Professional Documents
Culture Documents
Electrical Design For High Rise Building-Engr Orville Singson
Electrical Design For High Rise Building-Engr Orville Singson
Singson, PEE
via Webinar Conference
July 04, 2020
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 1 of 122
Facilitator’s Profile
Managing Director
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 2 of 122
OUTLINE
Introduction
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 3 of 122
OUTLINE
Electrical Design of a Multi-Family Dwelling Units in High-Rise
Building
Electrical Design for Commercial.
Electrical Design Analysis and Calculations
Feeder Size Determination
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 4 of 122
I. Introduction
Purpose
This presentation is intended for the licensed
electrical practitioner such (PEE, REE, and RME) starting
to prepare the electrical design plans. The discussion
contains the basic knowledge and requirements in the
electrical design of a single storey to multi-family
dwellings of the high-rise building.
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 5 of 122
2.1.2 Classification of a Building
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 6 of 122
Commercial: A building which consist of one or more
commercial units for the use of owners or for the
others. A commercial unit composed of one or more
rooms for the use one or more persons which usually
for profit/business making enterprise.
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 7 of 122
Mixed-Use: combination of residentials, offices,
hotels, and retails development.
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 8 of 122
Electrical Design Analysis
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 9 of 122
Design Analysis
1. General Lighting Loads 110 m² x 24VA/m² = 2640VA
Where:
110m² is the floor area as shown in the architectural layout
and the 24 volt-ampere is the unit load for dwelling units as per
Table 2.20.2.3
Provide one (1) 20A branch circuit. Although a 15AT circuit breaker
is adequate for the computed load, a 20AT circuit breaker is used
to take care of the expected possible additional loads. Refer to
section 2.40.1.6 for Standard Ampere Ratings for circuit breakers.
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 10 of 122
Design Analysis cont..:
2. Small Appliance Load = 1500VA
Load = (1) 20A @ 1,500 volt-amperes = 1,500VA
Where 1,500 volt-amperes is as per Section 2.20.3.13(a
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 11 of 122
Standard Ampere Ratings
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 12 of 122
Table of Cable Ampacities
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 13 of 122
Table of Conduit Fill
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 14 of 122
Design Analysis cont..:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 15 of 122
Design Analysis cont..:
Use: 2# 3.5mm², copper THWN, branch circuit
conductors. Refer to Table 3.10.1.16 for
ampacity.
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 16 of 122
Design Analysis cont..:
Other Loads:
8.0kW Electric Range @ 80% D.F = 6400VA
I (Load) = 6,400 VA / 230 V = 27.82 Amperes
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 17 of 122
Design Analysis cont..:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 18 of 122
Design Analysis cont..:
1.0HP Room ACU, 8A x 230V = 1,840VA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 19 of 122
Design Analysis cont..:
Use: 20mmØ Rigid PVC conduit. Refer to Table C10 for size
of conduit which can accommodate the 2#3.5mm² copper,
THWN.
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 20 of 122
Design Analysis cont..:
3.0HP Booster Pump, 17.0A x 230V = 3,910VA
Where 17.0A is as per Table 4.30.14.2
Rating of branch circuit protective device = 250% x 17.0A =
42.50A
Where 250% is the maximum inverse time rating of the
breaker as per Table 4.30.4.2, so provide 40A branch circuit
breaker for the Booster Pump.
Use: 2# 5.5mm², copper THWN, branch circuit conductors.
Refer to Table 3.10.1.16 for ampacity.
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 21 of 122
Design Analysis cont..:
Use: 20mmØ Rigid PVC conduit. Refer to Table C10 for size of
conduit which can accommodate the 2#5.5mm² copper,
THWN.
