Professional Documents
Culture Documents
Datasheet Himoinsa 60kva Stage V
Datasheet Himoinsa 60kva Stage V
Datasheet Himoinsa 60kva Stage V
Powered by FPT_IVECO
POWER kVA 60 60
POWER kW 48 48
1 1
AVAILABLE VOLTAGES V 230/132 · 230 V (t)
3 2 RATED AT POWER
FACTOR Cos Phi 0,8
5 5 SOUNDPROOFED RENTAL
CS5R
Outputs
230volt WATER-COOLED
2x 230 volt 16amp No1
THREE PHASE
400volt
1x 400volt 16amp No2
1x 400volt 32 amp No3
1x 400 volt 63amp No4 50 HZ
1x powerlocks (loose cable + quick connector) No5
1x terminal strip (loose cables)
terminal strip located inside the cabinet STAGE V
Adblue
Consumption
DIESEL
Machine is not equipped with adBlue
Himoinsa has the right to modify any feature without prior notice.
Weights and dimensions based on standard products. Illustrations may
include optional equipment.
Technical data described in this catalogue correspond to the available
information at the moment of printing.
The illustrations and images are indicative and may not coincide in their
entirety with the product.
Industrial design under patent.
2021-NOV.-09 08:37
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HRFW-60 S5
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HRFW-60 S5
SOUND PRESSURE
Sound pressure level dB(A)@7m 62 ± 2,4
APPLICATION DATA
EXHAUST SYSTEM NECESSARY AMOUNT OF AIR
Maximum allowed back pressure mbar 220 Cooling Air Flow m³/s 1
Exhaust Flange Size (external Alternator fan air flow m³/s 0,197
mm 90
diameter)
Soundproofed version
• Steel chassis • Fuel level gauge • External filling of the fuel tank with safety
key
• Manhole to fill the radiator • Bodywork made from high quality steel
plate • Emergency stop button (double emergency
• Pre-installation or niche to house the quick stop protection: Interior on the panel +
connection hydraulic fittings for fuel transfer • High mechanical strength Exterior on the bodywork)
• Anti-leakage chassis, predisposed to retain • Low noise emissions level • Mechanized for power cable output
liquids (retention tray)
• Soundproofing provided by high-density • Door with window to visualize control panel,
• Manhole for fuel tank cleaning and drainage volcanic rock wool alarms and measurements
• Tilting cap in the exhaust • Epoxy polyester powder coating • Pressure locks
• Anti-vibration shock absorbers • Full access for maintenance (water, oil and • IP Protection according to ISO
filters, no need to remove the canopy) 8528-13:2016
• Chassis with integrated fuel tank
• Oil sump extraction kit
2021-NOV.-09 08:37
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HRFW-60 S5
FEATURES OF THE
CONTROL UNITS
CEM 7
Voltage between phases •
Voltage between neutral and phase •
Current intensities •
Generator Readings
Frequency •
Apparent power (Kva) •
Active power (Kw) •
Reactive power (kVAr) •
Power factor •
Voltage between phases
Voltage between phases and neutral
Current intensities
Frequency
Mains Readings
Apparent power
Active power
Reactive power
Power factor
Coolant temperature •
Oil pressure •
Engine Readings
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HRFW-60 S5
CEM 7
High frequency •
Low frequency •
High voltage •
Low voltage •
Alternator Protections
Short-circuit •
Asymmetry between phases •
Incorrect phase sequence •
Inverse power •
Overload •
Genset signal drop •
Total hour counter •
Partial hour counter •
Kilowatt meter •
Starts valid counters •
Counters
GSM/GPRS modem ⓪
Remote screen ⓪
Tele signal ⓪ (8 + 4)
J1939 ⓪
Alarm history •
(10) / (opc. +100)
External start •
Start inhibition •
Mains failure start
Start under normative EJP •
Pre-heating engine control •
Genset contactor activation •
Mains & Genset contactor activation
Fuel transfer control •
Engine temperature control •
Manual override •
Programmable alarms •
Genset start function in test mode •
Features
Programmable outputs •
Multilingual •
GPS Positioning ⓪
Synchronisation
Special Functions
⓪
Mains synchronization ⓪
Second Zero elimination ⓪
RAM7 ⓪
Remote screen ⓪
• Standard Optional
2021-NOV.-09 08:37
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HRFW-60 S5
CONTROL
PANELS
M5
Digital manual Auto-Start control panel and thermal magnetic protection (depending on current and
voltage) and differential with CEM7.
Digital control unit CEM7
Electrical system
• M5 control panel with electronic • Adjustable earth leakage • Starter battery/ies installed
CEM7 control unit and switched protection (time & sensitivity) (cables and bracket included)
emergency stop standard in M5 and AS5, with
thermal magnetic protection • Ground connection electrical
• Power panel with built-in circuit installation with connection
breaker plates • 4-pole thermal magnetic circuit ready for ground spike (not
breaker supplied)
• Safety relay in output terminal
board (thermal magnetic trip • Battery charger alternator with • Battery Switch (Opcional).
and alarm in control unit) ground connection
2021-NOV.-09 08:37
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com