GENERAL NOTES ORA WING INDEX


GENERAL SITE & SLAB PREPARATION (continued) CONCRETE !continued) STRUCTURAL STEEL PURLINS AND GIRTS EXPANSION AND CHEMICAL ANCHORS S01 STANDARD NOTES AND DRAWING INDEX
Gl These drawings shall be read in conjunction with all architectural
and other Consultants' drawings and with such other written
SP7. Comply with Australian standard methods for compaction testing
as in the current version of AS 1726 - Geotechnical Site
C14. Reinforcement notations:
SL denotes hard-drawn wire reinforcing fabric
S1. Unless noted otherwise, All structural steelwork shall be Grade
300 plus with chemical and mechanical properties in accordance
PG1. All purlins and girts shall be Stramit sections or approved
equivalent, supported by submission of section properties, purlin
Al All expansion and chemical anchors are to be installed in
accordance with the manufacturer's specifications and standard
S02 FOOTING & SLAB LAYOUT PLAN
instructions as may be issued during the course of the contract.
Any discrepancy shall be referred to the Engineer or Project
Investigations.
For building platforms less than 3000 MSQ take a minimum of 3 No.
RL
R
denotes hard-drawn wire reinforcing fabric
denotes structural-grade plain round bars
with the requirements of AS/NZS 3678 and AS/NZS 3679,
especially satisfying low temperature ductility requirements.
capacity calculations, bridging capacity calculations and a
performance warranty, produced and detailed for this project. All
installation details.
S03 ROOF FRAMING PLAN
Manager prior to proceeding with the work tests per layer of fill and a minimum of 3 No. tests per visit. For
building platforms more than 3000 MSQ take a minimum of 1 No.
N denotes cold-worked deformed bar to the current version
of AS/NZS 4671 - Steel Reinforcing Materials. S2. All steelwork shall be provided with test certificates from a NATA
sections shall be produced from galvanised steel to AS1397 with a
2
coating mass of at least 350g/m and designed in accordance with
A2. Unless shown otherwise refer to the manufacturer for minimum
edge distances and minimum anchor centres.
S04 ELEVATIONS & SECTIONS
G2. Material and workmanship are ta be in accordance with the
relevant current Standards Australia codes except where varied
test per 1000 MSQ per layer of fill and a minimum of 3 No. tests
per visit. C15. The number immediately following the bar grade symbol represents
accredited testing facility. AS4600. Alt sections should be installed in accordance with the
manufacturers instructions with particular regard to bolt Al Expansion and chemical anchors are not to be installed into
SOS SLAB & FOOTING DETAILS SHEET 1
by the project specification,
SP8. All imported soil and fill is to be approved by the geotechnical
the normal bar diameter in millimetres. S3. Substitution of specified structural steel sections shall not be
made without the prior approval of the BYP Engineer. Such
locations and lap sizes. concrete until after the concrete has cured and attained 25 MPa
strength.
S06 SLAB & FOOTING DETAILS SHEET 2
G3. All dimensions are to be obtained from the Architect's drawings or
from site. Engineers drawings must not be scaled.
Engineer and is to have a chain of custody to ensure it is clean. C16. No holes, chases or embedment of pipes other than those shown
on the structural drawings shall be made in concrete members
substitutions may alter the performance of the structure. PG2. The purlin/girt layout shown on the structural drawings is
diagrammatic only. The purlin/girt centres nominated on the A4. All expansion and chemical anchors are to be torque tested in
S07 PRECAST PANEL DETAILS SHEET 1
G4. The approval of a substitution by the Engineer is not an FOUNDATIONS
without prior approval of the Engineer. 54. All steelwork shall be fabricated and installed in accordance with
the current version of AS 4100 - Steel Structures.
structural drawings are maximum and may need to be reduced to
comply with support spacings required by roof sheet manufacturer
accordance with the manufacturer's specifications prior to loading.
SOB PRECAST PANEL DETAILS SHEET 2
authorization for an extra. Any extra involved must be taken up
with the Architect or Superintendent before work commences. F1. All footings are to be founded 100 min. into very stiff clay at the
C17. Reinforcing bars terminating at openings in floors or walls to be
