SUPPLY
37.6:D 37.6:D OPERATED
FEEDBACK
110V DC FEEDBACK
AUX SUPPLY CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 36
34 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CONTROL WIRING DIAGRAM FOR INDICATING LAMP & SPRING Current Page 35
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. CHARGE MOTOR FOR BUSCOUPLER VCB FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

L11
A
K51 -X4 1 -X4 3 -X4 5

/33.3:A
B7 -R3 11
33.5:D SPARE SPARE SPARE -R1 11 /37.8:C
/37.4:B
33.5:C 7 3
7 3
B8 -X4 2 -X4 4 -X4 6

L11
L12

L13

L14

L15

L16

L17
B -AN
1 2 3 4 5 6 COM

O/C & E/F SPARE SPARE SPARE AC FAIL DC FAIL


WITH HIGHEST
TRIP

POWER ON

6 WINDOW ANNUNCIATOR
TEST
C

ACCEPT

RESET
P N C NO T A R E

1
E
L33

L34

L35

-X4 9 -X4 11 -X4 13 -X4 15 -X4 17 -X4 19 -X4 21

H1 H3 H5 H7 H9 H11 H13
+OG1/8.3:D +OG2/23.3:D +IC3/50.3:D +IC4/63.3:D +OG3/77.2:D
9 10
FROM FROM FROM FROM FROM FROM FROM
-R3 -R3
/37.8:C 5 1 /37.8:C 6 2
OG-1 IC-2 IC-1 OG-2 IC-3 IC-4 OG-3
+OG1/8.3:D +OG2/23.3:D +IC3/50.3:D +IC4/63.3:D +OG3/77.3:D
L31

L32

H2 H4 H6 H8 H10 H12 H14

-X4 10 -X4 12 -X4 14 -X4 16 -X4 18 -X4 20 -X4 22

E
1 3
-F6 -X4 23
6A x1
L34

2 4
DP MCB
-H
M1

M2
J3

J4

x2

-X4 24
-3A02 -3A03
4D06 4D07 35.7:E 35.7:E
37.7:D 37.7:D 230V AC HOOTER
110V DC AUX SUPPLY
F AUX SUPPLY

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 37
35 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CONTROL WIRING DIAGRAM OF ANN. WINDOW FOR BUSCOUPLER Current Page 36
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. VCB FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

A
230V AC AUX. SUPPLY 110V DC AUX. SUPPLY
FROM OUTGOING-1 FROM OUTGOING-1
+OG1/9.2:B +OG1/9.2:B +OG1/9.8:B +OG1/9.8:B
2ACP 2ACN 2DCP 2DCN

-XAC 1 2
-XDC 1 2

H3

H4
B -XAC
+OG2/24.3:A / +OG2-2ACP1
3
230V AC AUX. SUPPLY
-XDC
TO OUTGOING-2 -XAC +OG2-2DCP1 / +OG2/24.7:A
+OG2/24.3:A / +OG2-2ACN1 3
4 110V DC AUX. SUPPLY
-XDC TO OUTGOING-2
7 +OG2-2DCN1 / +OG2/24.7:A
A1 3 11 /36.4:A 4
-R1
A2

AC FAIL 5
A1 1 9 /36.1:D
RELAY
230V AC SUPPLY -R3 6
C
A2 2 10 /36.2:D
7
3 11 /36.4:A
DC FAIL
RELAY
H3

H4

H3

H4

J3

J4
3A00 3A01 110V DC SUPPLY
35.6:F 35.7:F
1

D TO VCB SPRING -F11 NL


CHARGE MOTOR 6A 2

J3

J4

J3

J4

J3

J4
H5

H9
11
4D00 4D01 4D04 4D05 4D06 4D07
35.0:F 35.0:F 36.0:F 36.1:F
-DLS 12
34.0:F 34.1:F
DOOR
LIMIT TO CLOSING & TO INDICAION TO ANN. WINDOW
SWITCH TRIPPING CIRCUIT CIRCUIT CIRCUIT
H12

E x1

-PL

x2

PANEL
LIGHT
HOLDER

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 38
36 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. AC & DC VOLTAGE CIRCUIT FOR BUSCOUPLER VCB FEEDER Current Page 37
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

MASTER TRIP RELAY (K86)


-K86
/34.3:B
/34.5:A
B /34.9:D
/35.4:C

K8
34.3:B / 1
1
1

TO CLOSING COIL
2
K9
34.3:C / 2
2

-X5 1 X31
C
3
3
SPARE NO CONTACT
4

-X5 2 X32 9 K13


4 9 / 34.9:D

K1 K1 10 K2
34.5:A / 5 10 / 34.9:E
5
5
TO TRIPING COIL
6
D K11
34.5:A / 6
6

L1
35.4:C / 7
7
7
TO TRIP LAMP
8
L9
35.4:C / 8
8

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 39
37 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. MACRO FOR MASTER TRIP RELAY (K86) OF BUSCOUPLER VCB Current Page 38
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

INTERLOCKING TRUTH TABLE

SR. NO. OG-1 BC OG-2


A

1) ON OFF ON
2) ON ON OFF
3) OFF ON ON

C
FOR OUTGOING-1 OF GRID FOR OUTGOING-2 OF GRID FOR BUSCOUPLER

K7
34.2:D / 3K3
OG1-K7 OG2-K7
+OG1/6.2:D / 1K3 +OG2/21.2:D / 2K3
-X8 11

-X8 3 -X8 7

L7 -X8 9
35.3:D / -3K1
OG1-L7 -X8 1 OG2-L7 -X8 5
+OG1/7.3:D / 1K1 +OG2/22.3:D / 2K1 A1 31 31
D
A1 11 11 A1 31 11 -3K1 1K1 OG1 2K1 OG2
A2 /39.1:D 32 /39.4:D 32
-1K1 3K1 BC 2K1 OG2 -2K1 3K1 BC 1K1 OG1
/39.7:D 12 /39.4:D 12 /39.7:D 32 /39.1:D 12 L2 -X8 10
A2 A2 35.3:E / -3K2
OG1-L2 -X8 2 OG2-L2 -X8 6
+OG1/7.3:E / 1K2 +OG2/22.3:E / 2K2 11 12 /39.2:D
31 32 /39.5:D
11 12 /39.5:D 11 12 /39.2:D
31 32 /39.8:D 31 32 /39.9:D -X8 12

-X8 4 -X8 8
K8
34.2:C / 3K4
OG1-K8 OG2-K8
+OG1/6.2:C / 1K4 +OG2/21.2:C / 2K4
TO CLOSING COIL
E
TO CLOSING COIL TO CLOSING COIL

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 40
38 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. INTERLOCKING DIAGRAM FOR OG-1, OG-2 & BUSCOUPLER FEEDER Current Page 39
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+BC-X2 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-S4:2 K6 1 EXTERNAL INTERLOCK

2 =

3 =
B
-X7:3 K7 4 =

-A2 5 REMOTE CLOSE CMD

-RS:10 1K4 6 =

-Q52-A5 7 CLOSING CIRCUIT K9 -K86-2 /36.3:C

-F2:3 K2 8 = -Q52-A6 /32.3:E

-Q52-B13 9 CLOSING CIRCUIT (ANTIPUMPING) K10 -R94:14 /32.3:B


C

-K86-5 K1 10 REMOTE TRIP CMD

-K86-6 K11 11 =

-S4:3 K1 12 =

-S4:4 K11 13 =

-Q52-A3 14 TRIPPING CIRCUIT K11 -K86-6 /36.3:D

D 15 = -Q52-A4 /32.4:D

-Q52-C5 16 TCH K12 -K51-A15 /31.4:D

-Q52-D5 17 VCB IN SERVICE POSITION L1 -F3:1 /33.0:F

-H9:x1 18 = L3 -Q52-D6 /33.1:C

-Q52-D9 19 VCB IN TEST POSITION

-H10:x1 20 = L4 -Q52-D10 /33.2:C


E
-Q52-A13 21 VCB SPRING CHARGE INDI.

-H8:x1 22 = L5 -Q52-A14 /33.2:C

-Q52-B1 23 VCB ON L1 -K86-7 /36.3:D

-H4:x1 24 = L7 -Q52-B3 /33.3:C

-H5:x1 25 VCB OFF L8 -Q52-B2 /33.4:C

-Q52-A1 26 SPRING CHARGE MOTOR M1 -F4:1 /33.6:E


F

-F4:3 M2 27 = -Q52-A2 /33.8:D

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 41
39 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +BC-X2 Current Page 40
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+BC-X2 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

28 SPARE CONTACT LIMIT SW. -LS:10 /33.5:F

-LS:6 29

-E1:1 30 EARTHING TB
B

Strip
External targets
+BC-X3 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-K51-D+ (S3) 4 K51 RELAY RS485

C
-K51-D- (S4) 5 =

6 =

Strip
External targets
+BC-X4 Internal targets

D
Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 SPARE ANN. WINDOW L11 -K51-A11 /31.5:D

2 = L13 -AN-2 /34.2:B

3 =

4 = L14 -AN-3 /34.3:B

5 =
E
6 = L15 -AN-4 /34.3:B

7 = -R3:11 /34.4:A

8 = L16 -AN-5 /34.4:B

+OG1-X4:5 9 HOOTER CMD FROM OG-1 (GRID)

10 = +OG1-X4:6 +OG1/8.3:D

11 HOOTER CMD FROM IC-2 OF BUS-1


F

12 =

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 42
40 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +BC-X2 +BC-X3 +BC-X4 Current Page 41
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+BC-X4 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

13 HOOTER CMD FROM IC-1 OF BUS-1

14 =

+OG2-X4:5 15 HOOTER CMD FROM OG-2 (GRID)


B
16 = +OG2-X4:6 +OG2/22.3:D

+IC3-X4:9 17 HOOTER CMD FROM IC-3 OF BUS-2

18 = +IC3-X4:10 +IC3/48.3:D

+IC4-X4:9 19 HOOTER CMD FROM IC-4 OF BUS-2

20 = +IC4-X4:10 +IC4/60.3:D

+OG3-X4:17 21 HOOTER CMD FROM OG-3 OF BUS-2


C

22 = +OG3-X4:18 +OG3/73.3:D

-H:x1 23 TO OUTDOOR HOOTER

-R3:10 L34 24 = -H:x2 /34.3:E

25 L/R SWITCH IN REMOTE MODE FEEDBACK X63 -1 /33.3:F

26 = X64 -A2 /33.3:F

D 27 E.STOP PB OPERATED FEEDBACK X65 -S4:13 /33.4:F

28 = X66 -S4:14 /33.4:F

Strip
External targets
+BC-X5 Internal targets

E Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-K86-3 X31 1 SPARE NC CONTACT (K86 RELAY)

-K86-4 X32 2 =

3 K51 RELAY SPARE DI X41 -K51-C1 /31.4:D

4 = K2 -F2:3 /32.0:F

5 = X42 -K51-C3 /31.4:E


F
6 = K2 -F2:3 /32.0:F

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 43
41 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +BC-X4 +BC-X5 Current Page 42
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+BC-X5 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

7 K51 RELAY SPARE DI X43 -K51-B5 /31.4:E

8 = K2 -F2:3 /32.0:F

9 = X44 -K51-B6 /31.4:E


B
10 = K2 -F2:3 /32.0:F

11 = X45 -K51-B8 /31.4:F

12 = K2 -F2:3 /32.0:F

13 = X46 -K51-B9 /31.4:F

14 = K2 -F2:3 /32.0:F

Strip
External targets
+BC-X6 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 SPARE VCB C/O CONTACT X11 -Q52-B4 /31.8:D

2 = X12 -Q52-B6 /31.8:E


D

3 = X13 -Q52-B5 /31.8:E

4 = X14 -Q52-B7 /31.9:D

5 = X15 -Q52-B9 /31.9:E

6 = X16 -Q52-B8 /31.9:E

E Strip
External targets
+BC-X7 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-X8:9 1 TO B/C FOR INTERLOCKING -H4:x1 /33.3:E

-X8:10 2 = L2 -H8:x2 /33.2:E

-X8:11 3 FOR CLOSING INTERLOCKING K7 -X2:4 /32.1:D


F

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 44
42 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +BC-X5 +BC-X6 +BC-X7 Current Page 43
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+BC-X7 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-X8:12 4 FOR CLOSING INTERLOCKING K8 -R94:1 /32.2:C

Strip
+BC-X8
B
External targets Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-1K1:A1 1 230V AC SUPPLY FROM OG-1 OG1-L7 +OG1-X7:1 +OG1/7.3:D

-1K1:A2 2 = OG1-L2 +OG1-X7:2 +OG1/7.3:E

-3K1:11 3 TO CLOSING COIL INTERLOCK IN OG-1 OG1-K7 +OG1-X7:3 +OG1/6.2:D

C
+OG1-X7:4 OG1-K8 4 = -3K1:12 /37.2:D

-2K1:A1 5 AUX. SUPPLY FROM OG-2 OG2-L7 +OG2-X7:1 +OG2/21.3:D

-2K1:A2 6 = OG2-L2 +OG2-X7:2 +OG2/21.3:E

-3K1:31 7 TO CLOSING COIL INTERLOCK IN OG-2 OG2-K7 +OG2-X7:3 +OG2/20.2:D

+OG2-X7:4 OG2-K8 8 = -3K1:32 /37.5:D

-3K1:A1 9 AUX. SUPPLY FROM BUSCOUPLER -X7:1 /33.3:D


D

-3K1:A2 10 = -X7:2 /33.3:E

-1K1:31 11 TO CLOSING COIL INTERLOCK IN BUSCOUPLER -X7:3 /32.2:D

-X7:4 12 = -1K1:32 /37.8:D

Strip
E
External targets
+BC-XAC Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-F4:2 H3 1 230V AC FROM OUTGOING-1 +OG1-XAC:5 +OG1/9.2:B

-F4:4 H4 2 = +OG1-XAC:6 +OG1/9.2:B

-F4:2 H3 3 230V AC AUX. SUPPLY TO OUTGOING-2 +OG2-XAC:1 +OG2/23.3:B

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 45
43 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +BC-X7 +BC-X8 +BC-XAC Current Page 44
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+BC-XAC Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-F4:4 H4 4 230V AC AUX. SUPPLY TO OUTGOING-2 +OG2-XAC:2 +OG2/23.3:B

