Connecting different

safety outputs to
safety inputs of
SINAMICS V90
Siemens
SINAMICS V90 / Safety / STO Industry
Online
https://support.industry.siemens.com/cs/ww/en/view/109740693 Support
This entry is from the Siemens Industry Online Support. The general terms of use
(http://www.siemens.com/terms_of_use) apply.

Security Siemens provides products and solutions with industrial security functions that
information
support the secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber
threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial security concept. Siemens’ products and solutions
constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants,
systems, machines and networks. Such systems, machines and components
should only be connected to an enterprise network or the internet if and to the
extent such a connection is necessary and only when appropriate security
measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be
implemented, please visit https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them
more secure. Siemens strongly recommends that product updates are applied as
soon as they are available and that the latest product versions are used. Use of
product versions that are no longer supported, and failure to apply the latest
updates may increase customer’s exposure to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial
© Siemens AG 2023 All rights reserved

Security RSS Feed under https://www.siemens.com/cert.

Table of content
1 Introduction ........................................................................................................ 3
1.1 Preliminary remark ............................................................................... 3
1.2 Safety integrated function..................................................................... 3
2 SINAMICS V90 connected directly to S7-1200F F-DQ.................................... 5
3 SINAMICS V90 connected to ET 200S F-RO ................................................... 6
4 SINAMICS V90 connected to SIRIUS 3SK1 safety relays .............................. 8
5 SINAMICS V90 combined with an emergency button .................................... 9
6 Connecting multiple SINAMICS V90 drives to one emergency button ...... 10
7 Connecting multiple SINAMICS V90 drives to ET 200SP F-DQ................... 11
8 Appendix .......................................................................................................... 12
8.1 Contact ............................................................................................... 12
8.2 History ................................................................................................ 12

Connecting different safety outputs to safety inputs of SINAMICS V90


Entry-ID: 109740693, V 1.3.1, 01/2023 2
1 Introduction

1 Introduction
1.1 Preliminary remark
This frequently asked question (FAQ) describes the topic “The wiring for the V90
STO input”. The document explains how to connect different safety outputs from
different sources to the safety inputs of SINAMICS V90 PN/PTI.

1.2 Safety integrated function


The integrated safety function “Safe Torque Off” (STO) prevents the drive from
restarting unexpectedly.
The safety function “STO” will be controlled via terminals and the terminal is shown
in figure 1-1:

STO1

STO+
V90 Drive

STO2

+24V

M
© Siemens AG 2023 All rights reserved

Figure 1-1: Standard configuration for the STO function


In the figure 1-1 STO1 and STO2 are the safety input pins. In the standard
configuration both inputs are bridged with STO+ to deselect STO (STO is not
active). The standard configuration explains the type of the safety input: P/P
switched input.
The STO+ pin is supplied by the standard 24V supply from the drive itself. The
STO+ pin is used to supply external safety devices / components which are
redirected to the V90 STO1/2 inputs.
The common pin of the safety inputs is the M pin which is also the M pin for the
standard 24V power supply of the drive.

NOTE If the customer is using the STO function then the bridge between
STO1 --STO+ - STO2 has to be removed. The wiring to the external safety
outputs / devices has to be installed.

CAUTION Safety function STO will deactivate the drive sporadically caused by
different 24V level with a fault message F01611.
If the application contains 2 or more different 24V DC power supply for the drive
and the safety components / devices then the error F01611 can occur. The
sporadic error is a result of an open loop between the STOx 24V-pin and the
necessary M-pin which is connected from another 24V power supply of the drive.
The problem can be avoided by connecting the common terminal of both power
supplies together.

