普通商用泳池机说明书
普通商用泳池机说明书
Commercial Type
Thank you very much for purchasing our product, please keep and read this manual carefully before you
install heat pump.
Packing List
2 Wire-controller 1
2
Please keep installation manual properly, and read it carefully before using.
The unit must be installed by professional personnel, and install it based on this manual as
possible.
Special reminding: if the unit would be installed where is vulnerable to lightning stroke,
lightning protection measurements must be carried out.
Special reminding: The unit is not suitable for using in the Winter (< -7 °C), when the unit leave
unused in Winter, the water reserved in the pipe network system must be drained.
Content
1. Accessories Description.............................................................................4
8. Instruction of operation............................................................................19
1. Accessories Description
3
Each unit produced by our factory with the following accessories:
No. Name Qty. Use
1 Installation & Operation Manual 1 PC Guide users to install the system
2 Wire controller 1 PC Used for the man-machine operation interface
3 Wire controller power adapter 1 PC Power supply for controller
3 Wire controller connecting cable 1 PC Connect wired controller to heat pump unit
4 Heat pump unit 1 SET For heating water
For function you need to purchase at least the following parts for each unit:
No. Name Qty. use
1 Water circulation pump Drive the water cycle
2 Swimming pool filter system Protect the heat pump heat exchanger and pipes
3 Water pipe and valves Connect the equipment and make circulation
NOTE
The types and quantity of the water pump, filters, pipes and water tank, refer to the real project
design. We do not suggest to install auxiliary electric heaters in the system, if must install
auxiliary electric heaters, should install the electric heaters by the specialized persons, and our
company has no responsibility for all the problem cause by the auxiliary electric heater.
Range of application:
1.Power supply: 380V/3N~50Hz.
2.Operation ambient temperature range: -7°C〜43°C :
3.Water temperature range: Min. inlet water temperature 8°C, Max. outlet water
temperature 40°C. If the system is always used beyond the available water range,
please contact with the local agent.
● The installation shall be done by the professional persons, to prevent leaking, electric shock, or
fire disaster.
● Confirm the ground connection, if the ground connection is not correctly done, it may cause
electric shock.
4
● When install the heat pump in a narrow space (equipment room), must keep well ventilated.
● Don't put finger or sticker into the air inlet or air outlet. Because the internal rotor high-speed
operation may cause injury.
● When an exception happens (burning smell), turn off the manual power switch immediately, stop
operating, and contact with after-sale service department. If continue the abnormal operation, it may
cause electric shock or fire disaster.
● When the unit needs to be removed or re-installed, please entrust after-sale service department
and specialized personnel to do it. If the installation is not well done, it may cause unit operation
failure, electric shock, fire, hurt, leaking, etc.
● Must not be unauthorized reformed, otherwise it may cause electric shock or fire.
● Can not install the unit in combustible gas easy-leaking places, once the combustible gas leaks
around the unit, it may cause a fire.
● Confirm if the installation base is strong enough, if it is not strong and has been used for a long
time, it may cause falling and injuries.
● Confirm if leakage protection switch is installed, if don't install a leakage protection switch, may
cause electric shock or fire.
● When cleaning the unit, the operation should be stopped, and power switch should be turned off.
5
3. Heat pump unit working principle
● Second, the overheated vapour is exhausted into the condenser and exchange the heat with the
water, then the refrigerant is condensed and becomes the saturated or over cooling high pressure
and high temperature refrigerant liquid. The water is heated up by heat pump when absorbing the
heat energy which released by the refrigerant.
● Third, the refrigerant liquid releases the pressure by passing the expansion valve, then becomes
the low temperature and low pressure liquid.
● Fourth, the refrigerant liquid flows into the evaporator and absorb the energy from the air, then is
vaporized and became the low pressure and overheated vapour. The refrigerant working repeatedly
as described above, then the water which flows through the condenser is heated up constantly, the
temperature rise and can get the hot water.
Figure 1
Qc (Heat energy get) =Qa (Compressor consumption) +Qb (Heat energy absorbed from ambient environment)
6
4. Installation of the unit
● Avoid installation in locations where air contains salt or other corrosive gas.