Strip
+BC-XDC
B
External targets Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-F6:2 J3 1 110V DC FROM OUTGOING-1 +OG1-XDC:5 +OG1/9.7:B

-F6:4 J4 2 = +OG1-XDC:6 +OG1/9.7:B

-F6:2 J3 3 110V DC AUX. SUPPLY TO OUTGOING-2 +OG2-XDC:1 +OG2/23.7:B

C
-F6:4 J4 4 = +OG2-XDC:2 +OG2/23.7:B

Strip
External targets
+BC-XT1 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

D 1 CT SHORTING T.B. FOR PROTECTION C11 -CT1:s1 /31.0:B

-K51-C5 C12 2 = -E2:1 /31.1:D

3 = C31 -CT2:s1 /31.1:C

-K51-C7 C32 4 = C10 -CT1:s2 /31.0:B

-K51-C12 C71 5 = C51 -CT3:s1 /31.1:C

-K51-C9 C52 6 = C10 -CT1:s2 /31.0:B


E

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page +IC3/46
44 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +BC-XAC +BC-XDC +BC-XT1 Current Page 45
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

33kV INCOMING SUPPLY-3


FROM 11.6MVA PANEL NOTE:- INCOMER-1 CONTROL WIRING WILL BE SAME AS INCOMER-3
R Y B
SA
R R
1
A
Y Y -E1

B B
NUMERICAL RELAY
CBCTS1 / 46.3:C (50,50N,51,51N,95,94F) 46.4:F 46.3:F
CBCT DC+ DC-
TO K51 RELAY -K51
350/1A /48.8:A
CBCTS2 / 46.3:C /48.9:A -PS
/49.4:C
K1
-XT1 AC
4D02 / 48.1:E
/50.1:A 110V DC
C11 7
C12 2 Ia 4
A1
K2 AUX SUPPLY
P1 s1 C5 AC
4D03 / 48.1:F
B A2
1 3
-CT1
/47.0:B
P2
s2 C10 8 C6
Ib A4
WD
2 4 A1 A3
C31 9
C32 C7 RL0
P1 s1 1 3 A2
CORE-2 -CT2
C8 A5

350/1A Ic
CL-5P10, 5VA
/47.1:B
P2
s2 C30 10
2 4
C9
A7
K13
B6 / 48.9:A
1 3 A1 A6
TRIP COMMAND
C51 11
C52 C10 RL1 TO TRIP CKT
C
IN A2
K1
P1 s1 B5 / 48.9:A
1C11 2 4 A8
-CT3 46.1:A / CBCTS1
C11
/47.1:C
P2
s2 C50 12
C71 1C10 1 3
46.1:B / CBCTS2
C12
A10
L12
B8 / 50.1:A
1 A1 A9
L1 O/C & E/F TRIP
-E2 K11 - +
RL2
48.8:B / D2 TO ANN. CKT
A14 A2 L11
L2 B7 / 50.1:A
TCH FUNCTION K12 - + A11

FOR TRIPPING COIL


48.8:B / D3
A15 L10
K1 A12
B10 / 49.5:D
48.8:A / D1 A1
D A16 TO TCH
RL3 INDICATION
L3 L1
-X5 4 -X5 X41 - + A2
B9 / 49.5:C
3 A13
SPARE DI C1

A1 B1 -Q52
C2 B4 B7
L4 RL4
-X5 6 -X5 X42 - + A2
5
SPARE DI C3 B2

C4 A1 B3
L5
-X5 8 -X5 X43 - + RL5
7 A2
E
SPARE DI B5
L6 B6 B5 B9 B8
-X5 10 -X5 X44 - +
B4

9
SPARE DI B6

(S3) 4 -X3

X11

X12

X13

X14

X15

X16
B7 L7 +
-X5 12 -X5 X45 - + D+
11
RS485 COMM.
SPARE DI B8 RS-485 (S4) 5 -X3 PORT -X6 1 -X6 2 -X6 3 -X6 4 -X6 5 -X6 6

-X5 X46 L8 -
-X5 14 - +

SPARE VCB CONTACT


D-
13
SPARE DI B9 6 -X3

B10
K2

K1

R Y B
47.0:A 47.1:A 47.1:A
46.6:B 46.6:B
TO NEXT SHEET DC- DC+
CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 47
+BC/45 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. POWER & CONTROL DIAGRAM FOR INCOMER-3 VCB FEEDER Current Page 46
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

FROM PREVIOUS SHEET NOTE:- INCOMER-2 CONTROL WIRING WILL BE SAME AS INCOMER-3
46.0:F 46.1:F 46.1:F
R Y B
110V AC SUPPLY
FROM OUTGOING-2 ON BUS-2
A

+OG2-VN2 / +OG2/19.7:E
+OG2-VR2 / +OG2/19.6:E

+OG2-VB2 / +OG2/19.7:E
+OG2-VY2 / +OG2/19.6:E
-XT1
D11 1
D12
P1 s1
-CT1
/46.0:B -XPT 1 2 3 4
P2
s2 D10 2

IC3-E11

IC3-E31

IC3-E51

IC3-E71
B

D31 3
D32
P1 s1
CORE-1 -CT2 1VR2 / +IC4/60.5:B
350/1A /46.1:B
CL-1, 5VA P2
s2 D30 4
1VY2 / +IC4/60.6:B110V AC SUPPLY
TO NEXT FEEDER ON BUS-2
1VB2 / +IC4/60.6:B

D51 5
D52 1VN2 / +IC4/60.6:B
1 3 5 7
P1 s1 -F1
6A
C -CT3 2 4 6 8
FP MCB
/46.1:C
P2
s2 D50 6
D71

E12

E32

E52

E72
1
-E2

E12

E32

E52

E72
D13

D33

D53

D13

D33

D53
D
-P2 -P3 1 2 3 4 5 6 8 9 10 11
DA MFM
RS1 RS2 YS1 YS2 BS1 BS2
DIGITAL AMMETER WITH INBUILT S1 S2 S1 S2 S1 S2 V1 V2 V3 VN
SELECTOR SWITCH
1 3 5 12 13 MULTI FUNCTION METER
-Q52
/46.7:D
/48.2:C
PH N RS 485
2 4 6
/49.1:C
/49.6:B 12 13 7 14
630A, 33kV VCB,

(S1)

(S2)
26.3kA FOR 3 SEC.,
3PH. 50Hz

E -X3 1 2 3
E12
E32

F
R
Y
B

TO COMMON BUS-2

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 48
46 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. POWER & METERING WIRING DIAGRAM FOR INCOMER-3 VCB Current Page 47
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

K1 K1 K1

S5 1

K1

K1

K1

K1

K1

K1
L R
A1 A2
A
-LS 9 -K51 K51
K86

K3

K4
/49.5:E /46.4:A /46.4:A
-X2 -X2 -X2 -X2 D1
/52.3:B
46.3:D B5
S6 -X2 5
5 3 5 1
46.6:C
2 S6 1
10 12 14 16
REMOTE 52.3:D
T CLOSING C REMOTE REMOTE REMOTE REMOTE
46.6:C
N 52.3:D
TRIPPING TRIPPING TRIPPING TRIPPING -S4 4 B6
-X2 6 N LT PANEL-1 LT PANEL-2
/48.1:C
C 6
T -X2 11 -X2 13 -X2 15 -X2 17 E.STOP
46.3:D

1K4
B 46.3:D
A
D2 D3
10

K13
-RS

K11

K11

K11

K11

K11

K11
K11
/49.1:E
6 2
SERVICE K5
B 10 10
-RT -RS 13
/49.2:E /49.1:E
6 2 6 2
TEST SERVICE -R94

K8
14
K86
1K5

9 /52.3:B
-R94 1
1 /48.3:B 52.3:B
5 1
-S4 52.3:C
/48.7:A
/49.4:F
2 2 -R94 10
K7
K6

/48.3:B
E.STOP

K11
6 2

K10

K12
-X2

K9
C
1 -X2
EXTERNAL -X2 7 -X2 9 -X2 18 -X2 20
INTERLOCK 4
EXTERNAL -Q52
-X2 2 INTERLOCK A5 B13 A3 C5

-X2 3 1 1 13
1K6

S91
S11 S12
4 3 /49.3:C 14
2
/49.3:C
9 S12
S92 4
10 1
11
D R1 S92
12 4
C1 C1
B14

K13
F2 F11
C2 C2
15
S2
A4 K86
16 /52.3:B
1
9
S43 52.6:C
2
52.6:D
10
A6
E

-X2 8 -X2 19
K2 K2
VCB ANTI PUMPING VCB AUX. SUPPLY
K1

K2

CLOSING COIL RELAY TRIPING COIL FOR MASTER


4D02 / 46.6:B 5 TRIP RELAY (K86)
AUX. SUPPLY
1 9 /48.2:B
4D03 / 46.6:BTO K51 RELAY 6
1 3 2 10 /48.4:C
-F2
6A 2 4
DP MCB
J3

J4

4D00 4D01
51.5:D 51.5:D

110V DC AUX SUPPLY


CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 49
47 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CLOSING & TRIPPING CONTROL WIRING DIAGRAM FOR INCOMER-3 Current Page 48
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. VCB FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

M1
11
-X2 30
-RDLS 12
DOOR
LIMIT
B
SWITCH
-Q52
S2 A1
1

2
L1

L1

L1

L1

L1
-V1
R3 R1
-X2 21 -X2 23 -X2 25 -X2 27 U1

M
-Q52 -M1
D5 D9 A13 B1 1~
R4
C U2
RECT
K86 K51
/52.3:B /46.4:A S2
13 7 B9 4
SERVICE TEST 46.6:D
5 13 52.3:D
POS. SW. POS. SW. S2
3
14 S11 S11 52.3:E 46.6:D
/48.4:C 6 /48.4:C 14 8 B10
A2

D6 D10 A14 B3 B2
-X2 31

L10

M2
L4

L5

L7

L8
L3

L9
-X2 22 -X2 24 -X2 26 -X2 28 -X2 29

VCB SPRING
CHARGE MOTOR

A1 x1 x1 A1 x1 x1 x1 x1 x1 A1 3A02 / 50.1:E
-RS -H9 -H10 -RT -H8 -H4 -H5 -H6 -H7 -LS TOANNUNCIATOR
3A03 / 50.2:E
E A2 x2 x2 A2 x2 x2 x2 x2 x2 A2
L2 L2

M1

M2
AUX. VCB IN VCB IN AUX. SPRING VCB ON VCB OFF VCB TRIP TRIP CKT AUX.
L1

L2

HEALTHY RELAY
1 3
RELAY SERVICE TEST RELAY CHARGE -F4
6 10 /48.1:B 6 10 /48.1:B 5 6A 2 4
2 2 1 9 /48.7:A DP MCB
6 10 /48.2:B 6
1 3 13
S5

H3

H4
2 1 2 10 /49.4:F
-F3 LS 10
6A
-S4 14 /49.5:E
DP MCB
2 4 L R /48.1:C
A1 A2 E.STOP 6 2
J3

J4

X65

X66
X63

X64

-X2 34 EARTHING TB 3A00 3A01


F -X2 32
33
EARTHING TB 51.1:D 51.2:D

4D04 4D05 -X4 11 12 -X4 13 14 SPARE CONTACT 1 230V AC


L/R SWITCH
51.6:D 51.6:D E.STOP PB LIMIT SW. -E1 AUX SUPPLY
IN REMOTE MODE
OPERATED
110V DC FEEDBACK
FEEDBACK
AUX SUPPLY CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 50
48 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CONTROL WIRING DIAGRAM FOR INDICATING LAMP & SPRING Current Page 49
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. CHARGE MOTOR FOR INCOMER-3 VCB FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

L11
A
K51 -X4 1 -X4 3 -X4 5

/46.4:A
B7 -R1 11 -R3 11
46.6:D SPARE SPARE SPARE /51.4:C /51.7:C

46.6:C 7 3 7 3

B8 -X4 2 -X4 4 -X4 6

L11
L12

L13

L14

L15

L16

L17
B -AN
1 2 3 4 5 6 COM

O/C & E/F SPARE SPARE SPARE AC FAIL DC FAIL


WITH HIGHEST
TRIP

POWER ON

6 WINDOW ANNUNCIATOR
TEST
C

ACCEPT

RESET
P N C NO T A R E

1
L35

L36

E
L33

L34

D
-X4 9 -X4 10
9 10
-R3 -R3
/51.7:C 5 1 /51.7:C 6 2
+BC-H9 +BC-H10
L31

L32

+BC/36.5:D +BC/36.5:E

TO COMMON HOOTER
IN BUSCOUPLER

1 3
-F6
E 6A 2 4
DP MCB
M1

M2
J3

J4

-3A02 -3A03
4D06 4D07 49.6:E 49.6:E
51.6:D 51.7:D 230V AC
110V DC AUX SUPPLY
AUX SUPPLY

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 51
49 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CONTROL WIRING DIAGRAM OF ANN. WINDOW FOR INCOMER-3 VCB Current Page 50
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

230V AC AUX. SUPPLY 110V DC AUX. SUPPLY


FROM OUTGOING-2 FROM OUTGOING-1
+OG2/24.2:B +OG2/24.2:B +OG2/24.8:B +OG2/24.8:B
+OG2-2ACP2 +OG2-2ACN2 +OG2-2DCP2 +OG2-2DCN2

-XAC 1 2
-XDC 1 2
B

H3

H4

J3

J4
-XAC
+IC4/64.3:A / 2ACP3 -XDC
230V AC AUX. SUPPLY 3 2DCP3 / +IC4/64.7:A
3 230V AC AUX. SUPPLY
TO INCOMER-4 (BUS-2) -XAC
+IC4/64.3:A / 2ACN3 -XDC TO INCOMER-4 (BUS-2)
4 2DCN3 / +IC4/64.7:A
4

7
A1 3 11 /50.4:A
-R1
5
C
A2 A1 1 9 /50.1:D
-R3 6
AC FAIL 2 10 /50.2:D
A2
RELAY 7
3 11 /50.4:A
230V AC SUPPLY DC FAIL
RELAY
H3