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 22 of 122
Design Analysis and Computations
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 23 of 122
Design Analysis and Computations
Studio Type Unit (S35)
1. General Lighting Loads 35 m² x 24VA/m² 840VA
2. Small Appliance Loads 1500VA
3. Laundry Circuit 1500VA
3840VA
Application of Demand Factor
First 3000VA @ 100% DF 3000VA
Remainder @ 35% DF 294VA
Total Net Computed Load 3294VA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 24 of 122
Design Analysis cont..:
Other Loads
4. Refrigerator 800VA
5. Aircon Load 5750VA
6. Water Heater 5500VA
7. Clothes Dryer 5000VA
8. Electric Range 8000VA x 0.80 6400VA
26744VA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 25 of 122
Service Conductor Ampacity
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 26 of 122
Design Analysis cont..:
One Bedroom Type Unit (1F66)
1. General Lighting Loads 66 m² x 24VA/m² 1584VA
2. Small Appliance Loads 1500VA
3. Laundry Circuit 1500VA
4584VA
Application of Demand Factor
First 3000VA @ 100% DF 3000VA
Remainder @ 35% DF 554VA
Total Net Computed Load 3554VA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 27 of 122
Design Analysis cont..:
Other Loads
4. Refrigerator 800VA
5. Aircon Load 5750VA
6. Water Heater 5500VA
7. Clothes Dryer 5000VA
8. Electric Range 8000VA x 0.80 6400VA
27004VA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 28 of 122
Service Conductor Ampacity
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 29 of 122
Design Analysis cont..:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 30 of 122
Design Analysis cont..:
Other Loads
4. Refrigerator 800VA
5. Aircon Load 5750VA
6. Water Heater 5500VA
7. Clothes Dryer 5000VA
8. Electric Range 8000VA x 0.80 6400VA
27340VA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 31 of 122
Design Analysis cont..:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 32 of 122
Penthouse Type Unit (P250)
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 33 of 122
Other Loads
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 34 of 122
Service Conductor Ampacity
Service Protection
[(38655VA-2076VA) + 250% (2076VA)] / 400V *1.732= 60.29A
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 35 of 122
Design Analysis cont..:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 36 of 122
Design Analysis cont..:
Calculations for Multi-Family Dwelling Units
Studio Type
1. General Lighting Loads = 840VA
2. Small Appliance Load = 1500VA
3. Laundry Circuit = 1500VA
4. Refrigerator = 800VA
5. Aircon Load = 5750VA
6. Water Heater = 5500VA
7. Clothes Dryer = 5000VA
8. Range = 8000VA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 37 of 122
Design Analysis cont..:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 38 of 122
Design Analysis cont..:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 39 of 122
Design Analysis cont..:
Penthouse Type
1. General Lighting Loads = 6000VA
2. Small Appliance Load = 1500VA
3. Laundry Circuit = 1500VA
4. Refrigerator = 800VA
5. Aircon Load = 17250VA
6. Water Heater = 5500VA
7. Clothes Dryer = 5000VA
8. Range = 8000VA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 40 of 122
Design Analysis cont..:
Calculations for Meter Center (MC-1) up to 39 floors
Total Connected Loads
1. Studio Type = 139,450VA
2. One Bedroom Type = 325,974VA
3. Two Bedroom Type = 122,376VA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 41 of 122
Design Analysis cont..:
Service Conductor Ampacity
Service Protection
[(223364VA-5750VA)+250% (5750VA)]/400V *1.732=334.85A
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 42 of 122
Design Analysis cont..:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 43 of 122
Design Analysis cont..:
Calculations for Meter Center (MC-2) 40 floor with Penthouse
Total Connected Loads
1. Studio Type = 139,450VA
2. One Bedroom Type = 325,974VA
3. Two Bedroom Type = 122,376VA
4. Penthouse = 45,550VA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 44 of 122
Design Analysis cont..:
Service Conductor Ampacity
Service Protection
[(234339VA-5750VA)+250% (5750VA)]/400V *1.732=350.69A
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 45 of 122
Design Analysis cont..:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 46 of 122
Commercial/Office Loads
= 35,000 VA x 10 units
= 350,000 VA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 47 of 122
Commercial/Office Loads
= 25,000 VA x 5 units
= 125,000 VA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 48 of 122
Commercial/Office Loads
Service Protection
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 49 of 122
Commercial/Office Loads
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 50 of 122
Other Loads cont..:
1. Elevators 20HP,400V,3Ø,60Hz,
Assumed 6 elevators
= 6 units x 35,625VA
= 213,750VA x 0.79 D.F. = 168,750VA (See Table 6.20.2.4)
Service Conductor Ampacity
[168750VA + 25%(35625VA)] / 400V*1.732 = 256.43A
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 51 of 122
Equation
M=
Where:
P – is rated passenger number in the car
75 – stands for 75kg/passenger
