1 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
This document is issued in Pulse.
Table of Contents
TABLE OF CONTENTS 1
MAIN COMPONENTS 3
FUNCTION 12
Start up 12
Continuous operation 12
© Siemens Industrial Turbomachinery AB
Turbine stop 12
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third
Cooling down 12
Parties without express authority is strictly forbidden.
Stand still 12
DISTURBANCES 12
Gas turbine trip 12
Generator breaker trip 12
Loss of power supply 13
System faults 13
Other faults 13
TECHNICAL SPECIFICATION 14
Design criteria and standards 14
Dimensioning data 14
Emergency power supply 14
Installation 14
INDEX OF COMPONENTS 16
A 087 0474-B 00-03 MS Word 97
2 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
This document is issued in Pulse.
The ABB AC generator is a 4-pole synchronous AC generator of salient pole type manufactured by
ABB in Sweden.
© Siemens Industrial Turbomachinery AB
We reserve all rights in this document and in the information
The generator is of a compact welded steel design. The design concept makes very efficient use of
contained therein. Reproduction, use or disclosure to third
active material employed, resulting in optimal performance with good economy and an
Parties without express authority is strictly forbidden.
Special emphasis has been placed on designing an electrical machine with good mechanical
stability. The box shaped machine base design allows the stator core with windings to rest directly
on the foundations, thus ensuring that all static and dynamic forces are transmitted directly into the
foundation.
A combination of short distance between the bearing centres and rigid bearing supports placed
under the centre of each bearing, minimises the level of vibration. Traditional sleeve bearings of
split type design are employed. The bearing liners are easily replaceable.
The rotor is of salient pole design running below the first lateral critical speed with a safe margin. A
very high thermal capacity is characteristic for this rotor design.
The shaft can be designed for double end drive, an often cost effective solution in combined cycles
where the gas turbine can drive the generator from one end and the steam turbine from the other.
Brushless excitation is achieved by a rotating exciter mounted on the main shaft outside the bearing
at the non driven end. The excitation power is taken from a permanent magnet generator driven by
the main generator shaft. The equipment is easy accessible for inspection.
The AC generator is tested according to a standard inspection plan issued by ABB.
A 087 0474-B 00-03 MS Word 97
3 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
This document is issued in Pulse.
Main components
• Generator
MKA10
The generator comprise following main components:
- Stator
- Rotor
- Stand still heater elements
• Exciter
MKC10
The exciter comprise following main components:
- Exciter with rotating diodes
- Pilot exciter
© Siemens Industrial Turbomachinery AB
MKY10
- AVR modules in dual channel arrangement. A heat sink module with molded components,
rectifier, CPU with regulating software, IGBT chopper and a set of interface terminals. The unit is
designed for either AC or DC supply as per technical data.
- Field circuit breakers.
-External diode bridges/rectifiers and smoothing capacitors for feeding the AVR module.
A 087 0474-B 00-03 MS Word 97
4 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
+BAC10
The HIGS cubicle is an integral part of the generator. HIGS cubicle is directly attached to the generator and
is divided into three compartments and control cubicle. Generator compartment, main transformer- and
auxiliary transformer compartment. The control cubicle contains all secondary circuits and AVR etc.
The following equipment is installed in HIGS:
- Generator circuit breaker, see below.
- Disconnector on line side, see below.
- Voltage transformers on both sides of the generator circuit breaker, see below.
- Current transformers on line- respective neutral side, see below.
- Surge capacitor (suppressor) on line side, see below
- Surge arrester on line side, see below.
- Anti condensation heater element, see below.
- Grounding resistor, see below.
- Earthing switches, see below.
© Siemens Industrial Turbomachinery AB
5 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
+BAC11CE001.T4.L1
+BAC11CE001.T4.L2
+BAC11CE001.T4.L3
The transformer measures current on the generator neutral side. Each transformer measures in one
phase and has three cores; one core is used for the AVR, two for protection.
• Surge capacitor
+BAC10GV002.C01.L1
+BAC10GV002.C01.L2
+BAC10GV002.C01.L3
• Surge arrester
+BAC10GV003.F01.L1
+BAC10GV003.F01.L2
© Siemens Industrial Turbomachinery AB
+BAC10GV003.F01.L3
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third
Parties without express authority is strictly forbidden.
• Heater element
+BAC10.E200
+BAC10.E201
+BAC10.E202
+BAC10.E203
• Grounding resistor
+BAC11GV001.R01
6 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
+BAC12GS003.Q17.L1
+BAC12GS003.Q17.L2
+BAC12GS003.Q17.L3
• Control cubicle
+BAC10GH100
The control cubicle is attached against the HIGS. It contains all the secondary circuits and
apparatus. The following equipment is installed in the terminal box:
© Siemens Industrial Turbomachinery AB
7 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
• MCB’s, protection/measuring
This document is issued in Pulse.