H4

H3

H4
110V DC SUPPLY
D

3A00 3A01
49.6:F 49.6:F
1 1

J3

J4

J3

J4

J3

J4
TO VCB SPRING -F11 -F12 NL
CHARGE MOTOR 6A 2 6A 2

4D00 4D01 4D04 4D05 4D06 4D07


H6

H9

48.0:F 48.1:F 49.0:F 49.0:F 50.0:E 50.1:E


11
H5

TO CLOSING & TO INDICAION TO ANN. WINDOW


-DLS TRIPPING CIRCUIT CIRCUIT CIRCUIT
DOOR
12 -XSH 1
LIMIT 13
E
PS SWITCH
TH
1
3 14
H12

2
H7

x1 x1

-SH
-PL 80W
x2

x2 -XSH 2

PLUG PANEL SPACE


F
SOCKET LIGHT HEATER
HOLDER

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 52
50 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. AC & DC VOLTAGE CIRCUIT FOR INCOMER-3 VCB FEEDER Current Page 51
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

MASTER TRIP RELAY (K86)


-K86
/48.3:B
/48.5:A
B /48.9:D
/49.4:C

K8
48.3:B / 1
1
1

TO CLOSING COIL
2
K9
48.3:C / 2
2

-X5 1 X31
C
3
3
SPARE NO CONTACT
4

-X5 2 X32 9 K13


4 9 / 48.9:D

K1 K1 10 K2
48.5:A / 5 10 / 48.9:E
5
5
TO TRIPING COIL
6
D K11
48.5:A / 6
6

L1
49.4:C / 7
7
7
TO TRIP LAMP
8
L9
49.4:D / 8
8

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 53
51 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. MACRO FOR MASTER TRIP RELAY (K86) OF INCOMER-3 VCB FEEDER Current Page 52
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+IC3-X2 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-S4:2 K6 1 EXTERNAL INTERLOCK

2 =

3 =
B
-R94:1 K7 4 =

-A2 5 REMOTE CLOSE CMD

-RS:10 6 =

-Q52-A5 7 CLOSING CIRCUIT K9 -K86-2 /50.3:C

-F2:3 K2 8 = -Q52-A6 /46.3:E

-Q52-B13 9 CLOSING CIRCUIT (ANTIPUMPING) K10 -R94:14 /46.3:B


C

-K86-5 K1 10 REMOTE TRIP CMD

-K86-6 K11 11 =

12 =

13 =

14 REMOTE TRIPPING LT PANEL-1

D 15 =

-S4:3 K1 16 REMOTE TRIPPING LT PANEL-2

-S4:4 K11 17 =

-Q52-A3 18 TRIPPING CIRCUIT K11 -K86-6 /50.3:D

19 = -Q52-A4 /46.4:D

-Q52-C5 20 TCH K12 -K51-A15 /44.4:D


E
-Q52-D5 21 VCB IN SERVICE POSITION L1 -F3:1 /47.0:F

-H9:x1 22 = L3 -Q52-D6 /47.1:D

-Q52-D9 23 VCB IN TEST POSITION

-H10:x1 24 = L4 -Q52-D10 /47.2:D

-Q52-A13 25 VCB SPRING CHARGE INDI.

-H8:x1 26 = L5 -Q52-A14 /47.3:D


F

-Q52-B1 27 VCB ON L1 -K86-7 /50.3:D

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 54
52 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +IC3-X2 Current Page 53
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+IC3-X2 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-H4:x1 28 VCB ON L7 -Q52-B3 /47.3:D

-H5:x1 29 VCB OFF L8 -Q52-B2 /47.3:D

-Q52-A1 30 SPRING CHARGE MOTOR M1 -F4:1 /47.6:E


B
-F4:3 M2 31 = -Q52-A2 /47.7:D

32 SPARE CONTACT LIMIT SW. -LS:10 /47.4:F

-LS:6 33

-E1:1 34 EARTHING TB

C
Strip
External targets
+IC3-X3 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 MFM RS-485 (S1) -P3-7 /45.6:E

2 = (S2) -P3-14 /45.6:E

3 = /44.5:F
D

-K51-D+ (S3) 4 K51 RELAY RS485

-K51-D- (S4) 5 =

6 =

Strip
E
External targets
+IC3-X4 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 SPARE ANN. WINDOW L11 -K51-A11 /44.5:D

2 = L13 -AN-2 /48.2:B

3 =

4 = L14 -AN-3 /48.3:B


F

5 =

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 55
53 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +IC3-X2 +IC3-X3 +IC3-X4 Current Page 54
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+IC3-X4 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

6 SPARE ANN. WINDOW L15 -AN-4 /48.3:B

7 = -R3:11 /48.4:A

8 = L16 -AN-5 /48.4:B


B
+BC-X4:17 9 TO COMMON HOOTER IN BC

+BC-X4:18 10 =

11 L/R SWITCH IN REMOTE MODE FEEDBACK X63 -1 /47.2:F

12 = X64 -A2 /47.3:F

13 E.STOP PB OPERATED FEEDBACK X65 -S4:13 /47.4:F

14 = X66 -S4:14 /47.4:F


C

Strip
External targets
+IC3-X5 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-K86-3 X31 1 SPARE NC CONTACT (K86 RELAY)


D

-K86-4 X32 2 =

3 K51 RELAY SPARE DO

3 K51 RELAY SPARE DI X41 -K51-C1 /44.4:D

4 = K2 -F2:3 /46.0:F

4 K51 RELAY SPARE DO

E 5 =

5 K51 RELAY SPARE DI X42 -K51-C3 /44.4:E

6 = K2 -F2:3 /46.0:F

6 K51 RELAY SPARE DO

7 K51 RELAY SPARE DI X43 -K51-B5 /44.4:E

8 = K2 -F2:3 /46.0:F
F
9 = X44 -K51-B6 /44.4:E

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 56
54 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +IC3-X4 +IC3-X5 Current Page 55
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+IC3-X5 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

10 K51 RELAY SPARE DI K2 -F2:3 /46.0:F

11 = X45 -K51-B8 /44.4:E

12 = K2 -F2:3 /46.0:F
B
13 = X46 -K51-B9 /44.4:F

14 = K2 -F2:3 /46.0:F

Strip
External targets
+IC3-X6 Internal targets

C
Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 SPARE VCB C/O CONTACT X11 -Q52-B4 /44.8:D

2 = X12 -Q52-B6 /44.8:E

3 = X13 -Q52-B5 /44.8:E

4 = X14 -Q52-B7 /44.9:D

5 = X15 -Q52-B9 /44.9:E


D

6 = X16 -Q52-B8 /44.9:E

Strip
External targets
+IC3-XAC Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement
E
-F4:2 H3 1 230V AC FROM OUTGOING-2 +OG2-XAC:3 +OG2/23.2:B

-F4:4 H4 2 = +OG2-XAC:4 +OG2/23.2:B

-F4:2 H3 3 230V AC AUX. SUPPLY TO INCOMER-4 +IC4-XAC:1 +IC4/61.3:B

-F4:4 H4 4 = +IC4-XAC:2 +IC4/61.3:B

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 57
55 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +IC3-X5 +IC3-X6 +IC3-XAC Current Page 56
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+IC3-XDC Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-F6:2 J3 1 110V DC FROM OUTGOING-2 +OG2-XDC:3 +OG2/23.7:B

-F6:4 J4 2 = +OG2-XDC:4 +OG2/23.7:B

-F6:2 J3 3 110V DC AUX. SUPPLY TO INCOMER-4 +IC4-XDC:1 +IC4/61.7:B


B
-F6:4 J4 4 = +IC4-XDC:2 +IC4/61.7:B

Strip
External targets
+IC3-XPT Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement
C
-F1:1 IC3-E11 1 110V AC SUPPLY FROM OG-2 +OG2-XPT:1 +OG2/18.4:E

-F1:3 IC3-E31 2 = +OG2-XPT:2 +OG2/18.4:E

-F1:5 IC3-E51 3 = +OG2-XPT:3 +OG2/18.4:E

-F1:7 IC3-E71 4 = +OG2-XPT:4 +OG2/18.4:E

Strip
D
External targets
+IC3-XSH Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-TH:13 1 SPACE HEATER T.B. H6 -F12:2 /49.3:D

-PL:x2 2 = -SH:x2 /49.3:E

Strip
External targets
+IC3-XT1 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 CT SHORTING T.B. FOR METERING D11 -CT1:s1 /45.0:B

-P2-RS1 D12 2 = -E2:1 /45.1:C


F
3 = D31 -CT2:s1 /45.1:B

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 58
56 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +IC3-XDC +IC3-XPT +IC3-XSH +IC3-XT1 Current Page 57
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+IC3-XT1 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-P2-YS1 D32 4 CT SHORTING T.B. FOR METERING D10 -CT1:s2 /45.0:B

-P3-6 D71 5 = D51 -CT3:s1 /45.1:C

-P2-BS1 D52 6 = D10 -CT1:s2 /45.0:B


B
7 CT SHORTING T.B. FOR PROTECTION C11 -CT1:s1 /44.0:B

-K51-C5 C12 8 = -E2:1 /44.1:C

9 = C31 -CT2:s1 /44.1:B

-K51-C7 C32 10 = C10 -CT1:s2 /44.0:B

-K51-C6 C71 11 = C51 -CT3:s1 /44.1:C

-K51-C9 C52 12 = C10 -CT1:s2 /44.0:B


C

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page +IC4/59
57 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +IC3-XT1 Current Page 58
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

33kV INCOMING SUPPLY-4


FROM 17.4MVA PANEL NOTE:- INCOMER-2 CONTROL WIRING WILL BE SAME AS INCOMER-4
R Y B

SA
R R
A 1

Y Y -E1

B B
NUMERICAL RELAY
CBCTS1 / 59.3:C (50,50N,51,51N,95,94F) 59.4:F 59.3:F
DC+ DC-
CBCT TO K51 RELAY -K51
/61.8:A
250/1A CBCTS2 / 59.3:C /61.9:A -PS
/62.5:C
K1
-XT1 AC
4D02 / 61.1:E
/63.1:A 110V DC
C11 7
C12 2 Ia 4
A1
K2 AUX SUPPLY
P1 s1 C5 AC
4D03 / 61.1:F
B A2
1 3
-CT1
/60.0:B
P2
s2 C10 8 C6
Ib A4
WD
2 4 A1 A3
C31 9
C32 C7 RL0
P1 s1 1 3 A2
CORE-2 -CT2
C8 A5

250/1A Ic
CL-5P10, 5VA
/60.1:B
P2
s2 C30 10
2 4
A7
C9 K13
B6 / 61.9:A
1 3 A1 A6
C10
TRIP COMMAND
C C51 11
C52 RL1 TO TRIP CKT
IN A2
K1
P1 s1 B5 / 61.9:A
1C11 2 4 A8
-CT3 59.1:A / CBCTS1
C11
/60.1:C
P2
s2 C50 12
C71 1C10 1 3
59.1:B / CBCTS2
C12
A10
L12
B8 / 63.1:A
A1 A9
L1 O/C & E/F TRIP
K11 - +
RL2
61.8:B / D2 TO ANN. CKT
1 A14 A2
L11
-E2 L2 B7 / 63.1:A
TCH FUNCTION K12 - + A11

FOR TRIPPING COIL


61.8:B / D3
A15 L10
K1 A12
B10 / 62.5:C
61.8:A / D1 A1
D
A16 TO TCH
RL3 INDICATION
L3 L1
-X5 4 -X5 X41 - + A2
B9 / 62.5:C
3 A13
SPARE DI C1

A1 B1 -Q52
C2 B4 B7
L4 RL4
-X5 6 -X5 X42 - + A2
5
SPARE DI C3 B2

C4 A1 B3
L5
-X5 8 -X5 X43 - + RL5
E 7 A2
SPARE DI B5
B6 B5 B9 B8
L6
-X5 10 -X5 X44 - +
B4

9
SPARE DI B6

X11

X12

X13

X14

X15

X16
(S3) 4 -X3
B7 L7 +
-X5 12 -X5 X45 - + D+
11
RS485 COMM. -X6 1 -X6 2 -X6 3 -X6 4 -X6 5 -X6 6
SPARE DI B8 RS-485 (S4) 5 -X3 PORT
L8
-X5 -X5 X46 -
SPARE VCB CONTACT
14 - +
D-
13
SPARE DI B9 6 -X3

B10
K2

K1

R Y B
60.0:A 60.1:A 60.1:A
59.6:B 59.6:B
TO NEXT SHEET DC- DC+
CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 60
+IC3/58 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. POWER & CONTROL DIAGRAM FOR INCOMER-4 VCB FEEDER Current Page 59
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

FROM PREVIOUS SHEET NOTE:- INCOMER-1 CONTROL WIRING WILL BE SAME AS INCOMER-4
59.0:F 59.1:F 59.1:F
R Y B 110V AC SUPPLY
FROM INCOMER-3 ON BUS-2
A

+IC3-1VN2 / +IC3/47.6:C
+IC3-1VR2 / +IC3/47.6:B

+IC3-1VB2 / +IC3/47.6:C
+IC3-1VY2 / +IC3/47.6:B
-XT1
D11 1
D12
P1 s1
-CT1 -XPT 1 2 3 4
/59.0:B
P2
s2 D10 2

IC4-E11

IC4-E31

IC4-E51

IC4-E71
B

D31 3
D32
P1 s1
CORE-1 -CT2 2VR2 / +OG3/72.5:C
250/1A /59.1:C
CL-1, 5VA P2
s2 D30 4
2VY2 / +OG3/72.6:C
110V AC SUPPLY
2VB2 / +OG3/72.6:C TO NEXT FEEDER ON BUS-2

D51 5
D52 2VN2 / +OG3/72.6:C
1 3 5 7
P1 s1 -F1
6A
C -CT3 2 4 6 8
FP MCB
/59.1:C
P2
s2 D50 6
D71

E12

E32

E52

E72
1
-E2

E12

E32

E52

E72
D13

D33

D53

D13

D33

D53
D
-P2 -P3 1 2 3 4 5 6 8 9 10 11
DA MFM
RS1 RS2 YS1 YS2 BS1 BS2
DIGITAL AMMETER WITH INBUILT S1 S2 S1 S2 S1 S2 V1 V2 V3 VN
SELECTOR SWITCH
1 3 5 12 13 MULTI FUNCTION METER
-Q52
/59.7:D
/61.2:C
PH N RS 485
2 4 6
/62.1:C
/62.7:B 12 13 7 14
630A, 33kV VCB,