● Make sure barrier-free for air inlet and outlet, also dry ventilated place.
● Make sure the bearing surface can meet the requirement and avoid shocks.
● The power supply and its capacity, wire diameter choice should be in accordance with the
electrical installation requirements.
● Electrical installation must comply with the relevant technical standards of electrical equipment,
and electrical insulation work must be done.
● The unit must be power on for at least eight hours before running and debugging.
7
4.3 Installation space
Keep the following indicated space for operation and maintenance first before installation
8
4.4 Heat pump unit size
YC-050TA1
YC-075TA1,YC-155TA1
Figure 4 Size
Size (mm)
L W H
Model No.
YC-050TA1 1410 748 1050
YC-075TA1 1590 850 1500
YC-155TA1 2150 1078 2258
9
4.5 Reserve the installation base for the heat pump
Please refer to Figure 5.
● Please use protective plate on the surface of the sets when moving, to avoid scratch and
deformation.
● The heat pump will produce condensation water,please consider the drainage channel when
make the installation base.
10
5. Installation of the pipeline
5.1 Attention
● Prevent air, dust and other sundries from going into the water pipes.
● Water inlet and outlet pipes shall be protected by the insulation layer.
● Stable water velocity shall be ensured, so that excessive throttling can be avoid.
● When moving, water inlet and outlet pipe shall not be used for hanging, only the holes on the
beam of the base can be used, please refer to Figure 9
● When connect the water inlet and outlet pipes, two pipe wrenches shall be used to control the two
parts of the pipes, and ensure the water inlet and outlet pipes not turning around, please refer to the
Figure 7
Figure 7
5.2 Instruction
5.2.1 Marginal data
11
5.2.2 Pipeline installation diagram
● The one-way valve is suggested for each unit, to prevent the water back flow.
● The system can be combined with multiple units, but should be controlled by each unit
independently.
● Regarding the installation of backup pump, maintenance valve and temperature measure point,
please consider it yourself.
● All pipes and valves of the unit need the heat preservation.
● The reference diagram used non-pressure water tank, the system also can be pressurized
system, use the pressurized water tank.
12
5.2.3 Selection of the water pipes
Model No. Inlet Outlet
YC-050TA1 65 mm 65 mm
YC-075TA1 65 mm 65 mm
YC-155TA1 100 mm 100 mm
● The pipe press and flow rate should be calculated before the diameter selection.
● The hydraulic calculation should be made after the selection of pipe diameter, if the resistance is
more than pump head, then need to choose a more power pump, or choose a bigger pipe.
NOTE
Please check the Electric Diagram which located inside of the unit
● The head of circulation pump = height difference between water level and main unit + total
pipelines resistance (determined by the hydraulic calculation) + pressure loss of main unit (see the
nameplate on heat pump ).
NOTE
When multi paralleled, the water pump head is subject to the worst working condition loop.
● The flow switch can be installed on the horizontal pipeline or the vertical pipeline which the fluid
flow direction is upward, but should not be installed on the vertical pipeline which the fluid flow
direction is downward.
● The flow switch must be installed on a straight pipeline, there must be more than five times the
length of the pipe diameter at its two sides. And, the direction of fluid must follow the arrow on the
13
controller. The terminal block should be in an easy operation position, (Figure 10)
● The pannier is absolutely forbid to touch the flow switch floor, or the switch will be deformed and
invalid, (Figure 11)
● Please be sure that the model of target sheet is determined by the system rated flow, diameter of
outlet pipe and the adjustable range of the target(see the user manual). And the target sheet can
not contact the in-wall of pipe or other throttlers in pipe, or will cause the switch can not reset.
Figure 10
Figure 11
● Unit power supply circuit must be ground, power supply wire and external grounding reliable
connection, and the external grounding is effective.
● Wiring must be constructed by the professional installation technicians in accordance with the
circuit diagram.
● Power line and signal line layout should be neat, reasonable, can not interfere with each other, but
not with the connecting pipe and the valve body contact.
● If the unit is not matching the power line, please supply specifications refer to provisions, wires
connecting is not allowed.
