Motor Start-Solo Run Procedure
Motor Start-Solo Run Procedure
Motor Start-Solo Run Procedure
Pre-start actions;
Every work platforms/tarpaulin that will obscure proper motor ventilation to be dismantled temporarily
At DE side, push shaft towards stator and mark.
Also push shaft towards coupling and mark; in order to ascertain clearance area for vibration probe installation
De-isolation of Main HV supply cell, LV pre-charge incomer and other auxiliary & control
Note: VSD cooling unit go on fault, after more than 3days of stoppage (because water conductance reaches alarm and
trip set points (1.5 and 1.9 micro-Siemens respectively). Normal value should be 0.6 micro-Siemens.
In this condition VSD cooling motor must be started manually using P80i software
VSD Cooling motor manual startup procedure
1. Push the emergency button of VSD you want to start cooling motor
2. Connect Ethernet cable to Laptop
a. VSD A & B has similar Controller IP is same (10.19.62.250)
4. Open P80i
8. Go to Online
9. Left Click on variable O00101 – Select Override see the below picture
10. Double click on variable O00101(Make High) to Start cooling motor
11. Cooling Pump motor will run – Continue to run Up to 15 Minutes – check conductance go down below 1.0 micro
Siemens in the cooling unit
12. Double click on variable O00101 (Make Low) to stop cooling motor
13. Remove override