(S1)

(S2)
26.3kA FOR 3 SEC.,
3PH. 50Hz

E -X3 1 2 3
E12
E32

F
R
Y
B
TO COMMON BUS-2

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 61
59 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. POWER & METERING WIRING DIAGRAM FOR INCOMER-4 VCB Current Page 60
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

K1 K1 K1

S5 1

K1

K1

K1

K1

K1

K1
L R
A1 A2
A
-LS 9 -K51 K51
K86

K3

K4
/62.5:E /59.4:A /59.4:A
-X2 -X2 -X2 -X2 D1
/65.3:B
59.3:D B5
S6 -X2 5
5 3 5 1
59.6:C
2 S6 1
10 12 14 16
REMOTE 65.3:D
T CLOSING C REMOTE REMOTE REMOTE REMOTE
59.6:C
N 65.3:D
TRIPPING TRIPPING TRIPPING TRIPPING -S4 4 B6
-X2 6 N LT PANEL-1 LT PANEL-2
/61.1:C
C 6
T -X2 11 -X2 13 -X2 15 -X2 17 E.STOP
59.4:D

1K4
B 59.4:D
A
D2 D3
10

K13
-RS

K11

K11

K11

K11

K11

K11
K11
/62.1:E
6 2
SERVICE K5
B 10 10
-RT -RS 13
/62.2:E /62.1:E
6 2 6 2
TEST SERVICE -R94

K8
14
K86
1K5

9 /65.3:B
-R94 1
1 /61.3:B 65.3:B
5 1
-S4 65.3:C
/61.7:A
/62.4:F
2 2 -R94 10
K7
K6

/61.3:B
E.STOP

K11
6 2

K10

K12
-X2

K9
C
1 -X2
EXTERNAL -X2 7 -X2 9 -X2 18 -X2 20
INTERLOCK 4
EXTERNAL -Q52
-X2 2 INTERLOCK A5 B13 A3 C5

-X2 3 1 1 13
1K6

S91
S11 S12
4 3 /62.3:C 14
2
/62.4:C
9 S12
S92 4
10 1
11
D R1 S92
12 4
C1 C1
B14

K13
F2 F11
C2 C2
15
S2
A4 K86
16 /65.3:B
1
9
S43 65.6:C
2
65.6:D
10
A6
E

-X2 8 -X2 19
K2 K2
VCB ANTI PUMPING VCB AUX. SUPPLY
K1

K2

CLOSING COIL RELAY TRIPING COIL FOR MASTER


4D02 / 59.6:B 5 TRIP RELAY (K86)
AUX. SUPPLY
1 9 /61.2:B
4D03 / 59.6:BTO K51 RELAY 6
1 3 2 10 /61.4:C
-F2
6A 2 4
DP MCB
J3

J4

4D00 4D01
64.5:D 64.5:D

110V DC AUX SUPPLY


CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 62
60 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CLOSING & TRIPPING CONTROL WIRING DIAGRAM FOR INCOMER-4 Current Page 61
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. VCB FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

M1
11

-RDLS 12
DOOR -X2 30
LIMIT
SWITCH
B

-Q52
S2 A1
1
L1

L1

L1

L1

L1
2

-X2 21 -X2 23 -X2 25 -X2 27 -V1


R3 R1
U1
-Q52
D5 D9 A13 B1 M
-M1
1~
R4
C U2
K86 K51
/65.3:B /59.4:A RECT
13 7 B9
SERVICE TEST
65.3:D 59.6:D S2
POS. SW. POS. SW. 5 13 4
S2
14 S11 S11 65.3:E 59.6:D
/61.4:C 6 /61.4:C 14 8 B10 3

A2
D6 D10 A14 B3 B2

-X2 31

L10
L4

L5

L7

L8
L3

L9
D

M2
-X2 22 -X2 24 -X2 26 -X2 28 -X2 29

VCB SPRING
CHARGE MOTOR

A1 x1 x1 A1 x1 x1 x1 x1 x1 A1
-RS -H9 -H10 -RT -H8 -H4 -H5 -H6 -H7 -LS 3A02 / 63.1:E
A2 x2 x2 A2 x2 x2 x2 x2 x2 A2 TOANNUNCIATOR
L2 L2 3A03 / 63.2:E
E
VCB OFF VCB TRIP TRIP CKT AUX.
AUX. VCB IN VCB IN AUX. SPRING VCB ON

M1

M2
L1

L2

HEALTHY RELAY
RELAY SERVICE TEST RELAY CHARGE
1 3
6 10 /61.1:B 6 10 /61.1:B 5
2 2 1 9 /61.7:A
-F4
6 10 /61.2:B 6A 2 4
6
2 DP MCB
2 10 /62.5:F
13 LS 10
1 3 S5 1

H3

H4
/62.5:E
-F3 -S4 14 6 2
6A 2 4 L R /61.1:C
DP MCB A1 A2 E.STOP
J3

J4

X65

X66

-X2 32
X63

X64

33 -X2 34 EARTHING TB 3A00 3A01


F SPARE CONTACT EARTHING TB 64.1:D 64.2:D
-X4 11 12 -X4 13 14 LIMIT SW.
4D04 4D05 L/R SWITCH 1 230V AC
E.STOP PB -E1
64.6:D 64.6:D IN REMOTE MODE AUX SUPPLY
OPERATED
110V DC FEEDBACK
FEEDBACK
AUX SUPPLY CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 63
61 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CONTROL WIRING DIAGRAM FOR INDICATING LAMP & SPRING Current Page 62
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. CHARGE MOTOR FOR INCOMER-4 VCB FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

L11
A
K51 -X4 1 -X4 3 -X4 5

/59.4:A
B7 -R1 11 -R3 11
59.6:D SPARE SPARE SPARE /64.4:C /64.7:C

59.6:C 7 3 7 3

B8 -X4 2 -X4 4 -X4 6

L11
L12

L13

L14

L15

L16

L17
B -AN
1 2 3 4 5 6 COM

O/C & E/F SPARE SPARE SPARE AC FAIL DC FAIL


WITH HIGHEST
TRIP

POWER ON

6 WINDOW ANNUNCIATOR
TEST
C

ACCEPT

RESET
P N C NO T A R E

1
L35

L36

E
L33

L34

D
-X4 9 -X4 10
9 10
-R3 -R3
/64.7:C 5 1 /64.7:C 6 2
+BC-H11 +BC-H12
L31

L32

+BC/36.6:D +BC/36.6:E

TO COMMON HOOTER
IN BUSCOUPLER

1 3
-F6
E 6A 2 4
DP MCB
M1

M2
J3

J4

-3A02 -3A03
4D06 4D07 62.7:E 62.7:E
64.6:D 64.7:D 230V AC
110V DC AUX SUPPLY
AUX SUPPLY

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 64
62 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CONTROL WIRING DIAGRAM OF ANN. WINDOW FOR INCOMER-4 VCB Current Page 63
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

230V AC AUX. SUPPLY 110V DC AUX. SUPPLY


FROM INCOMER-3 FROM INCOMER-3
+IC3/51.2:B +IC3/51.2:B +IC3/51.8:B +IC3/51.8:C
+IC3-2ACP3 +IC3-2ACN3 +IC3-2DCP3 +IC3-2DCN3

-XAC 1 2
-XDC 1 2
B

H3

H4

J3

J4
-XAC
+OG3/78.3:A / 2ACP4 -XDC
3 2DCP4 / +OG3/78.7:A
230V AC AUX. SUPPLY 3 230V AC AUX. SUPPLY
TO OUTGOING-3 (BUS-2) -XAC
+OG3/78.3:A / 2ACN4 -XDC TO OUTGOING-3 (BUS-2)
4 2DCN4 / +OG3/78.7:A
4

7
A1 3 11 /63.4:A 5
C A1
-R1 1 9 /63.1:D
A2 -R3 6
A2 2 10 /63.2:D
7
AC FAIL 3 11 /63.4:A
RELAY DC FAIL
230V AC SUPPLY RELAY

110V DC SUPPLY
H3

H4

H3

H4
D

3A00 3A01

J3

J4

J3

J4

J3

J4
62.6:F 62.7:F
1 1
TO VCB SPRING -F11 -F12 NL
CHARGE MOTOR 6A 2 6A 2
4D04 4D05 4D06 4D07
4D00 4D01
61.0:F 61.1:F 62.0:F 62.0:F 63.0:E 63.1:E
H6

H9

TO CLOSING & TO INDICAION TO ANN. WINDOW


11 CIRCUIT CIRCUIT
H5

TRIPPING CIRCUIT
-DLS
E
DOOR
12 -XSH 1
LIMIT 13
PS SWITCH
TH
1
3 14
H12

2
H7

x1 x1

-SH
-PL 80W
x2

x2 -XSH 2

F PLUG PANEL SPACE


SOCKET LIGHT HEATER
HOLDER

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 65
63 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. AC & DC VOLTAGE CIRCUIT FOR INCOMER-4 VCB FEEDER Current Page 64
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

MASTER TRIP RELAY (K86)


-K86
/61.3:B
/61.5:A
B /61.9:D
/62.4:C

K8
61.3:B / 1
1
1

TO CLOSING COIL
2
K9
61.3:C / 2
2

-X5 1 X31
C
3
3
SPARE NO CONTACT
4

-X5 2 X32 9 K13


4 9 / 61.9:D

K1 K1 10 K2
61.5:A / 5 10 / 61.9:E
5
5
TO TRIPING COIL
6
D K11
61.5:A / 6
6

L1
62.4:C / 7
7
7
TO TRIP LAMP
8
L9
62.4:C / 8
8

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 66
64 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. MACRO FOR MASTER TRIP RELAY (K86) OF INCOMER-4 VCB FEEDER Current Page 65
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+IC4-X2 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-S4:2 K6 1 EXTERNAL INTERLOCK

2 =

3 =
B
-R94:1 K7 4 =

-A2 5 REMOTE CLOSE CMD

-RS:10 6 =

-Q52-A5 7 CLOSING CIRCUIT K9 -K86-2 /62.3:C

-F2:3 K2 8 = -Q52-A6 /58.3:E

-Q52-B13 9 CLOSING CIRCUIT (ANTIPUMPING) K10 -R94:14 /58.3:B


C

-K86-5 K1 10 REMOTE TRIP CMD

-K86-6 K11 11 =

12 =

13 =

14 REMOTE TRIPPING LT PANEL-1

D 15 =

-S4:3 K1 16 REMOTE TRIPPING LT PANEL-2

-S4:4 K11 17 =

-Q52-A3 18 TRIPPING CIRCUIT K11 -K86-6 /62.3:D

19 = -Q52-A4 /58.4:D

-Q52-C5 20 TCH K12 -K51-A15 /56.4:D


E
-Q52-D5 21 VCB IN SERVICE POSITION L1 -F3:1 /59.0:F

-H9:x1 22 = L3 -Q52-D6 /59.1:D

-Q52-D9 23 VCB IN TEST POSITION

-H10:x1 24 = L4 -Q52-D10 /59.2:D

-Q52-A13 25 VCB SPRING CHARGE INDI.

-H8:x1 26 = L5 -Q52-A14 /59.3:D


F

-Q52-B1 27 VCB ON L1 -K86-7 /62.3:D

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 67
65 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +IC4-X2 Current Page 66
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+IC4-X2 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-H4:x1 28 VCB ON L7 -Q52-B3 /59.3:D

-H5:x1 29 VCB OFF L8 -Q52-B2 /59.4:D

-Q52-A1 30 SPRING CHARGE MOTOR M1 -F4:1 /59.6:E


B
-F4:3 M2 31 = -Q52-A2 /59.8:D

32 SPARE CONTACT LIMIT SW. -LS:10 /59.5:F

-LS:6 33

-E1:1 34 EARTHING TB

C
Strip
External targets
+IC4-X3 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 MFM RS-485 (S1) -P3-7 /57.6:E

2 = (S2) -P3-14 /57.6:E

3 = /56.5:F
D

-K51-D+ (S3) 4 K51 RELAY RS485

-K51-D- (S4) 5 =

6 =

Strip
E
External targets
+IC4-X4 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 SPARE ANN. WINDOW L11 -K51-A11 /56.5:D

2 = L13 -AN-2 /60.2:B

3 =

4 = L14 -AN-3 /60.3:B


F

5 =

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 68
66 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +IC4-X2 +IC4-X3 +IC4-X4 Current Page 67
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+IC4-X4 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

6 SPARE ANN. WINDOW L15 -AN-4 /60.3:B

7 = -R3:11 /60.4:A

8 = L16 -AN-5 /60.4:B


B
+BC-X4:19 9 TO COMMON HOOTER IN BC

+BC-X4:20 10 =

11 L/R SWITCH IN REMOTE MODE FEEDBACK X63 -1 /59.3:F

12 = X64 -A2 /59.3:F

13 E.STOP PB OPERATED FEEDBACK X65 -S4:13 /59.4:F

14 = X66 -S4:14 /59.4:F


C

Strip
External targets
+IC4-X5 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-K86-3 X31 1 SPARE NC CONTACT (K86 RELAY)


D

-K86-4 X32 2 =

3 K51 RELAY SPARE DI X41 -K51-C1 /56.4:D

4 = K2 -F2:3 /58.0:F

5 = X42 -K51-C3 /56.4:E

6 = K2 -F2:3 /58.0:F

E 7 = X43 -K51-B5 /56.4:E

8 = K2 -F2:3 /58.0:F

9 = X44 -K51-B6 /56.4:E

10 = K2 -F2:3 /58.0:F

11 = X45 -K51-B8 /56.4:E

12 = K2 -F2:3 /58.0:F
F
13 = X46 -K51-B9 /56.4:F

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 69
67 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +IC4-X4 +IC4-X5 Current Page 68
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+IC4-X5 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

14 K51 RELAY SPARE DI K2 -F2:3 /58.0:F

Strip
+IC4-X6
B
External targets Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 SPARE VCB C/O CONTACT X11 -Q52-B4 /56.8:D