● After all wiring construction is completed, please check it before switch on the power supply
carefully.
14
Figure 11
NOTE:
Here only for signal control never drive
it directly.
15
Figure 15
Figure 16
16
Figure 17
7.5 Electric control schematic diagram of parallel connection of multiple units (Online)
Figure 18
17
7.5 Electric wiring diagram
18
Figure
19
8. Instruction of operation
20
8.2 Wire controller and operation
8.2.1 Appearance and button functions of wire controller
● Appearance
When there is no failure, the main interface will show on/off status,operation mode, water
tank water temperature, setting temperature, date and time; When there is failure, the main
interface will show the error code and error details.
If there is no operation within 60 seconds, the display backlight will be off, we can press any
key to turn on the light.
Status: Heating
2013/05/15 16:03
NOTE
If the signal wire connection is fault, signal wire A connect to signal wire B, then the controller
will not work, and only shows “ 欢 迎 使 用 ” , please exchange the wire connection, it will work
correctly.
欢迎使用
21
● Button functions
On/Off key
Press this key for five 5 seconds to turn on /off the power
Menu key:
Press this key to enter the next menu under the main interface
Return key:
Press this key return to the upper interface
Go Up Key
Enter key
Go Down key
Press menu key to enter the next menu under the main interface.
Running Status
Parameter Setting
Time Setting
Timer Set
● When chose the Running status, press key to entry into the on-line menu, and then
can choose one machine and press key to check the running status about the
machine. #1 On #9
#2 On #10
#3 #11
#4 #12
#5 #13
#6 #1422
#7 #15
#8 #16
Water Temp. 25°C
Water Outlet Temp. 25°C
1# Evaporator 25°C
1# Exhaust Temp. 25°C
● When chose the Parameter Setting, press key to entry into the parameter query
interface, press key to check each parameter, when choose a parameter and
press key to set the parameter, press can change the value, when finish
● When chose the Time Setting, press key to entry into the time set interface, press
key to choose date or time setting, when the cursor over the Date, then press
key entry into the date setting( year first), press key change value, then
press key entry into the month setting, press key to change the value, then
press key entry into the day setting, same method, and then press key will finish
the date set and back to upper interface;
When the cursor over the Time, press the key entry into time setting (hour first), press
23
key to change the value, press the key again will entry into minutes setting,
press key to change the value, finally press key to confirm time
Date:2013/05/15
Time: 13:58
● When chose the Timer Set, press key to entry into the timer set interface, press
Unit Timing
Supply Timing
Feeding Timing
NOTE
● When the cursor over the Unit Timing, press key entry into the unit timer on/off
setting, when the cursor over the 1#Timing On, press key and press key to
choose no or yes, when choose yes, press the key entry into time setting (hour first),
press key to change the value, press the key again will entry into minutes
24
About 1#Timing Off, 2#Timing On, 2#Timing Off, 3#Timing On, 3#Timing Off, the setting
method is the same as the above setting method.
1#Timing On: No
1#Timing Off: No
2#Timing On: No
2#Timing Off: No
3#Timing On: No
3#Timing Off: No
● When the cursor over the Supply Timing, press key entry into the Supply Timing,
setting method is the same as Unit Timing.
● When the cursor over the Feeding Timing, press key entry into the Supply Timing,
setting method is the same as Unit Timing.
● When the cursor over the Failure Logging, press key to check the failure record.
NOTE
When checking the failure record, press key for 5 seconds, can cancel all the previous
failure record.
25
When entry into a menu, press can return to the upper menu, finally will back to the
main interface.
8.2.5 Go up/Go down key
When entry into a menu or parameter setting interface, press , can change the
parameter value.
Press key for 5 seconds will turn on the hot water supply function, press again for 5
seconds then will turn off this function.
Press key for 5 seconds will lock the screen, press again for 5 seconds then will
unlock the screen.
Press key for 5 seconds will feed cold water by manual, press again for 5 seconds then
stop feeding cold water.
Press key for 5 seconds will change the operation mode, there are three models:
Heating mode, Cooling mode or Constant temperature mode(Auto mode).