hooked. At all openings in walls add 2-N16 bars on all sides SS. All exposed external steelwork to be hot dip galvanised unless
and/or for architectural finishes etc. SLAB MAINTENANCE S09 FRAMING DETAILS SHEET 1
GS. Unless noted otherwise, the design of the structure addresses
base of any silt or proposed fill with an allowable minimum safe
bearing capacity of 250 kPa for isolated pads or 200 kPa for strip
projecting 600mm past the corners unless otherwise noted on the
structural drawings.
noted otherwise on these drawings or as specified by the
Architect/designer.
PG3. Refer to architectural documentation for type and thickness of
roof sheeting and finishes.
SMt During the life of a Building damage in various forms is likely to
occur to the concrete slab. Good housekeeping will keep problems
S10 FRAMING DETAILS SHEET 2
the structural adequacy of the completed building only. footings.
C18. All temporary openings to be formed in floors and walls for S6. All welding to be Category SP (Structural Purpose) in accordance PG4. The fabricator shall determine the total number of purlin/girt
to a minimum and extend the life of the floor and road stabs.
S11 FRAMING DETAILS SHEET 3
G6. THE BUILDER SHALL BE RESPONSIBLE FOR ENSURING THAT THE F2. Refer to soil report No 2338-5-R prepared by GeoAust construction purposes to be approved by the Engineer. with the current version of AS 1554 - Structural Steel Welding, runs required. The total number of purlin/girt runs required shall SM2. The following likely areas of damage may or may not occur during
STRUCTURE ANO ALL OF ITS ELEMENTS ARE AOEOUA TELY BRACED Geotechnical Engineers Pty. Ltd. dated 14/03/13. AH reinforcement for any one pour shall be completely placed and with E48XX electrodes or equivalent. be based on the written information contained on the structural the life of the building:-
AND FULLY TENSIONED AND MAINTAINED IN A SAFE AND STABLE tied prior to inspection by the Engineer or Architect. No concrete and architectural documentation. al Damage to joints such as fretting or breaking away at floor.
CONDITION DURING THE ENTIRE ERECTION ANO CONSTRUCTION F3. All footing excavations are to be inspected and approved by the shall be poured until reinforcement has been inspected and S7. All welding is to comply with Bruce Young Partners drawings and These should be repaired using epoxy concrete repair
PHASE. NO PART OF THE STRUCTURE SHALL BE ALLOWED TO BE
OVERSTRESSED DURING THE CONSTRUCTION PHASE.
Building Inspector or the Geotechnical Engineer, Footing
excavations in fill areas are to be inspected and approved by the
approved. the current version of AS1554 - Structural Steel Welding. PGS, The building and setout dimensions shall be obtained from the
architectural drawings.
products and the jointing material made good.
b) Cracking of slabs which may occur over the life of the slab,
C01 STORMWATER DRAINAGE & PAVEMENT LAYOUT PLAN
G7. The Steel Erector is to employ their own Erection Engineer to
Geotechnical Engineer. C19. AH beam stirrups shall have 135 degree bends at the free ends of
the bars.
58. U.N.O. all welds to be 6mm continuous fillet laid down with
approved covered electrode in accordance with the current version PG6. The fabricator shall provide all trimming angles required for the
These should be repaired by epoxy grouting as soon as
possible to prevent local fretting and breaking away.
C02 STORMWATER DRAINAGE & PAVEMENT DETAILS
fulfil! the obligations of Work Safe Victoria Industry Standard: F4. All water must be removed from footing excavations, and any of AS/NZS 1554 - Structural Steel Welding. support of box gutters, flashings etc. and the edge and end
Safe Erection of Structural Steel for Buildings Edition No. 1, May softened materials removed before concreting commences. C20. The Builder's attention is specially directed to the top steel on support of roof and wall sheeting. SM3. The definition of a crack which may become detrimental is one
2009. this job. Reinforcement is to be securely tied and supported in its S9. All base plates to be 6 cfw to columns/mullions U.N.O. which is greater than OJ mm,
F5. Blinding Concrete may be required. correct position so as not to be displaced during concreting. PG7. Purlins shall be evenly spaced between the ridge and eaves purlin