Connecting different safety outputs to safety inputs of SINAMICS V90


Entry-ID: 109740693, V 1.3.1, 01/2023 3
1 Introduction

The behavior of the SINAMICS V90 STO function is shown in table 1-1:

Table 1-1
Terminal State Action
STO1 STO2
HIGH HIGH STO not The servo motor will run when you power on
active the servo drive. STO is now deactivated.
There is no other error shown by the inverter.
LOW LOW STO active The servo motor will not run when you power
on the servo drive. The pulses from the
inverter are deactivated by selecting STO.
There is no error shown by the inverter.
HIGH LOW Error active/ Error F01611 occurs and the pulses from the
Internal STO drive have been deactivated with the error.
LOW HIGH Error active/ Error F01611 occurs and the pulses from the
Internal STO drive have been deactivated with the error.

The STO function integrated in SINAMICS V90 drive is a smart function. Customer
doesn’t need to set any parameters to activate or adjust this function.
© Siemens AG 2023 All rights reserved

Connecting different safety outputs to safety inputs of SINAMICS V90


Entry-ID: 109740693, V 1.3.1, 01/2023 4
2 SINAMICS V90 connected directly to S7-1200F F-DQ

2 SINAMICS V90 connected directly to


S7-1200F F-DQ
Figure 2-1
S7-1200F SM 1226
CPU F-DQ 2X RELAIS

L+ M L+ M 1L A 2L B

STO1

STO+

V90 Drive
STO2

DC24V +24V
DC Power
Supply DC0V
M
© Siemens AG 2023 All rights reserved

Figure 2-1 shows the case that only one DC 24V power supply used for the
SM1226 and for the V90 drive.
The S7-1200F CPU can be connected to the same or a different DC power supply.

Additional components:
• SM1226: 6ES7226-6RA32-0XB0

Connecting different safety outputs to safety inputs of SINAMICS V90


Entry-ID: 109740693, V 1.3.1, 01/2023 5
3 SINAMICS V90 connected to ET 200S F-RO

3 SINAMICS V90 connected to ET 200S F-RO


Figure 3-1
PM-E 4 F-DO (P/M 1 F-RO
24V DC Switching)
F-DO x
L+ M P M IN P IN M OUT1 OUT2

STO1

STO+

V90 Drive
STO2
© Siemens AG 2023 All rights reserved

DC24V +24V
DC Power
Supply DC0V
M

Figure 3-2
PM-E 4 F-DO (P/M 1 F-RO
24V DC Switching)
F-DO x
L+ M P M IN P IN M OUT1 OUT2

STO1

STO+
V90 Drive

STO2

DC24V +24V
DC Power
Supply DC0V
M

Connecting different safety outputs to safety inputs of SINAMICS V90


Entry-ID: 109740693, V 1.3.1, 01/2023 6
3 SINAMICS V90 connected to ET 200S F-RO

Figure 3-1 shows the direct supplied safety component / device from one DC24V
power supply. The STO+ pin is not used in this case.
Figure 3-2 shows the case that the DC power supply for the safety component /
device is supplied by the STO+ pin output of the V90.

Both solutions are equal because the main supply for the drive and the safety
component / device is the same.

Additional components:
• 4 F-DO: 6ES7138-4FB03-0AB0
• 1 F-RO: 6ES7138-4FR00-0AA0
© Siemens AG 2023 All rights reserved

Connecting different safety outputs to safety inputs of SINAMICS V90


Entry-ID: 109740693, V 1.3.1, 01/2023 7
4 SINAMICS V90 connected to SIRIUS 3SK1 safety relays

4 SINAMICS V90 connected to SIRIUS 3SK1


safety relays
Figure 4-1
3SK1122

A1 A2 Q2 Q1

STO1

STO+

V90 Drive
STO2

+24V
DC Power DC24V
Supply M
DC0V
© Siemens AG 2023 All rights reserved

Figure 4-1 shows the wiring example of the SIRIUS 3SK1 safety relay which is
connected to the V90 STO terminal.
Drive and relay are using the same DC 24V power supply.

