INSPECTION REPORT 19

Third Party Service - Third Party Inspections for


PHCC/TAC/73/2021 for Aluminum, Mashrabia and Skylight System

Buildings and Infrastructure Department

Client: COMO Facilities Management Services

Report Reference DOA.21.CIV.193.70_AMS/IR19

Revision 0
Date of Issue: January 25, 2024

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar i
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

INSPECTION REPORT 19
Date of
Report Ref. DOA.21.CIV.193.70_AMS/IR19 Rev. 0 January 25, 2024
Issue:

BV Client COMO Facilities Management Services

Project THIRD PARTY INSPECTIONS FOR PHCC/TAC/73/2021

Project Owner PHCC

Consultants Supervision : N/A

Main Contractor N/A

Inspection Dates 21st and 24th of January 2024

BV Inspector Donnie Fiesta Ganal

Donnie Fiesta Ganal Inspector, Bureau Veritas


Attendees
Mohamed Mosin Representative, COMO

Inspection Location PHCC/TAC/73/2021 – Muaither HC

Type: Purpose:
☐ Test Witnessing ☐ IDI (Inherent Defects Insurance)
Inspection  Visual Inspection  Civil/Structural Inspection
☐ Document Review ☐ MEP Inspection
☐ Others (specify)

☐ Preliminary Works  Operation & Maintenance


Stage ☐ Construction Stage ☐ Final Inspection
☐ Commissioning Stage

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 1
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

TABLE OF CONTENTS

LIST OF FIGURES ............................................................................................................................................ 2


LIST OF TABLES ............................................................................................................................................. 2
1 INTRODUCTION ........................................................................................................................................ 3
2 SCOPE OF WORKS................................................................................................................................... 3
3 REFERENTIAL DOCUMENTS .................................................................................................................. 3
4 EQUIPMENT ............................................................................................................................................... 3
5 INSPECTION FINDINGS ............................................................................................................................ 4
5.1 Aluminum ......................................................................................................................................... 4
5.1.1 Basement 1 .................................................................................................................................. 4
5.1.2 Ground Floor................................................................................................................................ 5
5.1.3 First Floor ................................................................................................................................... 10
5.2 Mashrabiya ..................................................................................................................................... 12
5.2.1 Ground Floor.............................................................................................................................. 12
5.2.2 First Floor ................................................................................................................................... 14
5.2.3 Roof ............................................................................................................................................ 15
5.3 Skylight ........................................................................................................................................... 18
5.3.1 Roof ............................................................................................................................................ 18
6 CONCLUSION & RECOMMENDATIONS ............................................................................................... 22
7 ATTACHMENTS....................................................................................................................................... 22

LIST OF FIGURES
LIST OF TABLES

Table 3.1: List of referential documents ....................................................................................................... 3


Table 4.1: List of Equipment .......................................................................................................................... 3

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 2
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

1 INTRODUCTION

BUREAU VERITAS INTERNATIONAL DOHA (L.L.C), herein referred to as Bureau Veritas, prepared this
INSPECTION REPORT 19 (Ref. DOA.21.CIV.193.70_AMS/IR19 dated on January 25, 2024) for COMO
FACILITIES MANAGEMENT SERVICES for the Third-Party Service - Third Party Inspections for
PHCC/TAC/73/2021.

2 SCOPE OF WORKS

The third-party services that BV provides for COMO includes the maintenance inspection of the following for
Primary Health Care Centers in Qatar:
A. Aluminum/Mashrabia/Skylight System – Yearly for 16 HC’s: 16 visits per year.

Upon completion of any inspection, inspection will be prepared and submitted to COMO. The inspection
report will contain the findings of the inspection, recommendations if testing (DT or NDT) is required and/or
preventive or corrective action must be undertaken.

3 REFERENTIAL DOCUMENTS

Table 3.1: List of referential documents


Title Reference No. Rev. Approval
Qatar Construction Specification 2014
Al Muaither Clinic – Prototype C Site & Q11025-0100D-CD-MT-A-
2
Location Plans 050
First Basement Floor Plan PHCC-MUA-AR-1B-102 3
Ground Floor Plan PHCC-MUA-AR-GF-100 3
First Floor Plan PHCC-MUA-AR-FF-101 4

4 EQUIPMENT

Table 4.1: List of Equipment


Calibration Calibration
Description Manufacturer Model ID No.
Date Due
Thermal Imager Fluke TiS55+ 21030126 18-05-2023 17-05-2024

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 3
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

5 INSPECTION FINDINGS

5.1 Aluminum
5.1.1 Basement 1
1. Aluminum glass door and window at Basement 1 Wellness Center (C0023) was checked. The aluminum
windows are free from any damages. Frames are straight with no sharp edges. Seal with glass is in
good condition and no noticeable severe wear.