GS. The Steel Erector 8,. Builder are to ensure that the steelwork is 510. Butt welds shall be conducted with pre-qualified welding locations, unless noted otherwise. The maximum end span for roof SM4. local Damage due to mechanical processes or pallets (with
erected in accordance with AS 3828-1998 and Work Safe Victoria F6. The limitations of excavations near footings shall be as follows: C21. Formwork stripping times. Recommended Minimum Stripping Times in procedures in accordance with AS 1554. sheeting at ridge, roof sheeting expansion joints and eaves protruding nails! should be repaired as soon as possible with an
Industry Standard: Safe Erection of Structural Steel for Buildings the Absence of calculation and Strength Testing. locations shall be 1000mm u.n.o. epoxy concrete repair product.
FOUNDATION
Edition No. 1, May 2009. S11. Welding shall be carried out under the direct supervision of a
Minimum Stripping Time (days) qualified welding supervisor as defined in AS1554. PG8. Girts shall be evenly spaced between top and bottom girt SM5. local movement of slabs caused by external sources such as
G9. All propietary products are to be installed in accordance with the ' for Average Air Temperature locations, unless noted otherwise. egress of water should be referred to the Structural Engineer to
Member During Period Prior to Stripping
manufacturer's specifications. Member Effective S12. All bolts shall be Grade 8.8 high strength structural bolts in determine the best method of repair.
�-+s+- BACKFILLED Type 20'( 10'(
Span (ml 5"C to Under accordance with AS1252 unless noted otherwise. PG9. Bridging locations are to be as shown on plan.
G10. No substitutions shall be made or sizes of structural members TRENCH OR and to SM6. If solid wheeled materials handling equipment is to be used, joint
10"( 5'C
varied without the written approval of the Engineer. The approval EXCAVATION over 20"( S13. All holding-down bolts shall be grade 4.6 in accordance with AS1111 PG10.Purlin and girt bridging is to be fixed in accordance with the damage should be expected and a regular maintenance program will
of a substitution from the Engineer shall not be an authorisation PIPE Vertical Walt, Column, unless noted otherwise. manufacturer's specification. be required.
0 2 J 5 1
for a variation. All variations shall be taken up with the Unloaded beam side
Superintendent before the work commences. Wall, Column S14. All structural bolts shall be snug-tightened in accordance with AS PG11. Girts shall be tied back to columns or supports at the top of watts GLAZING
Vertical or 4100 unless noted otherwise. at each end with 12 dia diagonal rods, or strutted off the top of
CRITICAL LINE OF REPOSE 0 5 6 1 9
G11. All costs incurred by the Engineer for assessment or approval of loadbearing loadbearing concrete dado panels to prevent sagging. GL1. All glazing to conform to the current version of AS 1288 - Glass in
substituted members or alternative building solutions shall be CONCRETE structure 515. The bolt tightening procedure is as follows: Buildings.
bourne by the Builder. under 3 7 10 14 21 • 4.6/S refers to commercial bolts of strength grade 4.6 to CRANE BEAMS
C1. CONCRETE TESTING Horizontal Slab 3 to 6 10 14 21 28 AS1111 tightened using a standard wrench to a snug-tight
G12. If cranes are to be located on slabs, details including wheel and PROJECT ASSESSMENT OF CONCRETE SHALL BE PERFORMED IN over 6 14 21 28 28 condition. CB1. It is the fabricator's and erector's responsibility to ensure that
outrigger loads are to be submitted to the Engineer prior to ACCORDANCE WITH THE CURRENT VERSION OF AS 1379 - • 8.8/S refers to high-strength bolts of strength grade 8.8 to the crane beams are fabricated and erected within the required
under 3 10 14 21 28
pouring slabs. The Builder shall provide load spreading as directed SPECIFICATION AND SUPPLY OF CONCRETE. ie. ONE SAMPLE SHALL AS1252 tightened using a standard wrench to a snug-tight tolerances for sweep, camber, level and alignment as per AS 4100
Horizontal Beam 3 to 6 14 21 28 28
by the Engineer. All reviews of construction loading will be done by BE TAKEN FROM EACH 50 CUBIC METRES OF CONCRETE SUPPLIED. condition. (especially sections 14 and 15} and AS 1418.1 (especially table
this office on a time and expense basis. THIS PROJECT IS TO BE REGISTERED WITH THE CONCRETE SUPPLIER over 6 21 28 28 28 • 8.8/TF refers to high-strength bolts of strength grade 8.8 to 7.20.9). This is to be checked and verified by both the fabricator