26
● Dial switch 1
Dial switch 8 Dial switch 7 Dial switch 6 Dial switch 5
Single/Three phase(s) Single/Double system Direct/Cycle heating Swimming pool / Hot
water
0:Single (OFF) 0:Single 0:Cycle 0:Hot water
1:Three ON) 1:Double 1:Direct 1:Swimming pool
Press key for 5 seconds will turn on the auxiliary electric heater, press again for 5
seconds will turn off it.
Entry into the Running Status interface, choose the on-line machine no.,press for 5
seconds, the selected machine will be forced to defrost.
8.2.13 Parameter setting
When the cursor over the Parameter Setting, press key for 5 seconds, will entry into
the factory settings, input the password 0814 will entry into the factory setting interface,
input the password 6688 will entry into the factory limited time setting interface, when finish
inputting the password, the press key to entry the parameter query interface, press
27
, keys to choose the parameter, when choose a target parameter, the press
key to set it., press , keys to change the value, while finish setting, press to
confirm and go back to the query interface.
Enter Password
****
● Chinese-English shift : First press key for 5 seconds to lock the screen, and then
press key for long time to change the language (Chinese or English)
1) Initial Interface
WELCOME
2) Main Interface
28
Status: Heating
Water temp. 25 ℃ Set 50 ℃
Supply Feeding Heater
2013/05/15 16:03
NOTE
Running Status
Parameter Setting
Time Setting
Timer Set
Failure Logging
#1 On #9
#2 On #10
#3 #11
#4 #12
#5 #13
#6 #14
#7 #15
#8 #16
29
NOTE
1# Comp. Current 0A ▲
1# EEV 350
Standby Temp. -30°C
2# Evaporator 25°C ▼
NOTE
Fan Motor On ▲
Four-Way Valve Off
Circulating Pump On
1#By-Pass Valve Off ▼
Emergency SW Close ▲
Flow SW Close
1#High-Press. Close
1#Low-Press. Close ▼
2#High-Press. Close ▲
2#Low-Press. Close
31
NOTE
NOTE
Water Temp.Drop= The heat pump restart to work temperature difference against to the setting
target temp.
Water Outlet Set: Target setting hot water temp.
Start Heater Set: Auxiliary electric heater target hot water temp. Setting
Ambient Temp. Set: Auxiliary electric heater start-up ambient temp.
WR Cycle 60min ▲
WR Time 15min
WS Mode Duration
Water Supply Set 40°C ▼
32
WS Temp.Drop 5°C ▲
Feeding Mode Level
Exhaust Temp.Set 115°C
Exhaust Temp.RST 85°C▼
NOTE
Enter Password
****
33
Defrost EEV Set 400 ▲
EEV Least Value 100
EEV Mode Auto
EEV Manual 350 ▼
NOTE
Choice Pump: Yes=Choose a water pump, No=Don’t choose the water pump
Flow Switch Mode: All=Independent, Main=Shared
Feeding Timing No ▲
NOTE
Date:2013/05/15
Time: 13:58
34
9) Timer Setting Interface
Unit Timing
Supply Timing
Feeding Timing
1#Timing On: No
1#Timing Off: No
2#Timing On: No
2#Timing Off: No
3#Timing On: No
3#Timing Off: No
Warning #1 E02
Phase fault
Warning
Warning #1 E03
35
Flow Switch Off
Warning
Warning #1 E09
Anti Freezing
Warning
Warning #1 E11
1#Over-Pressure
Warning
Warning #1 E12
#1 E06 1#Over-Exhaust
1#Pressure Low
Warning
Warning #1 E13
#1 E07 2#Over-Exhaust
2#Over-Pressure
Warning
Warning #1 E15
2#Pressure Low
36
Warning #1 E22
1#Evaporator Fault
Warning
Warning #1 E23
2#Evaporator Fault
Warning
Warning #1 E25
1#Exhaust Fault
Warning
Warning #1 E27
2#Exhaust Fault
Warning
Warning #1 E29
Ambient Fault
Warning
Warning #1 E30
37
Warning
2# Back Temp. Fault
#1 E37
In-out Over-Temp.