+BAC10GH100.F5.1, MCB
Generator protection sub.1
+BAC10GH100.F5.2, MCB
Generator protection sub.2
+BAC10GH100.F5.3, MCB
Measurement for synchronising
+BAC10GH100.F5.4, MCB
Active Power transducer
+BAC10GH100.F5.5, MCB
Open delta/earth fault-sub1
+BAC10GH100.F5.6, MCB
Open delta/earth fault-sub2
© Siemens Industrial Turbomachinery AB
The Miniature Circuit Breakers protects the generator protection respective measuring circuits from
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third
overload/overcurrent. An alarm is given if any of the MCB’s is tripped (excluding spare MCB).
Parties without express authority is strictly forbidden.
• MCB, PMG
+MKA10GA007.F01
+MKA10GA007.F02
The Miniature Circuit Breaker protects the PMG circuit from overload/overcurrent.
A 087 0474-B 00-03 MS Word 97
8 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
• Generator heater
This document is issued in Pulse.
MKA10AH005
The generator is equipped with following anti-condensation stand still heater elements:
MKA10AH005.R01
Heater element, generator hausing
MKA10AH005.R02
Heater element, generator hausing
MKA10AH005.R03
Heater element, generator hausing
MKA10AH005.R04
Heater element, generator hausing
MKA10AH005.R05
Heater element, generator hausing
MKA10AH005.R06
© Siemens Industrial Turbomachinery AB
The heater elements are connected so that they form one 3-phase power consumer.
Parties without express authority is strictly forbidden.
MKA10AH015.R01
Heater element in hood
MKC10AH005.R01
Heater element, exciter
The Pt100 sensor measures temperature of the cooling air leaving the generator.
High outgoing cooling air temperature (H1) gives an alarm.
9 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
MKA10CT025
The Pt100 sensor measures temperature of the cooling air coming to the generator in the non driven
end.
Cooling air temperature above (H1) gives an alarm.
The signal is used for indication and also in the AVR for biasing of the Field current limiter.
MKA10CT032
The Pt100 sensor measures the temperature at the phase L1 stator winding.
Winding temperature above (H1) gives event, high winding temperature (H2) gives an alarm and
high temperature (H3) initiates alarm and after 5 min. unloads the turbine.
10 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
MKA10CT038
The Pt100 sensor measures the temperature at the phase L2 stator winding.
Winding temperature above (H1) gives event, high winding temperature (H2) gives an alarm and
high temperature (H3) initiates alarm and after 5 min. also unloads the turbine.
MKA10CT042
Parties without express authority is strictly forbidden.
The Pt100 sensor measures the temperature at the phase L3 stator winding.
Winding temperature above (H1) gives event, high winding temperature (H2) gives an alarm and
high temperature (H3) initiates alarm and after 5 min. also unloads the turbine.
• Vibration transducer, DE
MKA10CY005
The accelerometer sensor measures vibration on the generator drive end bearing casing.
High vibration (H1) gives an alarm, high vibration (H2) gives an unloading shutdown and high
vibration (H3) gives turbine trip.
• Vibration transducer, DE
MKA10CY035
The accelerometer sensor measures vibration on the generator non drive end bearing casing.
High vibration (H1) gives an alarm, high vibration (H2) gives an unloading shutdown and high
A 087 0474-B 00-03 MS Word 97
11 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
• Vibration transducer, DE
This document is issued in Pulse.
MKA10CY040
The accelerometer sensor measures vibration on the generator non drive end bearing casing.
High vibration (H1) gives an alarm, high vibration (H2) gives an unloading shutdown and high
vibration (H3) gives turbine trip.
High vibration (H1) gives an alarm, high vibration (H2) gives an unloading shutdown and high
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third
12 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
This document is issued in Pulse.
Function
Start up
The generator voltage is controlled by the voltage regulator and the generator speed is determined
by the turbine during start up.
Continuous operation
The reactive power produced by the generator is determined by the voltage regulator and the active
power is determined by the turbine.
During continuous turbine operation the anti-condensation heaters in the stator, exciter and the
HIGS is switched off.
© Siemens Industrial Turbomachinery AB
We reserve all rights in this document and in the information
Turbine stop
contained therein. Reproduction, use or disclosure to third
Parties without express authority is strictly forbidden.
Cooling down
The gear, gas turbine and generator are rotating at barring speed during the gas turbine cooling
down period.
Stand still
During standstill the anti-condensation heaters shall be switched on.
Disturbances
Decision has then to be taken whether the unit should be shut down or synchronised and loaded
again.
13 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
This document is issued in Pulse.
System faults
If there are any damages on the generator the gas turbine unit may not be started or has to be shut
down.
- Electrical faults
The generator protection system protects the generator at internal electrical faults by tripping the
generator circuit breaker and if necessary also the turbine and the excitation circuit breaker.
The measuring/protection circuits are protected by an MCB on respective circuit, which will trip on
© Siemens Industrial Turbomachinery AB
overcurrent/overloading.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third
Parties without express authority is strictly forbidden.