TO GAIN ACCESS TO PRODUCTION ASSESSMENT DATA AS WELL AS x Effective span is the maximum distance between supports (either AS1252 fully tensioned to AS4100, designed as friction type and erector at the completion of each stage. The final centreline
DESIGN LOADS THE ABOVE TEST RESULT. temporary or permanent). joints. of the installed runway beam shall not deviate from the runway
• 8.8/TB refers to high-strength bolts of strength grade 8.8 to rail alignment by more than+/- 2mm.
The building has been designed for the following superimposed C22. Standard lap lengths for stabs and walls with less than 300mm of AS1252 fully tensioned to AS4100, designed as bearing type
design loads: C2, All concrete workmanship shall be in accordance with the current concrete cast below the bar and clear spacing of not less than joints, TIMBER FRAMING
version of AS 3600 - Concrete Structures. 150mm:
Category Region
516. Bolt hole clearance shall be 2mm for bolt diameters in the range of T1. Timber framing including roof and wall bracing shall comply with
Wind Terrain North 3 A
Cl All Concrete shall achieve the following minimum compressive CONCRETE STRENGTH -- 32 MPa 12mm to 24mm unless noted otherwise and 3mm for larger bolts. the requirements of the current version of AS 1720 and the IM,BJI ISU:LO:UG tERVICi!:$ I'll 'A' 'A'
South 3 A strength at 28 days: national timber framing code AS 1684 - Residential timber-framed
BAR DIAM N12 N16 N20 N24 N28 N32 N36 I"
I East
West
3
3
A
A
Footings
Slabs
25 MPa
Refer notes on plan.
COVER (mml LAP LAP LAP LAP
-
LAP
-
LAP
-
LAP
-
517. Gusset plates 8mm unless noted otherwise. construction. The most onerous of either shall apply.
... '
DESIGN LOADS, Note: Footings shall achieve a minimum strength of 20 MPa prior to 20 500 740 990 518. For steel connections not detailed, provide the following:- T2. Provide double stud support to each end of all beams and lintels I'1'111'1 I Tl ,/"
Dead load kPa live load kPa erection of steelwork, Concrete supplier shall confirm the time 25 470 100 950 1220 - - - Roof members: 10mm min cleat plate with min 2-M20 8.8/S bolts or unless shown otherwise.
1'1'111'1' 1•1·,11,·
1 ,q, / RAFTER
/-o:iy· ~.,
'
Warehouse Roof 0.21 , required to achieve minimum strength. To reduce the time required Depth of member/100 ie. 360 UB:;: 4-M20 8.8/S bolts, which ever is
30 430 670 920 1190 1480 1170 2080
-
..... J.
the concrete strength may need to be increased. greater. T3. All dual beams to be laminated in accordance with the current
1.1 1 I I' I 11'1' ' 11 I I "' I
Warehouse floor - U.D.L. I 25 kPa
35 400 630 880 1150 1440 1150 2080 Floor members: 10mm min cleat plate with min 2-M24 8.8/S bolts or version of AS 1684 - Residential timber-framed construction.
50 kN / POST LOAD-noY'- _/
within 500mm of any floor
Concrete sizes shown do not include finish and must not be Depth of member/100 ie. 360 UB:;: 4-M24 8.8/S bolts, which ever is IYi i,I' ··"11·
- Racking reduced or holed in any way without the Engineer's approval. C23. Standard lap lengths for band beams, beams and columns. 150 min. greater. T4. All roof framing members including beams and lintels supporting
joints. Based on standard bar spacing. Distance between lapped bars to be less than 3 bar light weight roofing shall be securely tied down to resist specified
Dexion layout. CS. Depths of beams are given first and include slab thickness. Slabs
and beams are to be poured together. Minimum specified design
diameters: S19. All cleats and drillings for fixing of timber members, etc., to be
provided by the fabricator.
design wind parameters. BOLT CLEARANCE DETAIL
2.0 T. SWL FORKLIFT WITH 4.7
- Forklift T. MAX FRONT AXLE LOAD thickness shall be maintained throughout for beams and slabs. CONCRETE STRENGTH -- 32 MPa TS. Roof truss installation and bracing shall comply with the current PORTAL FRAME END PLATE CONNECTIONS
(PNEUMATIC TYRES) BAR DIAM N12 N16 N20 N24 N28 N32 N36 520. Camber to structural steel roof beams, trusses, etc., to be 2mm version of AS 4440 - Installation of nailplated timber trusses.
New External
(6. Concrete cover to be maintained by means of approved chairs for every 1000mm of span between supports unless noted NOTE:
COVER (mml LAP LAP LAP LAP LAP LAP LAP
Pavement