2 = X12 -Q52-B6 /56.8:E

3 = X13 -Q52-B5 /56.8:E

C
4 = X14 -Q52-B7 /56.9:D

5 = X15 -Q52-B9 /56.9:E

6 = X16 -Q52-B8 /56.9:E

Strip

D
External targets
+IC4-XAC Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-F4:2 H3 1 230V AC FROM INCOMER-3 +IC3-XAC:3 +IC3/49.2:B

-F4:4 H4 2 = +IC3-XAC:4 +IC3/49.2:B

-F4:2 H3 3 230V AC AUX. SUPPLY TO OUTGOING-3 +OG3-XAC:1 +OG3/74.3:B

-F4:4 H4 4 = +OG3-XAC:2 +OG3/74.3:B


E

Strip
External targets
+IC4-XDC Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-F6:2 J3 1 110V DC FROM INCOMER-3 +IC3-XDC:3 +IC3/49.7:B


F
-F6:4 J4 2 = +IC3-XDC:4 +IC3/49.7:C

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 70
68 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +IC4-X5 +IC4-X6 +IC4-XAC +IC4-XDC Current Page 69
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+IC4-XDC Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-F6:2 J3 3 110V DC AUX. SUPPLY TO OUTGOING-3 +OG3-XDC:1 +OG3/74.7:B

-F6:4 J4 4 = +OG3-XDC:2 +OG3/74.7:B

Strip
External targets
+IC4-XPT Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-F1:1 IC4-E11 1 110V AC SUPPLY FROM INCOMER-3 +IC3-F1:1 +IC3/45.5:C

-F1:3 IC4-E31 2 = +IC3-F1:3 +IC3/45.5:C

C
-F1:5 IC4-E51 3 = +IC3-F1:5 +IC3/45.5:C

-F1:7 IC4-E71 4 = +IC3-F1:7 +IC3/45.5:C

Strip
External targets
+IC4-XSH Internal targets

D
Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-TH:13 1 SPACE HEATER T.B. H6 -F12:2 /61.3:D

-PL:x2 2 = -SH:x2 /61.3:E

Strip
External targets
+IC4-XT1 Internal targets
E

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 CT SHORTING T.B. FOR METERING D11 -CT1:s1 /57.0:B

-P2-RS1 D12 2 = -E2:1 /57.1:C

3 = D31 -CT2:s1 /57.1:B

-P2-YS1 D32 4 = D10 -CT1:s2 /57.0:B


F
-P3-6 D71 5 = D51 -CT3:s1 /57.1:C

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 71
69 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +IC4-XDC +IC4-XPT +IC4-XSH +IC4-XT1 Current Page 70
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+IC4-XT1 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-P2-BS1 D52 6 CT SHORTING T.B. FOR METERING D10 -CT1:s2 /57.0:B

7 CT SHORTING T.B. FOR PROTECTION C11 -CT1:s1 /56.0:B

-K51-C5 C12 8 = -E2:1 /56.1:D


B
9 = C31 -CT2:s1 /56.1:C

-K51-C7 C32 10 = C10 -CT1:s2 /56.0:B

-K51-C6 C71 11 = C51 -CT3:s1 /56.1:C

-K51-C9 C52 12 = C10 -CT1:s2 /56.0:B

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page +OG3/72
70 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +IC4-XT1 Current Page 71
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

33kV SUPPLY FROM


COMMON BUS-2
R
Y
B
A

1 3 5
-Q52
/72.7:D
/74.2:C 2 4 6
/75.1:B
/75.6:B
630A, 33kV VCB,
26.3kA FOR 3 SEC.,
110V AC SUPPLY
3PH. 50Hz FROM INCOMER-4 ON BUS-2
B

+IC4-2VN2 / +IC4/60.6:C
+IC4-2VR2 / +IC4/60.6:B

+IC4-2VB2 / +IC4/60.6:C
+IC4-2VY2 / +IC4/60.6:B
-XT1
D11 1
D12
P1 s1
-CT1
/73.0:B
P2
s2 D10 2

D31 3
D32 -XPT 1 2 3 4
C P1 s1
CORE-1 -CT2

OG3-E11

OG3-E31

OG3-E51

OG3-E71
30/1A /73.1:B
CL-1, 2.5VA P2
s2 D30 4

D51 5
D52 1 3 5 7
P1 s1 -F1
-CT3 6A
FP MCB 2 4 6 8
/73.1:C
P2
s2 D50 6
D71

E12

E32

E52

E72
D

1
-E2
-Q52
/72.0:A B4 B7

E12

E32

E52

E72
D13

D33

D53

D13

D33

D53
-P2 -P3 1 2 3 4 5 6 8 9 10 11
DA MFM
RS1 RS2 YS1 YS2 BS1 BS2
E DIGITAL AMMETER WITH INBUILT S1 S2 S1 S2 S1 S2 V1 V2 V3 VN
SELECTOR SWITCH B6 B5 B9 B8
12 13 MULTI FUNCTION METER

PH N RS 485

X11

X12

X13

X14

X15

X16
12 13 7 14
-X6 1 -X6 2 -X6 3 -X6 4 -X6 5 -X6 6

(S1)

(S2)
-X3 1 2 3 SPARE VCB CONTACT
E12
F
E32
R Y B
73.0:A 73.1:A 73.1:A

TO NEXT SHEET
CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 73
+IC4/71 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. POWER & CONTROL DIAGRAM FOR OUTGOING-3 (AUX. TRAFO.) VCB Current Page 72
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

FROM PREVIOUS SHEET


72.0:F 72.1:F 72.1:F
R Y B
NUMERICAL RELAY
A (50,50N,51,51N,95,94F) 73.5:F 73.5:F
DC+ DC-
-K51
/74.7:A
/74.9:A -PS K1
/75.4:B
-XT1 AC
4D02 / 74.1:E
/77.1:A 110V DC
C11 7
C12 2 Ia 4
A1
K2 AUX SUPPLY
P1 s1 C5 AC
4D03 / 74.1:F
A2
1 3
-CT1
/72.0:C
P2
s2 C10 8 C6
Ib A4
WD
2 4 A1 A3
C31 9
C32 C7 RL0
B
P1 s1 1 3 A2
CORE-2 -CT2
C8 A5

30/1A Ic
CL-5P10, 2.5VA
/72.1:C
P2
s2 C30 10
2 4
C9
A7
K13
B6 / 74.9:A
1 3 A1 A6
TRIP COMMAND
C51 11
C52 C10 RL1 TO TRIP CKT
IN A2 K1
P1 s1 B5 / 74.9:A
1C11 2 4 A8
-CT3 C11
/72.1:D
P2
s2 C50 12
C71 1C10 1 3
A10
C12
L12
C B8 / 77.1:B
A1 A9
L1 O/C & E/F TRIP
K11 - +
RL2
74.7:B / D2 TO ANN. CKT
1 A14 A2
L11
-E2 L2 B7 / 77.1:A
TCH FUNCTION K12 - + A11

FOR TRIPPING COIL


74.7:B / D3
A15 L10
SA K1 A12
B10 / 75.5:C
74.7:A / D1 A1
A16 TO TCH
R R RL3
L3 L1 INDICATION
1
-X5 4 -X5 X41 - + A2
B9 / 75.5:C
Y 3 A13
Y -E1 SPARE DI C1

A1 B1
D B B C2
L4 RL4
-X5 6 -X5 X42 - + A2
5
SPARE DI C3 B2

C4 A1 B3
L5
-X5 8 -X5 X43 - + RL5
CBCT SPARE DI
7 B5 A2
30/1A L6
-X5 10 -X5 X44 - +
B4

9
SPARE DI B6

(S3) 4 -X3
B7 L7 +
E
-X5 12 -X5 X45 - + D+
11
RS485 COMM.
SPARE DI B8 RS-485 (S4) 5 -X3 PORT
L8
-X5 14 -X5 X46 - + -
D-
13
SPARE DI B9 6 -X3

B10
K2

K1

73.7:A 73.7:A
DC- DC+
F

R Y B

TO OUTGOING AUX.
TRANSFORMER
CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 74
72 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. POWER & METERING WIRING DIAGRAM FOR OUTGOING-3 (AUX. Current Page 73
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. TRAFO.) VCB FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

K1 K1 K1

S5 1

K1

K1

K1

K1
L R
A1 A2
A
-LS 9 -K51 K51
K86

K3

K4
/75.5:D /73.5:A /73.5:A
-X2 -X2 D1 9 9
/79.3:B
73.5:C B5
S6 -X2 5 5 3 5 1
-K631 -K633 73.7:C
2 S6 1
10 12
REMOTE 79.3:D /76.1:E /76.3:E
T CLOSING C REMOTE REMOTE 5 1 5 1 73.7:B
N 79.3:D
TRIPPING TRIPPING -S4 4 B6
-X2 6 N /74.1:C 9
C 6 9
T -X2 11 -X2 13 E.STOP

1K4
B
73.5:C 73.5:C -K632 -K634
A
10 D2 D3 /76.2:E 5 1
/76.3:E 5 1
-KS

K13
K11

K11

K11

K11
K11
SERVICE
6 2
K5
B 10 10
-KT -KS
TEST SERVICE 13
6 2 6 2
-K94
K8 14
K86
1K5

9 /79.3:B
-K94 1
1 /74.3:B 79.3:B
5 1
-S4
79.3:C
/74.6:A 2
/76.9:A 2 -K94 10
K7
K6

E.STOP /74.3:B

K11
-X2 6 2

K10

K12
-X2 K9
C 4
1
EXTERNAL
EXTERNAL INTERLOCK -X2 7 -X2 9 -X2 14 -X2 16
INTERLOCK

-X2 3 -Q52
-X2 2 /72.0:A A5 B13 A3 C5
1 1 13
1K6

S91
S11 S12
4 3 /75.3:C 14
2
/75.4:C
9 S12
S92 4
10 1
11
D R1 S92
12 4
C1 C1
B14

K13
F2 F11
C2 C2
15
S2
A4 K86
16 /79.3:B
1
9
S43 79.6:C
2
79.6:D
10
A6
E

-X2 8 -X2 15
K2 K2
VCB ANTI PUMPING VCB AUX. SUPPLY
K1

K2

CLOSING COIL RELAY TRIPING COIL FOR MASTER


4D02 / 73.7:A 5 TRIP RELAY (K86)
AUX. SUPPLY
1 9 /74.1:B
4D03 / 73.7:ATO K51 RELAY 6
1 3 2 10 /74.3:C
-F2
6A 2 4
DP MCB
J3

J4

4D00 4D01
78.5:D 78.5:D

110V DC AUX SUPPLY


CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 75
73 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CLOSING & TRIPPING CONTROL WIRING DIAGRAM FOR OUTGOING-3 Current Page 74
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. (AUX. TRAFO.) VCB FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

M1
11
-X2 26
L1 -RDLS

L1

L1

L1

L1
12
DOOR
LIMIT
B
SWITCH
-X2 17 -X2 19 -X2 21 -X2 23 -Q52
/72.0:A S2 A1
1
-Q52
/72.0:A D5 D9 A13 B1
2

-V1
K86 K51 U1
R3 R1
/79.3:B /73.5:A
7 B9
SERVICE TEST 13
73.7:D M
5 13 79.3:D -M1
POS. SW. POS. SW. S2 1~
14 S11 S11 79.3:E 73.7:C
R4
C /74.4:C 6 /74.4:C 14 8 B10 U2
RECT

D6 D10 A14 B3 B2 S2
4

L10

L11
L4

L5

L7

L8
L3

L9
A2
-X2 18 -X2 20 -X2 22 -X2 24 -X2 25

-X2 27

M2
A1 x1 x1 A1 x1 x1 x1 x1 x1 A1
-RS -H9 -H10 -RT -H8 -H4 -H5 -H6 -H7 -LS
A2 x2 x2 A2 x2 x2 x2 x2 x2 A2 VCB SPRING
L2 L2 L2 CHARGE MOTOR
AUX. VCB IN VCB IN AUX. SPRING VCB ON VCB OFF VCB TRIP TRIP CKT AUX.
L1

L2

RELAY SERVICE TEST RELAY CHARGE HEALTHY RELAY


3A02 / 77.1:E
5 TOANNUNCIATOR
1 9 /74.6:A 3A03 / 77.2:E
E 6

M1

M2
2 10 /75.4:F

1 3

4D08 / 77.0:F -F4


TO ANN. CKT 6A 2 4
DP MCB
4D09 / 77.0:F
1 3

H3

H4
-F3 LS 10
6A /75.5:D
2 4
DP MCB -X2 30 EARTHING TB
6 2
EARTHING TB
J3

J4

1 3A00 3A01
F -X2 28
29 -E1 78.1:D 78.2:D

4D04 4D05 SPARE CONTACT 230V AC


78.6:D 78.6:D LIMIT SW. AUX SUPPLY
110V DC
AUX SUPPLY CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 76
74 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CONTROL WIRING DIAGRAM FOR INDICATING LAMP & SPRING Current Page 75
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. CHARGE MOTOR FOR OUTGOING-3 (AUX. TRAFO.) VCB FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

S5 1 13

A
L R -S4 14
A1 A2 /74.1:C
E.STOP

X61

X62

X63

X66
K21

K21

K21

K21

K21

K21

K21

K21
-X4 19 20 -X4 21 22

L/R SWITCH E.STOP PB


IN REMOTE MODE OPERATED
FEEDBACK FEEDBACK
B -X4 1 -X4 3 -X4 5 -X4 7 -X4 9 -X4 11 -X4 13 -X4 15

-FIELD

W.T.I. O.T.I. G.O.R. P.R.V. W.T.I. O.T.I. G.O.R M.O.G.