9.81 – is the acceleration due to gravity
s – is the rated speed
CF – is the counterweight factor (less than 1)
n – is the total efficiency of the installation (approx. 85%)
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 52 of 122
Other Loads cont..:
1. Transfer Pump 60HP,400V,3Ø,60Hz
Assumed 2 units Duty
= 2 units x 55,950VA
= 111,900VA
Service Conductor Ampacity
[111900VA + 25%(55950VA)] / 400V*1.732 = 181.70A
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 53 of 122
Other Loads cont..:
2. Booster Pump 10HP,400V,3Ø,60Hz
Assumed 1 unit Duty
= 1 unit x 9,325VA
= 9,325VA
Service Conductor Ampacity
[9325VA + 25%(9325VA)] / 400V*1.732 = 16.82A
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 54 of 122
Other Loads cont..:
3. Supply Fan 30HP,400V,3Ø,60Hz
Assumed 4 units
= 4 unit x 27,975VA
= 111,900VA
Service Conductor Ampacity
[111900VA + 25%(27975VA)] / 400V*1.732 = 171.61A
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 55 of 122
Other Loads cont..:
4. Exhaust Fan 50HP,400V,3Ø,60Hz
Assumed 4 units
= 4 unit x 46,625VA
= 186,500VA
Service Conductor Ampacity
[186500VA + 25%(46625VA)] / 400V*1.732 = 286.02A
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 56 of 122
Other Loads cont..:
5. Lift Pressurization Fan 20HP,400V,3Ø,60Hz
Assumed 4 units
= 2 unit x 23,312VA
= 46,624VA
Service Conductor Ampacity
[46624VA + 25%(23312VA)] / 400V*1.732 = 75.71A
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 57 of 122
Other Loads cont..:
6. Fire Stair Pressurization Fan 20HP,400V,3Ø,60Hz
Assumed 4 units
= 2 unit x 23,312VA
= 46,624VA
Service Conductor Ampacity
[46624VA + 25%(23312VA)] / 400V*1.732 = 75.71A
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 58 of 122
Other Loads cont..:
7. Fire Pump 100HP,400V,3Ø,60Hz
= 93,250VA
Service Conductor Ampacity
[93250VA + 25%(93250VA)] / 400V*1.732 = 168.25A
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 59 of 122
Other Loads cont..:
8. Jockey Pump 10HP,400V,3Ø,60Hz
= 9,325VA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 60 of 122
Compute for the Total Demand Loads
1. Residential loads = 587,800VA x 39 Floors
= 22924kVA + 633kVA
= 23557kVA x 23% D.F.
= 5418 kVA
1 unit of 1.5MVA,3Ø,34.5kV-400/230V,60Hz
Pad Mounted Transformer
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 61 of 122
Compute for the Total Demand Loads
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 62 of 122
Compute for the Total Demand Loads cont..:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 63 of 122
Compute for the Total Demand Loads cont..:
= 1.98MVA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 64 of 122
Compute for the Total Demand Loads cont..:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 65 of 122
Calculations for Feeder and Protection
For Transformer 1 (Residential)
= 2886.83A
Use: 3200A,Busduct,3W+N+G,600V,Cu
Use: 3200AT,3P,600V,65kAIC,ACB
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 66 of 122
Calculations for Feeder and Protection cont..:
For Transformer 2 (Residential)
= 2886.83A
Use: 3200A,Busduct,3W+N+G,600V,Cu
Use: 3200AT,3P,600V,65kAIC,ACB
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 67 of 122
Calculations for Feeder and Protection cont..:
For Transformer 3 (Residential)
= 2165.12A
Use: 2500A,Busduct,3W+N+G,600V,Cu
Use: 2500AT,3P,600V,65kAIC,ACB
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 68 of 122
Calculations for Feeder and Protection cont..:
For Transformer 4 (Common Loads)
= 2165.12A
Use: 2500A,Busduct,3W+N+G,600V,Cu
Use: 2500AT,3P,600V,65kAIC,ACB
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 69 of 122
Calculations for Generators cont..:
For Generators
Total Loads = 7.0MVA x .80 = 5600kW
Use: 3200A,Busduct,3W+N+G,600V,Cu
Use: 3200AT,3P,600V,65kAIC,ACB
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 70 of 122
Generators partial SLD cont..:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 71 of 122
VOLTAGE DROP CALCULATIONS
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 72 of 122
Voltage Drop
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 73 of 122
Voltage Drop
RACEWAY LENGTH OF
TYPE CABLE
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 74 of 122
Cable Impedances:
Shall be use to identify X and R parameters
a. PEC 2017 Table 10.1.1.9 p. 942
b. Catalogue
Length of wire:
Has an impact in determining total Impedance
of wire / cable
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 75 of 122
Cont…
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 76 of 122
Voltage Drop
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 77 of 122
ELECTRICAL CIRCUIT ARRANGEMENT SHOWING 5% VOLTAGE DROP
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 78 of 122
Source: IEEE Gray Book
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 79 of 122
Table 10.1.1.9 (Alternating-Current Resistance and Reactance for
600Volts Cables. PEC 2017
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 80 of 122
Basic Assumptions and the Limitations of the Table
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 81 of 122
VOLTAGE DROP CAL. : Output (Results)
* Efficiency of
the system.