- U.D.L. 10 kPa and/or concrete blocks spaced at approximately 600 cross otherwise. GENERAL PANEL NOTES BOLT CLEARANCES TO ADJACENT PLATES OR
centres, or to the approval of the Engineer. 20 650 960 1290 - - - -
UNLIMITED REPETITIONS WITH
25 610 910 1240 1590 - - - S21. Camber to Portal frames as shown in diagram. If no diagram is P1. All panels to be 150 min. struchral thickness U.N 0 FLANGES (DIMENSION 'A') TO BE EQUAL WITH
MAXIMUM LOAD OF 165
- Trucks
T./TANDEM AXLE & 21 T./TRI
C7. Clear concrete cover to reinforcement, unless otherwise noted to
30 560 810 1190 1540 1920 - -
supplied, contact the design Engineer for instructions. A MAXIMUM OF 2.0 x BOLT DIAMETER UNLESS
be: P2. Concrete strength for panels to be 40 MPa min.
AXLE.
35 520 820 1140 1490 1B70 2270 - S22. All diagonal roof bracing shall be hung from every second purlin.
APPROVED BY THE DESIGN ENGINEER
Structural Element:
2.0 T. SWL FORKLIFT WITH 4.7 P3. Concrete strength at lifting to be 25 MPa min.
Cast against forms complying with Exposed to 40 510 170 1090 1440 1810 2220 2650
- Forklift T. MAX FRONT AXLE LOAD
the current version of AS 3610 - ground, Aggressive 50 510 100 1000 1340 1710 2110 2540
523. Where the span of Roller door headers exceed 5000, provide 50 x 8 TYPICAL FOR ALL COLUMN/RAFTER
(PNEUMATIC TYRES! diagonal braces located as per typical details to prevent sag. P4. The Precast Supplier shall employ their own Erection Engineer to
Formwork for Concrete. In sheltered water or Conditions Where span does not exceed 5000mm diagonal brace is not fulfil the obligations of Work Safe Victoria Industry Standard: COLUMN/CANOPY RAFTER & RAFTER/RAFTER
locations and not later exposed. weather. C24. All concrete to be in the range of 600 - 650 maximum Microstrain required. Precast Tilt-up Concrete for Buildings. CONNECTIONS
Pad Footings - 65 15 at 56 days with a 70mm maximum slump+ \- 15mm. Stab to be cured
Strip Footings - 50 65 with Concure CR or approved equivalent in accordance with the S24. Masonry walls to be tied to structural steel members with R6 ties PS. A hard copy of shop drawings for all concrete panels are to be
SOIL CONDITIONS Columns & Pedestals 40 60 - C25. manufacturers specifications. or similar spaced at 600mm horizontally and 400mm vertically. submitted to the Engineer for review a minimum of 14 days prior to
Ties to be rigidly attached to steel members. the scheduled fabrication date and review of the same obtained
SC1. THE CLIENT AND BUILDER ARE TO READ AND FULLY UNDERSTAND Beams 40 60 - For atl surface finishes to both internal and external concrete before commencement of panel manufacture.
THE SOIL REPORT PRIOR TO COMMENCEMENT OF CONSTRUCTION. Slabs on Ground - 35 - pavements, refer to Architect. S25. Concrete encased structural steel to be enclosed by one layer Emailed shop detail drawings will not be accepted.
THE FOOTING AND SLAB SYSTEM ADOPTED HAS THE POTENTIAL Suspended Slabs 30 40 - Sl41 placed clear of steel. Encasing to provide 65mm cover, where
FOR SOME SETTLEMENT AND HEAVE, Walls 40 50 - C26. Internal and external concrete slabs on ground shall be separated exposed to earth, All other steelwork to be given one shop coat of P6, Shop drawings shall indicate all reinforcement, lifting points,
from concrete walls by a full depth continuous strip of Abelflex or approved paint after vigorous wire brushing. propping points, cast in plates, cast in ferrules, rebates, etc. In
SITE & SLAB PREPARATION CS. Camber to suspended slabs to be 3mm for every 1500mm of span, approved equivalent unless noted otherwise. In addition, external addition all penetrations should be located in panels for sewer,
unless noted otherwise. Minimum specified design thickness and interfaces shall be sealed with an approved sealant. S26. All steelwork {unless otherwise specified) shatl be shop primed as stormwater, electrical, mechanical, gas, water, telecom, etc and
SP1. Site and slab preparation shall be performed in accordance with cover to reinforcement shall be maintained throughout for beams follows: any other services The panel supplier is responsible for providing
soil report. and slabs. C27. For suspended slabs and beams, safety mesh reinforcement shall Generally Class 1 prep. GOZPH. alt propping and concrete pad footing propping supports required
be installed in accordance with 0. H. &- S. requirements. Contractor Canopy steel Hot dip galvanised for panel installation.