TRIP TRIP TRIP TRIP ALARM ALARM ALARM ALARM

C
K23

K24

K25

K26

K27

K28

K29

K30
-X4 2 -X4 4 -X4 6 -X4 8 -X4 10 -X4 12 -X4 14 -X4 16

A1 A1 A1 A1 A1 A1 A1 A1
-K631 -K632 -K633 -K634 -K635 -K636 -K637 -K638
A2 A2 A2 A2 A2 A2 A2 A2

E
K21

K22

TRANSFORMER FAULT AUX. RELAY


1 3
-F5
6A 2 4
DP MCB
5 9 /74.7:A 5 9 /74.8:A 5 9 /74.8:A 5 9 /74.9:A 6 10 /77.4:A 6 10 /77.5:B 6 10 /77.5:A 6 10 /77.6:B
J3

J4

1 1 1 1 2 2 2 2
6 10 /77.2:A 6 10 /77.2:B 6 10 /77.3:A 6 10 /77.3:B
2 2 2 2

F 4D06 4D07
78.6:D 78.7:D

110V DC
AUX SUPPLY

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 77
75 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CONTROL WIRING DIAGRAM OF TRAFO. FAULT AUX. RELAY FOR Current Page 76
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. OUTGOING-3 (AUX. TRAFO.) VCB FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

L11
A

K51 -X4 23
/73.5:A
B7 10 10 10 10 -K1 11 -K 11
73.7:C
-K631 -K633 -K635 -K637 SPARE
/76.1:E 6 2 /76.3:E 6 2 /76.4:E 6 2 /76.5:E 6 2 7 3 7 3
73.7:C
B8
10 10 10 10 -X4 24
-K632 -K634 -K636 -K638
/76.2:E 6 2 /76.3:E 6 2 /76.4:E 6 2 /76.5:E 6 2

L11
L12

L13

L14

L15

L16

L17

L18

L19

L20

L21

L22

L23
B

-AN
1 2 3 4 5 6 7 8 9 10 10 10 COM

O/C & E/F W.T.I. O.T.I. G.O.R. P.R.V. W.T.I. O.T.I. G.O.R M.O.G. AC FAIL DC FAIL SPARE
WITH HIGHEST TRIP TRIP TRIP TRIP ALARM ALARM ALARM ALARM
TRIP

POWER ON

C
12 WINDOW ANNUNCIATOR
TEST

ACCEPT

RESET
P N C NO T A R E

1
D
L35

L36

E
L33

L34

-X4 17 -X4 18
9 10
-K -K
5 1 6 2
+BC-H13 +BC-H14
+BC/36.6:D +BC/36.6:E

TO COMMON HOOTER
IN BUSCOUPLER

E
L1

L2

M1

M2

-3A02 -3A03
4D08 4D09 75.7:E 75.7:E
75.1:E 75.1:E 230V AC
110V DC AUX SUPPLY
AUX SUPPLY
F

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 78
76 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. CONTROL WIRING DIAGRAM OF ANN. WINDOW FOR OUTGOING-3 Current Page 77
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. (AUX. TRAFO.) VCB FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

230V AC AUX. SUPPLY 110V DC AUX. SUPPLY


FROM INCOMER-4 FROM INCOMER-4
+IC4/64.2:B +IC4/64.2:B +IC4/64.8:B +IC4/64.8:C
+IC4-2ACP4 +IC4-2ACN4 +IC4-2DCP4 +IC4-2DCN4

-XAC 1 2
-XDC 1 2
B

H3

H4

J3

J4
A1
-R1
A2

AC FAIL
RELAY

C A1

230V AC SUPPLY -R3


A2

DC FAIL
RELAY
H3

H4

H3

H4
3A00 3A01 110V DC SUPPLY
D 75.6:F 75.6:F
1 1
TO VCB SPRING -F11 -F12 NL
CHARGE MOTOR 6A 2 6A 2

J3

J4

J3

J4

J3

J4
H5

H6

H9
11
4D00 4D01 4D04 4D05 4D06 4D07
75.0:F 75.0:F 76.0:F 76.1:F
-DLS 74.0:F 74.0:F
DOOR
12 -XSH 1
LIMIT 13 TO CLOSING & TO INDICAION TO TRAFO. AUX.
SWITCH
TH TRIPPING CIRCUIT CIRCUIT RELAY CIRCUIT
14
E
H12

H7

x1 x1

-SH
-PL 80W
x2

x2 -XSH 2

PANEL SPACE
LIGHT HEATER
HOLDER

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 79
77 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. AC & DC VOLTAGE CIRCUIT FOR OUTGOING-3 (AUX. TRAFO.) VCB Current Page 78
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

MASTER TRIP RELAY (K86)


-K86
/74.2:B
/74.4:A
B /74.9:D
/75.4:B

K8
74.2:B / 1
1
1

TO CLOSING COIL
2
K9
74.2:C / 2
2

-X5 1 X31
C
3
3
SPARE NO CONTACT
4

-X5 2 X32 9 K13


4 9 / 74.9:D

K1 K1 10 K2
74.5:A / 5 10 / 74.9:E
5
5
TO TRIPING COIL
6
D K11
74.5:A / 6
6

L1
75.4:C / 7
7
7
TO TRIP LAMP
8
L9
75.4:C / 8
8

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 80
78 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. MACRO FOR MASTER TRIP RELAY (K86) OF OUTGOING-3 (AUX. Current Page 79
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. TRAFO.) VCB FEEDER Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG3-X2 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-S4:2 K6 1 EXTERNAL INTERLOCK

2 =

3 =
B
-R94:1 K7 4 =

-A2 5 REMOTE CLOSE CMD

-RS:10 6 =

-Q52-A5 7 CLOSING CIRCUIT K9 -K86-2 /75.3:C

-F2:3 K2 8 = -Q52-A6 /70.2:E

-Q52-B13 9 CLOSING CIRCUIT (ANTIPUMPING) K10 -R94:14 /70.3:B


C

-K86-5 K1 10 REMOTE TRIP CMD

-K86-6 K11 11 =

-S4:3 K1 12 =

-S4:4 K11 13 =

-Q52-A3 14 TRIPPING CIRCUIT K11 -K86-6 /75.3:D

D 15 = -Q52-A4 /70.4:D

-Q52-C5 16 TCH K12 -K51-A15 /69.5:C

-Q52-D5 17 VCB IN SERVICE POSITION L1 -F3:1 /71.0:F

-H9:x1 18 = L3 -Q52-D6 /71.1:C

-Q52-D9 19 VCB IN TEST POSITION

-H10:x1 20 = L4 -Q52-D10 /71.2:C


E
-Q52-A13 21 VCB SPRING CHARGE INDI.

-H8:x1 22 = L5 -Q52-A14 /71.3:C

-Q52-B1 23 VCB ON L1 -K86-7 /75.3:D

-H4:x1 24 = L7 -Q52-B3 /71.3:C

-H5:x1 25 VCB OFF L8 -Q52-B2 /71.4:C

-Q52-A1 26 SPRING CHARGE MOTOR M1 -F4:1 /71.6:E


F

-F4:3 M2 27 = -Q52-A2 /71.8:D

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 81
79 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG3-X2 Current Page 80
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG3-X2 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

28 SPARE CONTACT LIMIT SW. -LS:10 /71.4:F

-LS:6 29

-E1:1 30 EARTHING TB
B

Strip
External targets
+OG3-X3 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 MFM RS-485 (S1) -P3-7 /68.6:E

C
2 = (S2) -P3-14 /68.6:E

3 = /68.6:F

-K51-D+ (S3) 4 K51 RELAY RS485

-K51-D- (S4) 5 =

6 =

Strip
External targets
+OG3-X4 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-FIELD 1 W.T.I. TRIP FROM FIELD K21 -F5:1 /72.0:E

-FIELD K23 2 = -R631:A1 /72.1:E


E
-FIELD 3 O.T.I. TRIP FROM FIELD

-FIELD K24 4 = -R632:A1 /72.2:E

-FIELD 5 G.O.R. TRIP FROM FIELD

-FIELD K25 6 = -R633:A1 /72.3:E

-FIELD 7 P.R.V. TRIP FROM FIELD

-FIELD K26 8 = -R634:A1 /72.3:E


F

-FIELD 9 W.T.I. ALARM FROM FIELD

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 82
80 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG3-X2 +OG3-X3 +OG3-X4 Current Page 81
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG3-X4 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-FIELD K27 10 W.T.I. ALARM FROM FIELD -R635:A1 /72.4:E

-FIELD 11 O.T.I. ALARM FROM FIELD

-FIELD K28 12 = -R636:A1 /72.4:E


B
-FIELD 13 G.O.R ALARM FROM FIELD

-FIELD K29 14 = -R637:A1 /72.5:E

-FIELD 15 M.O.G. ALARM FROM FIELD

-FIELD K30 16 = -R638:A1 /72.5:E

+BC-X4:21 17 TO COMMON HOOTER IN BC

+BC-X4:22 18 =
C

19 L/R SWITCH IN REMOTE MODE FEEDBACK X61 -1 /72.8:A

20 = X62 -A2 /72.8:A

21 E.STOP PB OPERATED FEEDBACK X63 -S4:13 /72.9:A

22 = X66 -S4:14 /72.9:A

D
Strip
External targets
+OG3-X5 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-K86-3 X31 1 SPARE NC CONTACT (K86 RELAY)

-K86-4 X32 2 =

E 3 K51 RELAY SPARE DI X41 -K51-C1 /69.5:D

4 = K2 -F2:3 /70.0:F

5 = X42 -K51-C3 /69.5:D

6 = K2 -F2:3 /70.0:F

7 = X43 -K51-B5 /69.5:D

8 = K2 -F2:3 /70.0:F
F
9 = X44 -K51-B6 /69.5:E

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 83
81 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG3-X4 +OG3-X5 Current Page 82
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG3-X5 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

10 K51 RELAY SPARE DI K2 -F2:3 /70.0:F

11 = X45 -K51-B8 /69.5:E

12 = K2 -F2:3 /70.0:F
B
13 = X46 -K51-B9 /69.5:E

14 = K2 -F2:3 /70.0:F

Strip
External targets
+OG3-X6 Internal targets

C
Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 SPARE VCB C/O CONTACT X11 -Q52-B4 /68.8:D

2 = X12 -Q52-B6 /68.8:E

3 = X13 -Q52-B5 /68.8:E

4 = X14 -Q52-B7 /68.9:D

5 = X15 -Q52-B9 /68.9:E


D

6 = X16 -Q52-B8 /68.9:E

Strip
External targets
+OG3-XAC Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement
E
-F4:2 H3 1 230V AC FROM INCOMER-4 +IC4-XAC:3 +IC4/61.2:B

-F4:4 H4 2 = +IC4-XAC:4 +IC4/61.2:B

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 84
82 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG3-X5 +OG3-X6 +OG3-XAC Current Page 83
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG3-XDC Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-F5:2 J3 1 110V DC FROM INCOMER-4 +IC4-XDC:3 +IC4/61.7:B

-F5:4 J4 2 = +IC4-XDC:4 +IC4/61.7:C

Strip
External targets
+OG3-XPT Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-F1:1 OG3-E11 1 110V AC SUPPLY FROM OG-1 +IC4-F1:1 +IC4/57.5:C

-F1:3 OG3-E31 2 = +IC4-F1:3 +IC4/57.5:C

C
-F1:5 OG3-E51 3 = +IC4-F1:5 +IC4/57.5:C

-F1:7 OG3-E71 4 = +IC4-F1:7 +IC4/57.5:C

Strip
External targets
+OG3-XSH Internal targets

D
Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-TH:13 1 SPACE HEATER T.B. H6 -F12:2 /74.3:D

-PL:x2 2 = -SH:x2 /74.3:E

Strip
External targets
+OG3-XT1 Internal targets
E

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 CT SHORTING T.B. FOR METERING D11 -CT1:s1 /68.0:C

-P2-RS1 D12 2 = -E2:1 /68.1:D

3 = D31 -CT2:s1 /68.1:C

-P2-YS1 D32 4 = D10 -CT1:s2 /68.0:C


F
-P3-6 D71 5 = D51 -CT3:s1 /68.1:D

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page 85
83 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG3-XDC +OG3-XPT +OG3-XSH +OG3-XT1 Current Page 84
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
0 1 2 3 4 5 6 7 8 9

Terminal diagram
Strip
A
External targets
+OG3-XT1 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-P2-BS1 D52 6 CT SHORTING T.B. FOR METERING D10 -CT1:s2 /68.0:C

7 CT SHORTING T.B. FOR PROTECTION C11 -CT1:s1 /69.0:B

-K51-C5 C12 8 = -E2:1 /69.1:C


B
9 = C31 -CT2:s1 /69.1:B

-K51-C7 C32 10 = C10 -CT1:s2 /69.0:B

-K51-C6 C71 11 = C51 -CT3:s1 /69.1:C

-K51-C9 C52 12 = C10 -CT1:s2 /69.0:B

CLIENT:- M/S. Prathama Solar Connect Energy Pvt. Ltd. (PSEPL) Next Page
84 ISSUE FOR:- APPROVAL PROJECT:- 75MWP/55MW Ground Mounted Solar PV power plant, Veppankulam Village, Devakottai, Tamilnadu.
DRAWN ABID SCOPE:- OE Services for 75MWP/55MW Ground Mounted Solar PV power plant. JOB NO.:- JAA401/0305/01-06 DWG NO.:- SS/JAA401/320
R1 16.05.20 AS PER CLIENT COMMENTS DATE:-05.05.2020 CHECKED VGV OWNERS ENGINEERS:- M/s. TUV India Pvt. Ltd. NAME OF PANEL:- 33KV 700AMP 25KA/3SEC OUTDOOR TYPE PANEL
R0 21.03.20 PO N0.;- ABID APPROVED VGV EPC CONTRACTOR:- M/s. Prozeal Infra Engineering Pvt. Ltd. Terminal diagram +OG3-XT1 Current Page 85
REV. DATE DESCRIPTION NAME DATE 21-03-20 EPC DESIGN CONSULTANT:- M/s. Arbutus Consultants Pvt. Ltd. Total Page 85
BILLS OF MATERIAL / BILLS OF QUANTITY
CLIENT:- M/S. Prathama Solar connect Energy Pvt Ltd Job. No.:- JAA401/0305/01 Rev.:-R1
(PSEPL)