Figure 5:1 Aluminum Door and Window at Basement 1 Wellness Center

Figure 5:2 Aluminum Windows Glass Seals

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 4
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

5.1.2 Ground Floor


1. Aluminum windows around the buildings at Muaither Health Center ground floor was checked. The
windows are in good condition. Aluminum are free from defects and gaskets on window frame shows no
sign of wear. Gaps between window frame and concrete / stone is installed with sealant.

Figure 5:3 Aluminum Window around Building

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 5
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

2. Aluminum windows around the buildings at Muaither Health Center ground floor was checked from the
inside. Some of the aluminum windows have started to develop gaps on the applied sealant in between
concrete and the aluminum window frame. Sealant to be applied on the said gaps to prevent air and
moisture penetration.

Figure 5:4 Gaps on Sealant between Aluminum Frame and Ceiling at Isolation Room (C1073)

3. Aluminum doors and windows were checked on the entrances around the building of the health center.
The entrance door at EMS Room (C1100b) was poorly applied with seal around the glass with a white
colored sealant.

Figure 5:5 Poor Application of Seal Around Glass Door Entrance to EMS Room (C1100b)

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 6
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

4. Aluminum Louvers on windows around the building was checked. The louvers are in good condition with
no defects noticed. The sealant applied between the aluminum and adjacent surface are still in good
condition with no major sign of wear.

Figure 5:6 Aluminum Louvers

5. Aluminum canopy and columns were checked on the entrances around the building of the health center.
The aluminum is starting to show signs of wear. Aluminum needs to be cleaned.

Figure 5:7 Signs of wear on Canopy Finish at Receiving (C1048a)

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 7
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

Figure 5:8 Peeling-off Aluminum Canopy Finish at Entrance Vestibule (C1061a)

Figure 5:9 Minor Scratches at Column at Entrance Vestibule (C1096b)

Figure 5:10 Scratches on Aluminum Canopy at Receiving (C1048a)

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 8
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

6. Aluminum Sliding Doors were checked. The aluminum frame of the sliding door at Entrance of Vestibule
(C1061a) were noticed to have its bottom frame to be worn with its finish stripped.

Figure 5:11 Worn Bottom Sliding Door Frame at Entrance Vestibule (C1061a)

7. Aluminum glass installed beside the stairs along the corridor was checked. The aluminum was observed
to have small dents on the vertical frame.

Figure 5:12 Aluminum Glass Frame beside the Stairs

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 9
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

5.1.3 First Floor


1. Aluminum windows at first floor above the entrance was checked. Aluminum is plumb and straight.
Seals and gaskets are in good condition.

Figure 5:13 Aluminum Window at First Floor

2. Aluminum around the balcony was checked and found to be in good condition. Aluminum canopies
needs to be cleaned. Seals shows no sign of gaps or major wear.

Figure 5:14 Aluminum Canopy at Balcony

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 10
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

3. Aluminum was checked at the balcony. Aluminum is plumb and with no sharp edges at corners. Seals
and gaskets around the glass are in good condition.

Figure 5:15 Aluminum Beam at Balcony

4. Aluminum windows in different rooms was checked and found to be in good conditions. Sealants around
the aluminum frame are in good condition with no signs of wear or gaps.

Figure 5:16 Aluminum Window at Podiatry Room (C2036)

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 11
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

5.2 Mashrabiya
5.2.1 Ground Floor
1. Mashrabia at façade main entrance were checked. No dents were found, and seals are in good
condition. Joint seals were in good condition and no signs of wear or gaps observed. However, paints
were noticed to have minor scratches on the mashrabiya.

Figure 5:17 Mashrabiya at Main Entrance

Figure 5:18 Mashrabiya at Back of Building

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 12
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

2. Mashrabia at external building was checked. The mashrabiya installed on the ancillary building was
noticed to have its paint peeling off.

Figure 5:19 Mashrabiya at Ancillary

Figure 5:20 Paint Peeling-off on Mashrabiya at Ancillary Building

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 13
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

5.2.2 First Floor


1. Mashrabiya installed on the first-floor windows are in good condition and only needs to be cleaned from
dirt and stains. Seals are still in good condition with no major sign or wear.