Project No: 13018


SP2. Slab preparation shall consist of grading site to level and C9. Construction joints where not shown shall be properly formed and is to allow for placement and reinforcement supplier is to allow Office steel Class 1 prep. GOZPH. client:
removing all loose debris, organic matter and vegetation from the located to the approval of the Engineer, for supply. Exposed steel Hot dip galvanised P7. Grout to be non-shrink structural grout with minimum compressive

Drawing No: S01


natural surface before backfilling is commenced. Note: GOZPH indicates grey oxide zinc phosphate, strength of 50 MPa and is to be located under the full bearing
C10. Concrete to be kept free of supporting brickwork by two layers of C28. Place 2-N12 bars x 1500 tong top in slabs on ground diagonally area of all panels. NICHOLAS & ALEXANDER ARCHITECTS
SP3. Where required fill shall be as approved by the soil Engineer and a suitable membrane !Malthoid, etcJ or as directed by the Engineer. across all re-entrant corners. Place 2-N16 bars x 2000 long top S27. Grout to be non-shrink structural grout with minimum compressive 31 Bevan Street, Albert Park, 3206
compacted in accordance with their report. Vertical faces of concrete to be kept free by a 12mm thickness of
Abelflex or approved equivalent.
and bottom of suspended slabs and in each face of walls
diagonally across re-entrant corners.
strength of 50 MPa and is to be located under the full bearing
area of all structural elements.
PS. Each fabric wire cut to allow placement of fitments shall be
replaced with 1-N12 bar lapping 500mm each end with fabric wires. Date: March 2021 Tel : 9696 5811
fax, 9696 5811
SP4. All fitting is to be compacted to 98% of the maximum dry density
determined by the standard compaction test in accordance with the
current version of AS 1289.
C11. Check with the Architect re V joint on rendered surfaces.
Brickwork must not be built on concrete slabs or beams until
C29. Welding or heating of reinforcement shall not be permitted without
written approval from the Engineer.
S28. A hard copy of the shop detail drawings shall be submitted to the
Engineer a minimum of 14 days prior to the scheduled fabrication
P9. Precast panels cast off-site have been designed by this office for
in service conditions only.
Revision: 01 Email : naarch@bigpond.net.au
ACN 010 432 932
formwork supporting same has been removed. date and review of the same obtained before commencing © Copyright Bruce Young Partners Pty. Ltd. 2020. This drawing »hall not be copied or modified in whole or
in part without the prior written permis»ion of Bruce Young Partners Pty. Ltd.
SP5. During compaction, the fill material should have a moisture content FABRIC LAP fabrication. Review will not cover dimensions or layout. P10. The fabricator shall supply and locate all lifting inserts as
within the range of 85 - 115 % of the optimum moisture content as C12. Reinforcement is shown diagrammatically and not necessarily in its Emailed shop detail drawings will not be accepted. required. These shall take the form of cast in erection anchors, consultant:
determined by the standard compaction test in accordance with the true projection. 25mm MAXIMUM Fabric mesh shall be lapped hooks and/or j-bolt ferrules etc.
current version of AS 1289. by one full panel of fabric S29, It is the fabricators and erectors responsibility to ensure that the
C13, Splices in reinforcement shall be made only in positions shown. plus 25mm so that the two steelwork is fabricated and erected within the required tolerances
SP6. level 1 certification is required to justify compaction density and Welding of reinforcement will not be permitted unless shown on outermost wires of one sheet for sweep, camber, level and alignment as per AS4100 lespecially 01 31.05.21 RS AS CERTIFIED BRUCE YOUNG PARTNERS
25mm MAXIMUM
moisture content in accordance with the current version of AS the structural drawings. overlap the two outermost sections 14 and 15). consulting structural and civil engineers
3198. • • • transverse wires of the PC 08.0S.21 RS ISSUED FOR TENDER
sheet being lapped by 25mm. 530. The ends of all tubular members shall be sealed with nominal PB 02,0S.21 RS ISSUED FOR CLIENT PRESENTATION
thickness plates and continuous fillet weld u.n.o. 2 Small Street, Hampton. Victoria 3188
PA 24.04.21 RS PRELIMINARY ISSUE
Ph: 03 9521 8588 Fax: 039521 8211
rev: date: by: description· Emaii: byp@byp.com.au A.B.N. 78 005 394 758
INTERNAL PAVEMENT PAD FOOTING SCHEDULE
MARK SIZE (L X w X DI REINFORCEMENT