PROJECT:-75MWp/55MW Ground Mounted Solar PV Power Drg. No. :- SS/JAA401/420


Date:- 16.05.2020
Plant, Veppankulam Village, Devakottai, TamilNadu

SCOPE:- OE Services for 75MWp/55MW Ground Mounted


Solar PV Power Plant
OWNERS ENGINEERS:-M/S. TUV India Pvt. Ltd PO NO.:-
EPC CONTRACTOR:-M/S. Prozeal Infra Engineering Pvt
Ltd NAME OF PANEL:-33KV,700Amp,25Ka/3sec OUTDOOR TYPE
EPC DESIGN CONSULTANT:-M/S. Arbutus Consultants Pvt PANEL
Ltd
SR. NO. TAG NO. RATING DISCRIPTION QTY MAKE TYPE/PART NO.
33kV HT VCB OUTGOING-1&2 FEEDER 2 Nos.
[A] VACUUM CIRCUIT BREAKER
1 Q52 1250A 33kV Drawout Type VCB (STR: 26.3kA for 3 Sec.) 1 No. Schneider
6NO+6NC Contact With inbuilt Mechanical Anti -
Pumping Feature
2 230V AC Spring Charging Motor 1 No.
3 110V DC Closing Coil 1 No. Schneider
4 110V DC Tripping Coil 1 No. Schneider
[B] CURRENT TRANSFORMER & POTENTIAL TRANSFORMER

700/1/1/1A Core-1, Class-0.5S, 5VA

Core-2, Class-5P10, 5VA ECS/SEI/Pragati/Precise/Starlit


e Electrical/Schneider App.
1 CT1-3 3 Nos. Resin Cast
Vendor
Core-3, Class-PS,

CT Secondary Termination on P2 Side

Single phase, Fix type PT,


ECS/SEI/Pragati/Precise/Starlit
105VA e Electrical/Schneider App.
2 PT1-3 3 Nos. Resin Cast
(35VA/PH.) PTR: 33000V/√3/110V/√3/110V/√3 Vendor

Core-1 Class-0.5 , Core-2 Class-3P

[C] RELAYS
Numerical Modbus Communicable Multi Protection
1 K51 110V DC Relay(50,50N,51,51N,95,27,59,50BF) Flush Mounting with 1 No. Schneider/ABB/Alsthom P3U30/Equi.
16DI and 8DO
Electromechanical Type Master Trip Relay with 3NO+1NC
2 K86 110V DC 1 No. Alstom/ABB
Conatct, Flush Mounting
[D] METERS
Schneider/
1 P1 110V AC Digital Voltmeter with inbuilt selector switch, 96X96mm, 1 No.
Secure/Elmeasure
Digital Ammeter with inbuilt selector switch, Schneider/
2 P2 110V AC 1 No.
96X96mm, Secure/Elmeasure
Digital Multifunction Meter with RS-485 port,CL-1, Schneider/
3 P3 110V AC 1 No.
96X96mm, Secure/Elmeasure
[E] INDICATING LAMP
1 H1 63.5V AC R-Phase Indicating Lamp (Red), LED Type 1 No. L&T (Esbee)
2 H2 63.5V AC Y-Phase Indicating Lamp (Yellow), LED Type 1 No. L&T (Esbee)
3 H3 63.5V AC B-Phase Indicating Lamp (Blue), LED Type 1 No. L&T (Esbee)
4 H4 110V DC ON Indicating Lamp (Red) , LED Type 1 No. L&T (Esbee)
5 H5 110V DC OFF Indicating Lamp (Green), LED Type 1 No. L&T (Esbee)
6 H6 110V DC TRIP Indicating Lamp (Amber), LED Type 1 No. L&T (Esbee)
7 H8 110V DC Spring Charge Indicating Lamp (Blue), LED Type 1 No. L&T (Esbee)
8 H9 110V DC VCB In Test Indicating Lamp (White), LED Type 1 No. L&T (Esbee)
9 H10 110V DC VCB in Service Indicating Lamp (Yellow), LED Type 1 No. L&T (Esbee)
[F] PUSH BUTTON & SELECTOR SWITCH

1 S5 6A 2Pole, 2Ways, Without Off L/R Selector Switch, Rotary Type 1 No. Salzer

2 S4 Emergency Stop PB (Red) With 1NC+2NO Contact 1 No. L&T (Esbee)


[G] OTHER CONTROL COMPONENTS
TNC, 1 Pole, 2 Ways, Spring Return to Neutral, Pistol Grip
1 S6 32A 1 No. Switron
Handle, Angular Movement : 45+45°, Rotary Type
R94,RS,RT, Omron/BCH/PLA/OEN/PHOEN
2 110V DC 4 C/O Aux. Relay for Antipumping Application,Service,Test 4 No.
LS IX
Omron/BCH/PLA/OEN/PHOEN
3 R1 230V AC 4 C/O Aux. Relay for AC Fail 1 No.
IX
Omron/BCH/PLA/OEN/PHOEN
4 R3 110V DC 4 C/O Aux. Relay for DC Fail 1 No.
IX
5 F1,F01 6A FP Control MCB for Metering 2 Nos.
6 F2-F5 6A DP Control MCB 3 Nos.
Schneider/Equi.
7 FAC 16A DP Control MCB for AC Circuit 1 No.
8 FDC 10A DP Control MCB for DC Circuit 1 No.

9 AN 230VAC/110V DC 6 Window Annunciator With Accept, Reset ,Test Push Button, 1 No. EAPL/Minilec/GIC

10 SA 30KV , 10KA Surge arraster , CL-2 1Set Mecol/Nelson/Equi.


[H] MICELENIOUS ITEMS
1 PLS 20A 3 Pin Plug Socket 1 No. Anchor/or equivalent
2 PL 230V AC Panel Light Holder 1 No. Anchor/or equivalent
3 RDLS Door Limit Switch 1 No. Jainson/Suraj/or equivalent
4 SH 80W Space Heater 1 No. Girishgo/or equivalent
5 TH Thermostate, 30°-85°C 1 No. Girishgo/or equivalent
6 F11-12 6A SP Control MCB 2 Nos. Schneider
7 X2-X6,XSH Control Terminals Lot Elmex/Connectwell
8 End Plate with End Clamp for Control Terminals Lot Elmex/Connectwell
9 XT1,XPT C.T. & P.T. Terminals Set 1Set Elmex/Connectwell
RR Kable/Polycab/KEI/
Copper Flexible Wire Lot
10 Finolex/Lapp
BILLS OF MATERIAL / BILLS OF QUANTITY
CLIENT:- M/S. Prathama Solar connect Energy Pvt Ltd Job. No.:- JAA401/0305/01 Rev.:-R1
(PSEPL)

PROJECT:-75MWp/55MW Ground Mounted Solar PV Power Drg. No. :- SS/JAA401/420


Date:- 16.05.2020
Plant, Veppankulam Village, Devakottai, TamilNadu

SCOPE:- OE Services for 75MWp/55MW Ground Mounted


Solar PV Power Plant
OWNERS ENGINEERS:-M/S. TUV India Pvt. Ltd PO NO.:-
EPC CONTRACTOR:-M/S. Prozeal Infra Engineering Pvt
Ltd NAME OF PANEL:-33KV,700Amp,25Ka/3sec OUTDOOR TYPE
EPC DESIGN CONSULTANT:-M/S. Arbutus Consultants Pvt PANEL
Ltd
SR. NO. TAG NO. RATING DISCRIPTION QTY MAKE TYPE/PART NO.
33kV HT VCB BUSCOUPLER FEEDER 1 No.
[A] VACUUM CIRCUIT BREAKER
1 Q52 1250A 33kV Drawout Type VCB (STR: 26.3kA for 3 Sec.) 1 No. Schneider
6NO+6NC Contact With inbuilt Mechanical Anti -
Pumping Feature
2 230V AC Spring Charging Motor 1 No. Schneider
3 110V DC Closing Coil 1 No. Schneider
4 110V DC Tripping Coil 1 No. Schneider
[B] CURRENT TRANSFORMER

1 CT1-3 700/1A Core-1, Class-5P10, 5VA


ECS/SEI/Pragati/Precise/Starlit
CT Secondary Termination on P2 Side 3 Nos. e Electrical/Schneider App. Resin Cast
Vendor

[C] RELAYS
Numerical, Communicable IDMT Relay, 3O/C + 1E/F with
1 K51 110V DC Highset (50/51/50N/51N/95), Flush Mounting with 8DI and 1 No. Schneider/ABB/Alsthom MicomP111/Equi.
5DO
Electromechanical Type Master Trip Relay with 3NO+1NC
2 K86 110V DC 1 No. Alstom/ABB
Conatct, Flush Mounting
[D] INDICATING LAMP
1 H4 110V DC ON Indicating Lamp (Red) , LED Type 1 No. L&T (Esbee)
2 H5 110V DC OFF Indicating Lamp (Green), LED Type 1 No. L&T (Esbee)
3 H6 110V DC TRIP Indicating Lamp (Amber), LED Type 1 No. L&T (Esbee)
4 H8 110V DC Spring Charge Indicating Lamp (Blue), LED Type 1 No. L&T (Esbee)
5 H9 110V DC VCB In Test Indicating Lamp (White), LED Type 1 No. L&T (Esbee)
6 H10 110V DC VCB in Service Indicating Lamp (Yellow), LED Type 1 No. L&T (Esbee)
[C] PUSH BUTTON & SELECTOR SWITCH

1 S5 6A 1Pole, 2Ways, Without Off L/R Selector Switch, Rotary Type 1 No. Salzer

2 S4 Emergency Stop PB (Red) With 1NC+2NO Contact 1 No. L&T (Esbee)


[D] OTHER CONTROL COMPONENTS
TNC, 1 Pole, 2 Ways, Spring Return to Neutral, Pistol Grip
1 S6 32A 1 No. Switron
Handle, Angular Movement : 45+45°, Rotary Type
R94,RS,RT, Omron/BCH/PLA/OEN/PHOEN
2 110V DC 4 C/O Aux. Relay for Antipumping Application,Service,Test 4 No.
LS IX
Omron/BCH/PLA/OEN/PHOEN
3 R1 230V AC 4 C/O Aux. Relay for AC Fail 1 No.
IX
Omron/BCH/PLA/OEN/PHOEN
4 R3 110V DC 4 C/O Aux. Relay for DC Fail 1 No.
IX
5 F2-F5 6A DP Control MCB 3 Nos. Schneider
1K1,2K1, Schneider/ABB
6 110V DC 2NO+2NC Aux. Contactor 3 Nos.
3K1
Schneider/ABB
7 KX1 & KX2 110V AC 2NO+2NC Aux. Contactor 2 Nos.

1K2,2K2, Schneider/ABB
8 110V AC 9A, 4P Power contactor with 2NC conatct for PT Interlocking 3 Nos.
3K2
90-270V
9 H Hooter, 96X96mm 1 No. Proton/Arihant
AC/DC
[E] MICELENIOUS ITEMS
1 PL 230V AC Panel Light Holder 1 No. Anchor/or equivalent
2 RDLS Door Limit Switch 1 No. Jainson/Suraj/or equivalent
3 F11 6A SP Control MCB 1 No. Schneider
4 X2-X6, Control Terminals Lot Elmex/Connectwell
5 End Plate with End Clamp for Control Terminals Lot Elmex/Connectwell
6 XT1,XPT C.T. Terminals Set 1Set Elmex/Connectwell
RR Kable/Polycab/
Copper Flexible Wire Lot
7 Finolex/KEI/Lapp
BILLS OF MATERIAL / BILLS OF QUANTITY
CLIENT:- M/S. Prathama Solar connect Energy Pvt Ltd Job. No.:- JAA401/0305/01 Rev.:-R1
(PSEPL)

PROJECT:-75MWp/55MW Ground Mounted Solar PV Power Drg. No. :- SS/JAA401/420


Date:- 16.05.2020
Plant, Veppankulam Village, Devakottai, TamilNadu

SCOPE:- OE Services for 75MWp/55MW Ground Mounted


Solar PV Power Plant
OWNERS ENGINEERS:-M/S. TUV India Pvt. Ltd PO NO.:-
EPC CONTRACTOR:-M/S. Prozeal Infra Engineering Pvt
Ltd NAME OF PANEL:-33KV,700Amp,25Ka/3sec OUTDOOR TYPE
EPC DESIGN CONSULTANT:-M/S. Arbutus Consultants Pvt PANEL
Ltd
SR. NO. TAG NO. RATING DISCRIPTION QTY MAKE TYPE/PART NO.
33kV HT VCB OUTGOING 100KVA AUX. TRAFO FEEDER- 1 1 No.
[A] VACUUM CIRCUIT BREAKER
1 Q52 630A 33kV Drawout Type VCB (STR: 26.3kA for 3 Sec.) 1 No. Schneider
6NO+6NC Contact With inbuilt Mechanical Anti -
Pumping Feature
2 230V AC Spring Charging Motor 1 No. Schneider
3 110V DC Closing Coil 1 No. Schneider
4 110V DC Tripping Coil 1 No. Schneider
[B] CURRENT TRANSFORMER

1 CT1-3 30/1A Core-1, Class-0.5S, 2.5VA


ECS/SEI/Pragati/Precise/Starlit
Core-2, Class-5P10, 2.5VA 3 Nos. e Electrical/Schneider App. Resin Cast
Vendor
CT Secondary Termination on P2 Side

ECS/SEI/Pragati/Precise/Starlit
2 CBCT 30/1A Core balance current transformer,2.5VA 1 No. e Electrical/Schneider App.
Vendor
[C] RELAYS
Numerical, Communicable IDMT Relay, 3O/C + 1E/F with
1 K51 110V DC Highset (50/50N/51/51N/95/94F), Flush Mounting with 8DI 1 No. Schneider/ABB/Alsthom MicomP111/Equi.
and 5DO
Electromechanical Type Master Trip Relay with 3NO+1NC
2 K86 110V DC 1 No. Alstom/ABB
Conatct, Flush Mounting

K631 110V DC Transformer Fault Aux. Relay, 5 No. ABB/Schneider/OEN/ PHOENIX


3
[D] METERS
Digital Multifunction Meter with RS-485 port,CL-1, Schneider/
1 P3 110V AC 1 No.
96X96mm, Secure/Elmeasure
Digital Type Ammeter With in built Selector Switch, Schneider/
2 P2 110V AC 1 No.
96X96mm, Secure/Elmeasure
[E] INDICATING LAMP
1 H4 110V DC ON Indicating Lamp (Red) , LED Type 1 No. L&T (Esbee)
2 H5 110V DC OFF Indicating Lamp (Green), LED Type 1 No. L&T (Esbee)
3 H6 110V DC TRIP Indicating Lamp (Amber), LED Type 1 No. L&T (Esbee)
4 H8 110V DC Spring Charge Indicating Lamp (Blue), LED Type 1 No. L&T (Esbee)
5 H9 110V DC VCB In Test Indicating Lamp (White), LED Type 1 No. L&T (Esbee)
6 H10 110V DC VCB in Service Indicating Lamp (Yellow), LED Type 1 No. L&T (Esbee)
[F] PUSH BUTTON & SELECTOR SWITCH

1 S5 6A 1Pole, 2Ways, Without Off L/R Selector Switch, Rotary Type 1 No. Salzer

2 S4 Emergency Stop PB (Red) With 1NC+2NO Contact 1 No. L&T (Esbee)


[G] OTHER CONTROL COMPONENTS
TNC, 1 Pole, 3 Ways, Spring Return to Neutral, Pistol Grip
1 S6 32A 1 No. Switron
Handle, Angular Movement : 45+45°, Rotary Type
R94,RS,RT, Omron/BCH/PLA/OEN/PHOEN
2 110V DC 4 C/O Aux. Relay for Antipumping Application,Service,Test 4 No.
LS IX
Omron/BCH/PLA/OEN/PHOEN
3 R1 230V AC 4 C/O Aux. Relay for AC Fail 1 No.
IX
Omron/BCH/PLA/OEN/PHOEN
4 R3 110V DC 4 C/O Aux. Relay for DC Fail 1 No.
IX
5 F1 6A FP Control MCB for Metering 1 No.
Schneider
6 F2-F4 6A DP Control MCB 3 Nos.

