INSPECTION FORM
VARIABLE FREQUENCY DRIVE, 600V, <37 kW ID:
10 Manufacturer:
Bypass Thermal
20 Setting /
Overload Electronic Class: A
30 Rating:
Protection: Not Applicable Model:
Unknown
Control Power
Size: VA Sec. Voltage: V Primary Fuse: A Secondary Fuse: A
Transformer:
1.00 Yes
Full Load Amps: A Service Factor: Inverter Duty Other:
1.15 No
Cleanliness (As Found): Good Acceptable Poor Support Insulators: Good Acceptable Poor
Visual Inspection / Cleaning
Electro/Mechanical
Connections Good Acceptable Poor Good Acceptable Poor
Interlock:
Ground Connection Good Acceptable Poor Contactor Condition: Good Acceptable Poor
Door Mechanical Good Acceptable Poor Contact Alignment: Good Acceptable Poor
Cables Supported Appropriately: Yes No Unit Cleaned: Yes Photograph Taken: Yes
Comments:
Comments:
WARNING: DISCONNECT ALL POWER CABLES FROM VFD MODULE AND ALL CONTROL POWER FUSES PRIOR TO TEST.
Insulation Resistance (M )
Ground all phases not
Insulation Resistance Test
Test Voltage
under test!
A B C
Disconnect
1000 VDC
Line to GND
Disconnect
1000 VDC
Load to GND
Disconnect
1000 VDC
Line to Load
Test Summary
Bypass Contactor Test Passed
1000 VDC
Line To GND
Test Inconclusive
Bypass Contactor Further Investigation
1000 VDC Required.
Load To GND
Test Failed
Bypass Contactor
1000 VDC
Line to Load
Comments:
Remote (RTU/PLC/DCS)
A
Displayed Motor Current:
Completed: Yes No
Performed By
Checked By
Note: The person performing the check is responsible for ensuring that the data is transcribed from the handwritten form correctly, and that
the analysis results are correct.
Fuse Mfg.
Fused Disc. Rating: A Fuse Size: A
Circuit Model:
Starter Data
Protection: Manufacturer:
Breaker Inst.
Rating: A A
MCP Setting: Model:
10 Manufacturer:
Thermal
Overload 20 Setting /
Electronic Class: A
Protection: 30 Rating:
Intelligent Model:
Unknown
Control Power
Size: VA Sec. Voltage: V Primary Fuse: A Secondary Fuse: A
Transformer:
A
Current Ground Present
Phases: B None Ratio: Ratio:
Transformers: Fault CT: Not Present
C
Cleanliness (As Found): Good Acceptable Poor Support Insulators: Good Acceptable Poor
Visual Inspection / Cleaning
Electro/Mechanical
Connections Good Acceptable Poor N/A Good Acceptable Poor
Interlock:
Ground Connection: Good Acceptable Poor Contactor Condition: Good Acceptable Poor
Door Mechanical Good Acceptable Poor Contact Alignment: Good Acceptable Poor
Cables Supported Appropriately: Yes No Unit Cleaned: Yes Photograph Taken: Yes
Comments:
Fuse Resistance (µ )
Comments:
Insulation Resistance (M )
Ground all phases not
Test Voltage
under test!
A B C
Comments:
Performed By
Checked By
Note: The person performing the check is responsible for ensuring that the data is transcribed from the handwritten form correctly, and that
the analysis results are correct.
Air Winding
Cooling: # Cooling Fans:
Fan Material:
Paint: Good Acceptable Poor Filter Media: N/A Good Acceptable Poor
Cooling Fans: N/A Good Acceptable Poor Fan Controls: N/A Good Acceptable Poor
Cleanliness (As Found): Good Acceptable Poor Unit Cleaned: Yes Photograph Taken: Yes
- -
500
40
- -
500
40
- -
500
40
Notes:
(a) Testing to 10 minutes and calculation of Polarization Index is only required for motors > 150 kW (200 HP)
Test Summary Test Passed Test Inconclusive. Further Investigation Required. Test Failed
Test Inconclusive
Further Investigation Required.
Test Failed
Comments:
Not Applicable
Bearing Insulation
500
500
Test Summary Test Passed Test Inconclusive. Further Investigation Required. Test Failed
Not Applicable
Actual Winding Temperature: °C Actual Bearing Temperature °C
Calculated Calculated
Resistance Resistance
RTD Temperature RTD Temperature
( ) ( )
(°C) (°C)
RTD Resistance
Test Summary Test Passed Test Inconclusive. Further Investigation Required. Test Failed
Note: Test connection resistance of bolted connections. Report on cable inspection sheet.
Performed By
Checked By
Note: The person(s) performing the check is responsible for ensuring that the data is transcribed from the handwritten form correctly, and
that the analysis results are correct.
Physical Damage on Exposed Ends: Yes No Cable Identification Tag Installed: Yes No
Inspection
Visual
Insulation Resistance (M )
Test Test Summary
Voltage
A-GND B-GND C-GND N-GND
Test Passed
Test Inconclusive
Reading
Further Investigation Required.
V Test Failed
Corrected to 20oC
Utilize 1000VDC Test Voltage for 600V rated cables, 500VDC for cables rated <= 300V.
Comments:
Note: Torque check required for all cables. Connection Resistance Test required for cables 4/0 AWG or larger.
Connection Resistance
Source OK
Dest. / Load OK
Comments:
Performed By
Checked By