0
180 THICK R.C. SLAB ON GROUND U.N.O. 40 MPa.
C E F F'cf @) 90 DAYS SHALL BE 5.0 MPa. F1 1600 X 1400 X 600 SL81 TOP & BOTTOM
SL92 TOP. 35mm COVER. TO BE PLACED ON
APPROVED MOISTURE BARRIER, LAPPED AND TAPED, F2 1000 X 1600 X 600
SL81 TOP &
1 LAYERS SL81 BOTTOM

F3
ON 50mm PACKING SAND BED OR APPROVED 1100 X 1100 X 600 SL91 TOP & BOTTOM
EQUIVALENT OVER 100mm OF CLASS 3 CRUSHED
ROCK, 20mm NOM. SIZE.
. - F4. -- 1500 X 1500 X 800
- -- .-· - . ----- --SL81 TOP'·& BO
.
TTOM

F5
. .
ADJOINING BUILDING THIS PROJECT IS TO BE REGISTERED FOR PROJECT --
--�
NOT USED \
ASSESSMENT AND FOR PRODUCTION ASSESSMENT.
REFER TO CONCRETE TESTING NOTE C1 ON SHEET S01. ____
.___ / "�. .•./ _____/ . .• ____
./ .___ / ,_____,/

BAR CH AIRS @1600 CRS EACH WAY. SLAB CURING METHOD TO BE


/
COMPATIBLE WITH ARCHITECTUR AL FINISHES AND CURRENT AUSTR ALIAN STRIP FOOTING SCHEDULE
STANDARDS. ALL CONCRETE TO BE IN THE R ANGE OF 600-650

lI __
MICROSTRAIN AND SHALL HAVE A 60mm MAX. SLUMP ,/-15mm. MARK SIZE (W X DI REINFORCEMENT
"' REFER TO ARCHITECT'S DWGS FOR SETDOWNS, RECESSES,
II
--t-1
" FINISHES AND SLAB GRADES
L,U�r;F2 F2 L....,<SIZ::,,,.-'F2 '--,H.,
--'
F2 SF1 --
su ________
N L...,,<C,iz,,.._.....J NOT USED

V,

"'"' �1 -- -+ -------- ---- SCJ I


SF2 4-L11TH TOP & BOTTOM

- y
400 X 600
I I
J
R10-800 SPACER LIGS
1
I. 11�
VJ
FOOTING RL'S = 16.7 " 4-L11TH TOP & BOTTOM
I SF3
I I
400 X 600
PSF1
('
- � - -- -- -- --- - -

STRIP FOOTING REINFORCEMENT IS TO BE


c=n-;== Rl0-800 SPACER LIGS
I
DRILL & EPOXY 2-N20 x SF3[E]]
I/ J +--1 I I
I - > II CARRIED THRU ANY PAD FOOTINGS IN THE LINE
OF THE STRIP FOOTING.
600 LONG TOP & BOTTOM pJ
+-+--+- _ - - - - PJ (
I -= I
300 INTO EXISTING STRIP f-+-
FOOTING
i==f--1 ('
>
1 1

