Title Replacement of the resin cartridge + pressure switch on the de-ionized cooling water
Trade MECHANICAL
P1 P2
2. Use the pressure /Air release valve to reduce the pressure inside the cartridge. Open the valve slowly
for smooth pressure release and do not open fully, (using rag sponge the water released)
Note: If the valve opened fully under pressure the resin will spill out.
3. After the pressure release disconnect the flexible hose at the points P1 & P2 mark the both flexible
according resin cartridge inlet and outlet inlet and outlet to avoid mistake during reconnection.
5. Test the solenoid to be sure the valve is open when the led is green
6. Disconnect the flexible metal hose from the old cartridge mark the both flexible according resin
cartridge inlet and outlet inlet and outlet
Note: The water flow must be from IN – OUT all the times.