System No.

WW-D-0096
November 18, 2010

Construction Joints
Assembly Ratings – 2, 3 and 4 Hr (See Item 1)
Nominal Joint Width – 1 In.
Class II Movement Capabilities – 12.5% Compression Or Extension

Wall to Wall
1. Wall Assembly – Min 7-1/2 in. (191 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structural
concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
The assembly rating is equal to the hourly rating of the wall assembly.
2. Joint System – Max width of joint (at time of installation of joint system) is 1 in. (25 mm). The joint system is designed to
accommodate a max 12.5 percent compression or extension from its installed width. The joint system shall consist of the following:
A. Packing Material – Nom 1-1/4 in. (32 mm) diameter polyethylene backer rod compressed and installed into joint. Packing material to
be recessed from each surface of wall to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* – Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with both surfaces of wall.
3M COMPANY
3M FIRE PROTECTION PRODUCTS – FD 150+
*Bearing the UL Classification Mark
Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc.
Copyright © 2010 Underwriters Laboratories Inc.®

WWD

3Fire Protection Products Product Support Line


www.3m.com/firestop W W-D-0096 • 1 of 1 1-800-328-1687