Warning
Warning
#1 E31
#1 E42
Water Switch Fault
1# Condenser Fault
Warning
Warning
#1 E32
#1 E43
Outlet Over-temp.
2# Condenser Fault
Warning
Warning
# E35
#1 E44
1#Comp. Overload
Ambient Temp. Too Low
Warning
#1 E36
2#Comp. Overload
38
9. Adjusting and Initial operation
9.1 Attention
● Within 12 hours after running, please connect the circuit breaker, and make the
crankcase heater be preheated.
● Open the valve of water system, and the valve of assistant tank, inject water into the
system, and exhaust air inside.
● Do adjustment after electrical safety inspection.
● After the power is switched on, start the test running of heat pump, to see if it can function
well.
● Forced operation is forbidden, because it is very dangerous to work without protector.
39
● The supply voltage can meet the requirement of rated voltage.
● Air inlet and outlet function can work well.
● Electrical leakage protector can work well.
9.3 Adjustment Process
● Check if the switch of the line controller can work well.
● Check if the function keys of the line controller can work well.
● Check if the indicator light can work well.
● Check if the drainage system can work well.
● Check if the system can work well after starting up.
● Check if the water outlet temperature is acceptable.
● Check if there is vibration or abnormal sound when the system is functioning.
● Check if the wind, noise and condensate water produced by the system affect the
environment around.
● Check if there is refrigerant leakage.
● If any fault occurs, please check the instructions first, to analyze and remove the fault.
40
● The dirt retention on the surface of evaporator fin should be blowed by more than 0.6Mpa
compressor air, brushed by fine copper wire, or flushed by high pressurized water, usually
one time per month; if too much dirt, we can use paintbrush dipping gasoline to clean.
● After long downtime, if we restart the equipment, we should make following preparations:
examine and clean the equipment carefully, clean the water pipeline system, examine the
water pump, and fasten all the wire connections.
● Replacement parts must use our company original accessories, can not be replaced by
other similar accessories.
41
buy controlling switch, please turn off the general power switch.
● Never short connect the wire for protection required device, or else, in case unit
malfunction, it can not be protected normally and will damage the unit.
42
12. Technical parameter
12.1 Parameter
Model No. YC-050TA1 YC-075TA1 YC-155TA1
Power Supply 380V/3/50Hz 380V/3/50Hz 380V/3/50Hz
Heating Capacity(kW) ¹ 50 75 155
Power Input(kW) ¹ 8.7 13.5 27.8
COP ¹ 5.75 5.56 5.58
Heating Capacity(kW) ² 42 65 126
Power Input(kW) ² 8.6 13.5 27.0
COP ² 4.88 4.81 4.67
Heating Capacity(kW) ³ 32 48.8 100
Power Input(kW) ³ 7.8 12.2 24.0
COP ³ 4.09 4.01 4.17
Max Power Input(kW) 13.2 20.1 48.5
Max Current(A) 23.5 35.9 87.0
Refrigerant Type R410A R410A R410A
Compressor Type Scroll Scroll Scroll
Heat Exchanger Titanium alloy heat ex-changer Titanium alloy heat ex-changer Titanium alloy heat ex-changer
Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Air Flow Direction Vertical Type Vertical Type Vertical Type
Water Flow Volume(m3/h) 20,000 30,000 65,000
Net Dimensions(L*W*H)(mm) 1410×748×1050 1590×850×1500 2150×1078×2258
Working temperature range(°C) -7~43 -7~43 -7~43
Noise(dB) ≤65 ≤68 ≤72
Net Weight(kg) 250 550 900
Water connection(mm) 65 65 100
NOTE
43
² Heating Capacity at Air 15°C/12°C, Water 26°C
³ Heating Capacity at Air 7°C/6°C, Water 26°C
2).The specifications, technical parameter please refer to the product nameplate, if by the technological
upgrading, and the above parameters to change without prior notice to product nameplate shall prevail.
After-sale service
If your hot water heater can not operate normally, please turn off the unit and cut off
the power supply at once, then contact with our service center or technical
department.
44
45