Additional component:
• SIRIUS 3SK1 Advanced safety relay: 3SK1122-1CB41
NOTE You can download the application manual about SIRIUS safety integrated from
the following link:
https://support.industry.siemens.com/cs/ww/en/view/81366718

Connecting different safety outputs to safety inputs of SINAMICS V90


Entry-ID: 109740693, V 1.3.1, 01/2023 8
5 SINAMICS V90 combined with an emergency button

5 SINAMICS V90 combined with an


emergency button
Figure 5-1
Emergency
Stop Button

STO1

STO+

V90 Drive
STO2

+24V
DC Power DC24V
Supply M
DC0V

Figure 5-2
Emergency
Stop Button
© Siemens AG 2023 All rights reserved

STO1

STO+
V90 Drive

STO2

+24V
DC Power DC24V
Supply M
DC0V

Figure 5-1 shows the direct supplied emergency button from one DC24V power
supply. The STO+ pin is not used in this case.
Figure 5-2 shows the case that the DC power supply for the emergency button is
supplied by the STO+ pin output of the V90.

Both solutions are equal because the main supply for the drive and the safety
component / device is the same.

Connecting different safety outputs to safety inputs of SINAMICS V90


Entry-ID: 109740693, V 1.3.1, 01/2023 9
6 Connecting multiple SINAMICS V90 drives to one emergency button

6 Connecting multiple SINAMICS V90 drives


to one emergency button
Figure 6-1
Emergency
Stop Button

STO1

V90 Drive 1
STO+

STO2

+24V
DC Power DC24V
Supply M
DC0V

STO1

V90 Drive 2
STO+
© Siemens AG 2023 All rights reserved

STO2

+24V

Figure 6-1 shows the wiring example of the emergency button connected to two
V90 drives. The emergency button is supplied directly from one DC 24V power
supply.

Connecting different safety outputs to safety inputs of SINAMICS V90


Entry-ID: 109740693, V 1.3.1, 01/2023 10
7 Connecting multiple SINAMICS V90 drives to ET 200SP F-DQ

7 Connecting multiple SINAMICS V90 drives


to ET 200SP F-DQ
Figure 7-1
F-DQ 4xDC 24V/2A F-RQ 1x24VDC/24..230VAC/5A
PM Switching

P M IN P IN M OUT1 OUT2

STO1

STO+

V90 Drive
© Siemens AG 2023 All rights reserved

STO2

DC24V +24V
DC Power
Supply DC0V
M

STO1

STO+
V90 Drive

STO2

+24V

Figure 7-1 shows the case that the DC power supply for the safety component /
device is supplied from one DC24V power supply. The STO+ pin in the V90 drive
are not used in this case. The DC24V power supply to V90 drives also need to be
from the same DC24V power supply device.

Additional components:
• F-DQ 4xDC 24V/2A: 6ES7136-6DB00-0CA0
• BU15-P16+A0+2B: 6ES7193-6BP00-0BA0
• F-RQ 1x24VDC/24..230VAC/5A ST: 6ES7136-6RA00-0BF0
• BU20-P8+A4+0B: 6ES7193-6BP20-0BF0

Connecting different safety outputs to safety inputs of SINAMICS V90


Entry-ID: 109740693, V 1.3.1, 01/2023 11
8 Appendix

8 Appendix
8.1 Contact
Siemens Ltd., China
DF M3-BF GMC
No. 18 Siemens Road
Jiangning Development Zone
Nanjing, 211100
China
mailto: mc_gmc_mp_asia.cn@siemens.com

8.2 History
Table 8-1
Version Date Modifications
V1.0 09/2016 First version
V1.1 11/2016 Textual update
V1.2 06/2017 Connected with S7-1200F F-DQ update
© Siemens AG 2023 All rights reserved

V1.2.1 08/2017 Text corrections


V1.3 12/2022 Add chapter 7
V1.31 01/2023 Removed markings in wiring diagrams

Connecting different safety outputs to safety inputs of SINAMICS V90