Figure 5:21 Mashrabiya Bottom near Well Baby Assessment (B1047)

2. Mashrabia installed at the balcony was checked. Mashrabiya needs to be cleaned accordingly but are
still in good condition and shows no sign of defects.

Figure 5:22 First Floor Mashrabiya Installed at Balcony

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 14
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

5.2.3 Roof
1. Mashrabiya on the roof floor around the skylights was checked above the Large Courtyard. Seals
installed are in good condition. The Mashrabiya needs to be cleaned from stains and dirt.

Figure 5:23 Mashrabiya above Big Courtyard

Figure 5:24 Dirt and Stains on Mashrabiya

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 15
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

2. Mashrabiya on the roof floor around the skylight was checked above the Main Entrance Area. Seals
installed on the joints are still in good condition. Cleaning needs to be done to remove stains and dirt.

Figure 5:25 Mashrabiya above Main Entrance

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 16
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

3. Mashrabiya on the roof floor around the skylight of the Small Courtyard was checked. Seals installed on
the mashrabiya, and aluminum are still in good condition with no sign of gaps or major wear. Cleaning
needs to be done to remove dirt and stains.

Figure 5:26 Mashrabiya at Small Courtyard

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 17
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

5.3 Skylight
5.3.1 Roof
1. Skylight at Big Courtyard was checked. The glasses were in good condition with the aluminum having
no damages or defects. Seals and aluminum cover are in good condition. No noticeable leak marks are
observed from the inside.

Figure 5:27 Big Courtyard Skylight

Figure 5:28 Glass Joint Seal at Big Courtyard

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 18
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

2. Skylight at Small Courtyard was checked. The glasses were in good condition with the aluminum having
no damages or defects. Seals and aluminum cover are in good condition. No noticeable leak marks are
observed from the inside.

Figure 5:29 Small Courtyard Skylight

Figure 5:30 Glass Joint Seal at Small Courtyard Skylight

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 19
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

3. Skylight at Main Entrance was checked and found to be in good condition with no leaks observed during
the rain. Glasses are free from cracks or defects. Glass beads and aluminum frame are free from any
defects. Skylight needs to be cleaned.

Figure 5:31 Main Entrance Skylight

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 20
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

4. Thermographic imager was used to check the skylights to check if any temperature differences around
the skylight which indicates possible temperature leak. The skylight was measured to be in between 35
to 40 degrees Celsius with an average of about 38 degrees Celsius during the time of checking. No
temperature drop or spike were observed on the imager around the skylight.

Figure 5:32 Thermographic Imaging on Skylight

DOA.CIV.70.FO-01 REV-1
BUREAU VERITAS INTERNATIONAL DOHA (W.L.L)
First Floor, Building #35, D-Ring Road Old Airport Area Doha – Qatar 21
P.O. Box 22157 Tel: +974 4032 9729 | www.bureauveritas.com
INSPECTION REPORT 19
BUREAU VERITAS INTL.DOHA W.L.L. THIRD PARTY INSPECTIONS FOR
Buildings and Infrastructures Department PHCC/TAC/73/2021
COMO FACILITIES MANAGEMENT SERVICES
Report No.:
Rev: 0 Date of Issue: January 25, 2024
DOA.21.CIV.193.70_AMS/IR19

6 CONCLUSION & RECOMMENDATIONS

The inspection of the project PHCC/TAC/73/2021 for Primary Health Care Center (PHCC) at Muaither was
conducted. It was inspected for installed aluminum, mashrabiya and skylight. The aluminum and mashrabiya
were in good condition and show no major defects that could affect its performance. Minor scratches and paint
chipping were observed on both assets and needs to be cleaned from stains and dirt. The skylight was in good
working condition with noticeable visual signs of leaks and would just need to be maintained and cleaned.
Seals both between glasses and aluminum are still in good condition and shows no noticeable wear or
damage. Skylight were also checked using a Thermal Imaging equipment and no noticeable anomalies that
could indicate any problem. Contractor to do the necessary corrective action as per approved materials and
methodology of the client.

Schedule of next visit: TBA

7 ATTACHMENTS

Item Attachment Name Total Pages Description

1 Checklist 4 Aluminum, Mashrabia and Skylight checklist

Prepared by: Reviewed by: Approved by:

DONNIE FIESTA GANAL


QA/QC Engineer COMO Representative PHCC Representative
Buildings & Infrastructures COMO-EMMS PHCC
Department
Bureau Veritas International
Doha L.L.C.
Date of Issue: January 25, 2024
Distribution:  Client ☐ Consultant ☐ Others (specify)