Professional Documents
Culture Documents
F05ADDSI
F05ADDSI
p. 36.9, 1st column, 3rd line. The subscript for PWF should be “ser.”
p. 36.13, References. Add the following source after Lovvorn and
Hiller (1985):
Lovvorn, N.C. and C.C. Hiller. 2002. Heat pump life revisited. ASHRAE
Transactions 108(2):107-112.
p. 41.28, Case Study, 2nd paragraph. Change “3200 KW” to
“3200 kW.”
p. 45.6, 2nd col., end of 1st paragraph. The correct Research
Fig. 8 Grain Recirculators Convert Bin Dryer to Project is RP-1134 (Tompkins 2002).
High-Speed Continuous-Flow Dryer p. 45.13, References. Delete Idem 2002 and insert the following
(2003 HVAC Applications, Chapter 23, p. 7) source after Sterling and Kabayashi 1981:
Tompkins, D. 2002. Evaluation of photocatalytic air cleaning capability.
p. 23.7, Fig. 8. The bottom part of the figure was cut off; refer to the ASHRAE Research Project RP-1134.
full version here. p. 47.15, Tables 8 and 9. The titles for Tables 8 and 9 should read
p. 26.7, 2nd line from bottom. Change “only a very few grains of “with 25 mm Fiberglass Lining” and “with 50 mm Fiberglass Lin-
moisture” to “very little moisture.” ing,” respectively.
p. 47.22, Table 22. In the footnote, change “1.5 pcf” to “24 kg/m3.”
p. 27.2, Adiabatic Compression. In the second paragraph, change
“1.84W” to “1.884W.” In the definitions for Equation (1), units for p. 47.23, Ex. 3. Change “5 ft” to “1.52 m.”
E should be 1 kJ/(102 m·kg). In Example 1, units for the solution
should be kW. p. 47.41, 1st col., 3rd paragraph. Change “12 m/s” to “1.2 m/s.”
p. 27.6. Step 6 should read, “The enthalpy of air hai at 28°C satu- p. 49.6, Fig. 7. The arrow for “Union (typical)” should point to the
rated and 104.983 kPa is 109 kJ/kg. Σai = 109 – (4.1868)(0.037) union symbol, not the gate valve symbol. The correct figure is pre-
(28) = 104.66 kJ/kg.” sented here.
p. 27.10, 2nd col., 5th full paragraph. Change “calorific” to p. 50.1, Snow-Melting Heat Flux Requirement. The fourth list
“heat.” In Equation (18), change “Btu/h” to “kW.” item should be “wind speed near the heated surface.”
p. 51.7, Cooling Large Motors, 3rd paragraph. Delete “hour”
p. 27.11, Eq. (19). Rt should be turbulent resistance.
after “kilowatt.”
p. 31.5, Type II Hoods, Condensate hood. The second and third sen-
p. 53.3, Fig. 3. Delete the entire note below the figure.
tences for this item should read, “The hood is designed to direct the
condensate toward a perimeter gutter for collection and drainage, p. 53.9, Symbols. Delete the entries for “clo” and “met.”
allowing none to drip onto the appliance below. Flow rates are typi-
cally based on 255 to 380 L/s per square metre of hood opening.” p. 54.4, Eqs. (7) and (8). In the definitions for Wp, delete “in new-
tons = mass.”
p. 31.11, Traditional Registers. Terminal velocities should be
≤0.25 m/s. p. 54.12, 1st col., 4th line from bottom. Change “??°C” to
“590°C.”
p. 32.4, 2nd col., last paragraph. In the second sentence, velocity
should be limited to a maximum of 0.03 m/s. p. I.4, Index. Add “F15.12” to the entries for BAS and Building
automation system.
p. 32.6, 2nd col., 4th paragraph. Change “flashing” to “flushing.”
The units for free residual chlorine content should be mg/kg.
2004 HVAC Systems and Equipment
p. 33.22, 1st col. In the third line under Equation (38), change “KJ”
to “kJ.” p. 2.5, Fig. 8. The caption for Figure 9 should read “Chemical
Dehumidification.”
p. 34.2, Lower Initial Cost, 3rd paragraph. Change “660 W” to
“660 kW.” p. 6.7, Table 1. The complete table is supplied here.
Additions and Corrections A.3
xp
----- 0.32
kp
xp
----- 0.38
kp
x p – Do / 2 p. 24.2, 1st two lines. Change “15 to 35 cfm” to “7 to 16.5 L/s,” and
----------------------- ≈0 “15 cfm” to “7 L/s.”
kp
p. 25.4, Eq. (5). There should be an equals symbol after Dpc.
x p – Do / 2 p. 25.21, Tables 8 and 9. Delete “g·” from the units for KGa.
----------------------- ≤ 0.12
kp p. 31.3, 2nd equation. The unit for qc should be W.
p. 34.31, Symbols. Delete the definition for gc.
p. 35.19, Purging, 2nd paragraph. Change “Chapters 35 and 38 of
p. 7.22, 1st col., 13th line from bottom. Change “horsepower” to this volume” to “Chapter 38 of this volume.”
“power.”
p. 36.4, Fig. 9. Change “350 to 500 ft” to “100 to 150 m.”
p. 7.23, Turbocharger Heat Recovery. Delete “(280 kJ/kWh).”
p. 36.14, Fig. 25. The corrected figure is supplied on p. A.4.
p. 8.5, Fig. 5. The top two figures, for air/air and water/air refriger-
ant changeover, were cut off. The two figures are provided here. p. 44.10, Fig. 5. Replace with the corrected figure, supplied on p. A.4.
A.4 2005 ASHRAE Handbook—Fundamentals (SI)