7 AN 110V DC 12 Window Annunciator With Accept, Reset ,Test Push Button 1 No. EAPL/Minilec/GIC

8 SA 30KV , 10KA Surge arraster , CL-2 1Set Mecol/Nelson


[H] MICELENIOUS ITEMS
1 PL 230V AC Panel Light Holder 1 No. Anchor/or equivalent
2 SH 80W Space Heater 1 No. Girishgo/or equivalent
3 RDLS Door Limit Switch 1 No. Jainson/Suraj/or equivalent
4 TH Thermostate, 30°-85°C 1 No. Girishgo/or equivalent
5 F11-12 6A SP Control MCB 2 Nos. Schneider
6 X2-X6,XSH Control Terminals Lot Elmex/Connectwell
7 End Plate with End Clamp for Control Terminals Lot Elmex/Connectwell
8 XT1,XPT C.T. & P.T. Terminals Set 1Set Elmex/Connectwell
RR Kable/Polycab/
Copper Flexible Wire Lot
9 Finolex/KEI/Lapp
33kV HT VCB INCOMER-2&4 FEEDER [FROM 11.6MVA PANEL] 2 No.
[A] VACUUM CIRCUIT BREAKER
1 Q52 630A 33kV Drawout Type VCB (STR: 26.3kA for 3 Sec.) 1 No. Schneider
6NO+6NC Contact With inbuilt Mechanical Anti -
Pumping Feature
2 230V AC Spring Charging Motor 1 No. Schneider
3 110V DC Closing Coil 1 No. Schneider
4 110V DC Tripping Coil 1 No. Schneider
[B] CURRENT TRANSFORMER

CT1-3 250/1A Core-1, Class-0.5S, 5VA


1

Core-2, Class-5P10, 5VA 3 Nos. ECS/SEI/Pragati/Precise/Starlit Resin Cast


e Electrical/Schneider App.
Vendor
CT Secondary Termination on P1 Side

ECS/SEI/Pragati/Precise/Starlit
2 CBCT 250/1A Core balance current transformer,5VA 1 No. e Electrical/Schneider App.
Vendor
[C] RELAYS
Numerical, Communicable IDMT Relay, 3O/C + 1E/F with
1 K51 110V DC Highset (50/50N/51/51N/95/94F), Flush Mounting with 8DI 1 No. Schneider/ABB/Alsthom MicomP111/Equi.
and 5DO
Electromechanical Type Master Trip Relay with 3NO+1NC
2 K86 110V DC 1 No. Alstom/ABB
Conatct, Flush Mounting
BILLS OF MATERIAL / BILLS OF QUANTITY
CLIENT:- M/S. Prathama Solar connect Energy Pvt Ltd Job. No.:- JAA401/0305/01 Rev.:-R1
(PSEPL)

PROJECT:-75MWp/55MW Ground Mounted Solar PV Power Drg. No. :- SS/JAA401/420


Date:- 16.05.2020
Plant, Veppankulam Village, Devakottai, TamilNadu

SCOPE:- OE Services for 75MWp/55MW Ground Mounted


Solar PV Power Plant
OWNERS ENGINEERS:-M/S. TUV India Pvt. Ltd PO NO.:-
EPC CONTRACTOR:-M/S. Prozeal Infra Engineering Pvt
Ltd NAME OF PANEL:-33KV,700Amp,25Ka/3sec OUTDOOR TYPE
EPC DESIGN CONSULTANT:-M/S. Arbutus Consultants Pvt PANEL
Ltd
SR. NO. TAG NO. RATING DISCRIPTION QTY MAKE TYPE/PART NO.
[D] METERS
Digital Multifunction Meter with RS-485 port,CL-1, Schneider/
1 P3 110V AC 1 No.
96X96mm, Secure/Elmeasure
Digital Type Ammeter With in built Selector Switch, Schneider/
2 P2 110V AC 1 No.
96X96mm, Secure/Elmeasure
[E] INDICATING LAMP
1 H4 110V DC ON Indicating Lamp (Red) , LED Type 1 No. L&T (Esbee)
2 H5 110V DC OFF Indicating Lamp (Green), LED Type 1 No. L&T (Esbee)
3 H6 110V DC TRIP Indicating Lamp (Amber), LED Type 1 No. L&T (Esbee)
4 H8 110V DC Spring Charge Indicating Lamp (Blue), LED Type 1 No. L&T (Esbee)
5 H9 110V DC VCB In Test Indicating Lamp (White), LED Type 1 No. L&T (Esbee)
6 H10 110V DC VCB in Service Indicating Lamp (Yellow), LED Type 1 No. L&T (Esbee)
[F] PUSH BUTTON & SELECTOR SWITCH

1 S5 6A 1Pole, 2Ways, Without Off L/R Selector Switch, Rotary Type 1 No. Salzer

2 S4 Emergency Stop PB (Red) With 1NC+2NO Contact 1 No. L&T (Esbee)


[G] OTHER CONTROL COMPONENTS
TNC, 1 Pole, 3 Ways, Spring Return to Neutral, Pistol Grip
1 S6 32A 1 No. Switron
Handle, Angular Movement : 45+45°, Rotary Type
R94,RS,RT, Omron/BCH/PLA/OEN/PHOEN
2 110V DC 4 C/O Aux. Relay for Antipumping Application,Service,Test 4 No.
LS IX
Omron/BCH/PLA/OEN/PHOEN
3 R1 230V AC 4 C/O Aux. Relay for AC Fail 1 No.
IX
Omron/BCH/PLA/OEN/PHOEN
4 R3 110V DC 4 C/O Aux. Relay for DC Fail 1 No.
IX
5 F1 6A FP Control MCB for Metering 1 No.
Schneider
6 F2-F4 6A DP Control MCB 3 Nos.

7 AN 110V DC 6 Window Annunciator With Accept, Reset ,Test Push Button 1 No. EAPL/Minilec/GIC

8 SA 30KV , 10KA Surge arraster , CL-2 1 Set Nelson/Mecol/Equi.


[H] MICELENIOUS ITEMS
1 PLS 20A 3 Pin Plug Socket 1 No. Anchor/or equivalent
2 PL 230V AC Panel Light Holder 1 No. Anchor/or equivalent
3 RDLS Door Limit Switch 1 No. Jainson/Suraj/or equivalent
4 SH 80W Space Heater 1 No. Girishgo/or equivalent
5 TH Thermostate, 30°-85°C 1 No. Girishgo/or equivalent
6 F11-12 6A SP Control MCB 2 Nos. Schneider
7 X2-X6,XSH Control Terminals Lot Elmex/Connectwell
8 End Plate with End Clamp for Control Terminals Lot Elmex/Connectwell
9 XT1,XPT C.T. & P.T. Terminals Set 1Set Elmex/Connectwell
RR Kable/Polycab/
Copper Flexible Wire Lot
10 Finolex/KEI/Lapp
33kV HT VCB INCOMER-1&3 FEEDER [FROM 17.4MVA PANEL] 2 No.
[A] VACUUM CIRCUIT BREAKER
1 Q52 630A 33kV Drawout Type VCB (STR: 26.3kA for 3 Sec.) 1 No. Schneider
6NO+6NC Contact With inbuilt Mechanical Anti -
Pumping Feature
2 230V AC Spring Charging Motor 1 No. Schneider
3 110V DC Closing Coil 1 No. Schneider
4 110V DC Tripping Coil 1 No. Schneider
[B] CURRENT TRANSFORMER

CT1-3 350/1A Core-1, Class-0.5S, 5VA


1

Core-2, Class-5P10, 5VA 3 Nos. ECS/SEI/Pragati/Precise/Starlit Resin Cast


e Electrical/Schneider App.
Vendor
CT Secondary Termination on P1 Side

ECS/SEI/Pragati/Precise/Starlit
2 CBCT 350/1A Core balance current transformer,5VA 1 No. e Electrical/Schneider App.
Vendor
[C] RELAYS
Numerical, Communicable IDMT Relay, 3O/C + 1E/F with
1 K51 110V DC Highset (50/50N/51/51N/95/94F), Flush Mounting with 8DI 1 No. Schneider/ABB/Alsthom MicomP111/Equi.
and 5DO
Electromechanical Type Master Trip Relay with 3NO+1NC
2 K86 110V DC 1 No. Alstom/ABB
Conatct, Flush Mounting
[D] METERS
Digital Multifunction Meter with RS-485 port,CL-1, Schneider/
1 P3 110V AC 1 No.
96X96mm, Secure/Elmeasure
Digital Type Ammeter With in built Selector Switch, Schneider/
2 P2 110V AC 1 No.
96X96mm, Secure/Elmeasure
[E] INDICATING LAMP
1 H4 110V DC ON Indicating Lamp (Red) , LED Type 1 No. L&T (Esbee)
2 H5 110V DC OFF Indicating Lamp (Green), LED Type 1 No. L&T (Esbee)
3 H6 110V DC TRIP Indicating Lamp (Amber), LED Type 1 No. L&T (Esbee)
5 H8 110V DC Spring Charge Indicating Lamp (Blue), LED Type 1 No. L&T (Esbee)
6 H9 110V DC VCB In Test Indicating Lamp (White), LED Type 1 No. L&T (Esbee)
7 H10 110V DC VCB in Service Indicating Lamp (Yellow), LED Type 1 No. L&T (Esbee)
BILLS OF MATERIAL / BILLS OF QUANTITY
CLIENT:- M/S. Prathama Solar connect Energy Pvt Ltd Job. No.:- JAA401/0305/01 Rev.:-R1
(PSEPL)

PROJECT:-75MWp/55MW Ground Mounted Solar PV Power Drg. No. :- SS/JAA401/420


Date:- 16.05.2020
Plant, Veppankulam Village, Devakottai, TamilNadu

SCOPE:- OE Services for 75MWp/55MW Ground Mounted


Solar PV Power Plant
OWNERS ENGINEERS:-M/S. TUV India Pvt. Ltd PO NO.:-
EPC CONTRACTOR:-M/S. Prozeal Infra Engineering Pvt
Ltd NAME OF PANEL:-33KV,700Amp,25Ka/3sec OUTDOOR TYPE
EPC DESIGN CONSULTANT:-M/S. Arbutus Consultants Pvt PANEL
Ltd
SR. NO. TAG NO. RATING DISCRIPTION QTY MAKE TYPE/PART NO.
[F] PUSH BUTTON & SELECTOR SWITCH

1 S5 6A 1Pole, 2Ways, Without Off L/R Selector Switch, Rotary Type 1 No. Salzer

2 S4 Emergency Stop PB (Red) With 1NC+2NO Contact 1 No. L&T (Esbee)


[G] OTHER CONTROL COMPONENTS
TNC, 1 Pole, 3 Ways, Spring Return to Neutral, Pistol Grip
1 S6 32A 1 No. Switron
Handle, Angular Movement : 45+45°, Rotary Type
R94,RS,RT, Omron/BCH/PLA/OEN/PHOEN
2 110V DC 4 C/O Aux. Relay for Antipumping Application,Service,Test 4 No.
LS IX
Omron/BCH/PLA/OEN/PHOEN
3 R1 230V AC 4 C/O Aux. Relay for AC Fail 1 No.
IX
Omron/BCH/PLA/OEN/PHOEN
4 R3 110V DC 4 C/O Aux. Relay for DC Fail 1 No.
IX
5 F1 6A FP Control MCB for Metering 1 No.
Schneider
6 F2-F4 6A DP Control MCB 3 Nos.

7 AN 110V DC 6 Window Annunciator With Accept, Reset ,Test Push Button 1 No. EAPL/Minilec/GIC

8 SA 30KV , 10KA Surge arraster , CL-2 1 Set Nelson/Mecol/Equi.


[H] MICELENIOUS ITEMS
1 PLS 20A 3 Pin Plug Socket 1 No. Anchor/or equivalent
2 PL 230V AC Panel Light Holder 1 No. Anchor/or equivalent
3 RDLS Door Limit Switch 1 No. Jainson/Suraj/or equivalent
4 SH 80W Space Heater 1 No. Girishgo/or equivalent
5 TH Thermostate, 30°-85°C 1 No. Girishgo/or equivalent
6 F11-12 6A SP Control MCB 2 Nos. Schneider
7 X2-X6,XSH Control Terminals Lot Elmex/Connectwell
8 End Plate with End Clamp for Control Terminals Lot Elmex/Connectwell
9 XT1,XPT C.T. & P.T. Terminals Set 1Set Elmex/Connectwell
RR Kable/Polycab/
Copper Flexible Wire Lot
10 Finolex/KEI/Lapp