The stator winding temperature in each phase is monitored and alarm is given if any of them goes
high. Should the temperature continue to increase then an unloading turbine trip is initiated.
- Bearings
Wear or damage to the bearings gives high vibration or/and high bearing metal temperature.
Generator vibration respective bearing metal temperature is monitored and alarm is given if any of
them goes high.
Other faults
Fault in connecting systems:
- Electrical faults
The relay protection system protects the generator at external electrical faults by tripping the
generator circuit breaker and if necessary also the turbine and excitation circuit breaker.
14 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
This document is issued in Pulse.
Technical specification
Dimensioning data
The generator is designed to match the turbine output curve. The turbine output at base load
operation (TBO 40000h) shall be generated with a PF of 0.8 with temperature rise as per class B at
nominal voltage and frequency.
The generator shaft/flange is designed for 5 x nominal torque in order to withstand a 2 phase short
© Siemens Industrial Turbomachinery AB
circuit.
We reserve all rights in this document and in the information
contained therein. Reproduction, use or disclosure to third
Parties without express authority is strictly forbidden.
Installation
A protective cover for the shaft/coupling shall be installed.
A 087 0474-B 00-03 MS Word 97
15 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
This document is issued in Pulse.
16 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
This document is issued in Pulse.
Index of Components
+BAC11CE003.T5
Voltage transformer, phase L1 4
+ Voltage transformer, phase L2 4
Voltage transformer, phase L3 4
+BAC10 +BAC11GS001.Q01
HIGS 4 Generator circuit breaker 6
+BAC10.E200 +BAC11GS002.Q1
Heater element 5 Disconnector 6
+BAC10.E201 +BAC11GS003.Q15
Heater element 5 Earthing switch, phase L1 5
+BAC10.E202 Earthing switch, phase L2 5
Heater element 5 Earthing switch, phase L3 5
+BAC10.E203 +BAC11GV001.R01
Heater element 5 Grounding resistor 5
+BAC10CE001.T6 +BAC12GS003.Q17
Voltage transformer, phase L1 4 Earthing switch, phase L1 6
© Siemens Industrial Turbomachinery AB
+BAC10GH100 +MKA10GA002.F5
Control cubicle 6 MCB, Active Power transducer 7
Parties without express authority is strictly forbidden.
+BAC10GH100.F5 +MKA10GA004
MCB, AVR 6 Field instruments terminal box 7
+BAC10GH100.F5.1 +MKA10GA006
MCB, Generator protection sub.1 7 Heater elements terminal box 7
+BAC10GH100.F5.2 +MKA10GA007
MCB, Generator protection sub.2 7 PMG terminal box 7
+BAC10GH100.F5.3 +MKA10GA007.F01
MCB, Measurement for synchronising 7 MCB, AVR 7
+BAC10GH100.F5.5 +MKA10GA007.F02
MCB, Generator protection sub.1 7 MCB, AVR 7
+BAC10GH100.F5.6
MCB, Generator protection sub.2 7
+BAC10GH100.F6.2 M
MCB, AVR 6
+BAC10GS003.Q16 MKA10
Earthing switch, phase L1 5 Generator 3
Earthing switch, phase L2 5 MKA10AH005
Earthing switch, phase L3 5 Generator heater 8
+BAC10GV002.C01 MKA10AH005.R01
Surge capacitor, phase L1 5 Heater element, hausing 8
+BAC10GV002.C02 MKA10AH005.R02
Surge capacitor, phase L2 5 Heater element, hausing 8
+BAC10GV002.C03 MKA10AH005.R03
Surge capacitor, phase L3 5 Heater element, hausing 8
+BAC10GV003.F01 MKA10AH005.R04
Surge arrester, phase L1 5 Heater element, hausing 8
+BAC10GV003.F02 MKA10AH005.R05
Surge arrester, phase L2 5 Heater element, hausing 8
+BAC10GV003.F03 MKA10AH005.R06
Surge arrester, phase L3 5 Heater element, hausing 8
+BAC11CE001.T4 MKA10AH015.R01
Current transformer, neutral side, phase L1 5 Heater element in Cubicle 8
Current transformer, neutral side, phase L2 5 MKA10CT005
Current transformer, neutral side, phase L3 5 Temperature Transmitter 8
A 087 0474-B 00-03 MS Word 97
+BAC11CE002.T2 MKA10CT010
Current transformer, line side, phase L1 4 Temperature Transmitter 8
Current transformer, line side, phase L2 4 MKA10CT015
Current transformer, line side, phase L3 4 Temperature Transmitter 8
17 (17)
Respons. dept Date Reg. )
SYSTEM DESCRIPTION OEEE1 2013-07-01
MKA Prepared
Missan Oil
GENERATOR SYSTEM P.Stenholt BD000130-U01-U02
This document is issued in Pulse.
MKA10CT041 AVR 3
Parties without express authority is strictly forbidden.
A 087 0474-B 00-03 MS Word 97