VOLTAGE
DROP * Compliance
with code
CALCULATION requirement.
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 82 of 122
Voltage Drop Calculations
The effective length of the main feeder is approximately 15m long, from
Transformer to LVSG and the feeder circuit currents as calculated is 2500A .
The Busduct is 3000A and copper.
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 83 of 122
Cont….
Step # 1: Find the value of resistance and reactance.
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 84 of 122
Cont….
Step #2 : Find the approximate voltage drop.
2.15 x 10ˉ⁴ 1.20 x 10ˉ⁴ 1.732
= 1.066 V
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 85 of 122
Cont….
Step #4 : Find the voltage present at the load end of the circuit.
V = (Vs - Vc)
= 400V – 0.266V
= 399.73 V
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 86 of 122
Cont….
from LVSG to last floor of the building and the feeder circuit currents
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 87 of 122
Cont….
Step # 1: Find the value of resistance and reactance
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 88 of 122
Cont….
Step #2 : Find the approximate voltage drop.
1.73 x 10ˉ³) 9.61 x 10ˉ⁴) 1.732
= 8.57 V
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 89 of 122
Cont….
Step #4 : Find the voltage present at the load end of the circuit.
Vt = (Vs - Vc)
= 400V – (1.066V + 8.57V)
= 390.36 V
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 90 of 122
Cont….
For Transformer 3
Step # 1: Find the value of resistance and reactance.
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 91 of 122
Cont….
Step #2 : Find the approximate voltage drop.
4.32 x 10ˉ⁴ 2.33 x 10ˉ⁴ 1.732
= 1.36 V
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 92 of 122
Cont….
Vt = (Vs - Vc)
= 400V – 1.36V
= 398.64 V
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 93 of 122
Cont….
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 94 of 122
Cont….
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 95 of 122
Cont….
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 96 of 122
Cont….
Vt = (Vs - Vc)
= 400V – (1.36V + 10.86V)
= 387.78 V
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 97 of 122
Sample VD calculation for 3 phase load
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 98 of 122
Cont….
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 99 of 122
Cont….
Solution:
Zc = (R x cosθ) + (X x sinθ)
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 100 of 122
Cont….
Step #2 : Find the impedance (Z) corrected to 0.80 power factor
(Zc)
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 101 of 122
Cont….
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 102 of 122
Cont….
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 103 of 122
Cont….
Vt = (Vs - Vc)
= 400V – 5.30V
= 394.7 V
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 104 of 122
SHORT CIRCUIT CALCULATIONS
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 105 of 122
SINGLE LINE DIAGRAM
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 106 of 122
Assumed MVA base = 100MVA
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 107 of 122
X/R = 20; θ = tanˉ¹ (20) = 87.13⁰
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 108 of 122
2. Transformer: 2MVA %Z = 5.75 X/R = 8
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 109 of 122
3. Cable Busduct: Zc1 = 3200A; L = 15m
R = 1.439x10-5Ω/m x 15m = 0.000215Ω
X = 0.801x10-5Ω/m x 15m = 0.000120Ω
Convert Ω to p.u.
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 110 of 122
4. Lump Load 1; 200kVA,3Ø,400V X”d = 25% X/R = 10
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 111 of 122
Rpu = cos (84.28⁰) x 125 = 12.45 pu
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 112 of 122
5. Lump Load 2; 120kVA,3Ø,400V X”d = 25% X/R = 10
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 113 of 122
Rpu = cos (84.28⁰) x 208.33 = 20.76 pu
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 114 of 122
Impedance Diagram
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 115 of 122
Impedance Diagram cont..:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 116 of 122
SCC cont..:
Series Connections:
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 117 of 122
SCC cont..:
Parallel Connections:
R2(pu) = 5.66 pu
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 118 of 122
SCC cont..:
X2(pu) = 56.52 pu
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 119 of 122
SCC cont..:
Rth(pu) = 0.459 pu
( ) . .
Xth(pu) = 2.96 pu
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 120 of 122
SCC cont..:
Zth(pu) = 2.99 pu
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 121 of 122
Permission to share obtained from Engr. Orville Singson (THANK YOU) Page 122 of 122