Service Report 12324
Service Report 12324
Serial No. 2T11010262242000T Notes and SBR2 MOTOR FAILED THE WINDING
Recommendation: INSULATION RESISTANCE.(see test
report)
REINSULATION OF SBR2 MOTOR IS
NEEDED FOR THE OPERATION OF THE
SOFT STARTER.(see temporary
operation procedure)
Check operating current regularly.
Complete commissioning and
testing of ABB soft starter.
Service Details
Engineer’s Remarks TESTING WAS DONE AND APPROVED BY: Mr. Nathaniel Aldave
Page | 1
SUPERVISED BY:
Page | 2
TEMPORARY OPERATIONAL START-UP MANUAL
I. TURN THE MAIN CIRCUIT BREAKER OF THE SOFT STARTER PANEL TO ‘’ON –
POSITION’’.
II. TURN THE CIRCUIT BREAKER OF THE ‘’230V CONTROLS’’ OF SOFT STARTER
PANEL TO ‘’ON –POSITION’’.
D. MOTOR WILL RUN FOR 2 HOURS THEN WILL TURN OFF AUTOMATICALLY.
F. MOTOR 2 WILL RUN, HOWEVER THE CIRCUIT BREAKER IS OFF BECAUSE SBR2 MOTOR
HAS FAILED WINDING INSULATION RESISTANCE AND OVER CURRENT IS OCCURING
RENDERING SBR2 UNOPERATIONAL UNTIL REPAIRED/REPLACED.
G. THIS WILL TRIGGER FAULTY CONNECTION ERROR IN THE SOFT STARTER, PRESS THE
STOP BUTTON AND RESET THE FAULT IN THE SOFT STARTER THEN RESTART THE PANEL.
H. REPEAT THE PROCEDURE FROM THE START TO RUN THE SBR1 MOTOR.
Page | 3
PREPARED BY:
Page | 4
SBR2 TEST RESULT