FOOTING RL'S = 27.00,


LOCALLY WIDEN STRIP
I I I I NOTE:
1

''•·�·"'ll :,
11
SF3 BY 600 x 600 TO
EXCEPT THOSE NOTED ON PLAN
''
NOTE: FOR SUBGRADE PREPARATION REFER TO
ACCOMADATE M1

� /'I � �1 3 �1 0::1 �I �I
I I
(' II SOIL REPORT No. 2338-5-R BY GEOAUST NEAR GRIDS A-B/l
I >I
° u u

"'1 == I = = -+I I I� GEOTECHNICAL ENGINEERS PTY. LTD. DATED BUILDER TO PAY PARTICULAR
V,

"'1
I s�5 '
14 MARCH 2013. ATTENTION TO PAD FOOTING AT
�-7--
--- --
--t---
- - - -
--;I
SCJ
I DOWNPIPE DETAIL PRIOR TO
I I I>I
' I
POURING FOOTINGS.
REFER TO ARCHITECTS

l_
EXISTING COLUMN
1 ''

''>
ITYPICALI
I I
I
I I DRAWINGS FOR ALL SETDOWNS,

----,---
F3
I --j -- -- RECESSES & SLAB GRADES
--+-- - -_ S
I
>
_SC_
J ----
I
_J -- �I �(>

1
I I >I
''
II
I I ''
I I�
''>
I NOTE:
I I II ALL FILLING IS TO BE COMPACTED TO 98% OF THE
I
I

I == = = I MAXIMUM DRY DENSITY DETERMINED BY THE


I I
>
STANDARD COMPACTION TEST IN ACCORDANCE WITH
THE CURRENT VERSION OF AS 1289.
---- � -----0
DDJ
I
DDJ I I
'
/>
I

I I DURING COMPACTION, THE FILL MATERIAL SHOULD


I

I F3
HAVE A MOISTURE CONTENT WITHIN THE RANGE OF
'

I I 11_j
I

,j
85 - 115 % OF THE OPTIMUM MOISTURE CONTENT AS
I I I I� DETERMINED BY THE STANDARD COMPACTION TEST IN
s
I

----r--- I

__j _SCJ_
---, - -- -----+-- -

- �I- _S�(
= -=
I
ACCORDANCE WITH THE CURRENT VERSION OF AS 1289.

LEVEL 1 CERTIFICATION IS REQUIRED TO JUSTIFY


/'>
\

I I COMPACTION DENSITY AND MOISTURE CONTENT IN


I I ACCORDANCE WITH THE CURRENT VERSION OF AS 3798.
1

-+-
ADJOINING BUILDING '>
I I ALL IMPORTED SOIL AND FILL IS TO BE APPROVED BY
\
I

F3
I
I

I IN THE GEOTECHNICAL ENGINEER AND IS TO HAVE A CHAIN


>----- - : - _J - I
+-+--
I I '(
-
I
I -
-t PJ
➔1. --+-IHI t?;
OF CUSTODY TO ENSURE IT IS CLEAN.

-v-✓-v
1

✓-v-✓-v ✓-v-✓-v- -- - -- -- -- -- I
- -- -- II
;: :r

NEW PIPELINE
I I

------------,----
I DECOMMISSIONED
I
I
----
SCJ PIPELINE
1
1
1
I
I
I l!&EIA IBl.llllXUG SfflVICES: Ila..

I ·1111111 ''I I' ·I'{ .


I ·1111111 T'I' ,i 'I r 11111,: 1,•·1• ·,
1

I ., I 11 I '•II'" ' I '' I I I ,-, I ,, ' 11 ; I Vt "


& EPOXY 1-N10 x
600 LONG TOP & BOTTOM
\ 1

<
''
INTO EXISTING STRIP
I ,,- \ r,I f' ., 'I I' · I : ' ·,";, ·,, ·,
&
NOTE , FOOTINGS TO BE BLINDED
E �ISTING CANOPY DOWN TO RL = 15.50 TO AVOID
u REFER TO CIVIL DWGS FOR I
s A E
D AGE T

)
� �:- �--�
}
�- �--� �--�- �--� �--A- �--� �--A- �-'� =- �=-□:: ,A_ �--A- �--A- �--A_ :: :� :_«_ �_,A_ �_/,_�_,A_ �_/,_�_jA_ �_/,__A__/

========�======================="=:,:�� EXISTING
COLUMN
CANOPY

ADJOINING BUILDING

u� o u u ,o ,o so ,o 10 u 10 100

Scale: 1:100 Metres

© Copyright Bruce Young Partners Pty. Ltd. 2020. This drawing shall not be �opied or modified in whole or in part without the prior written permission of Brute Young Partners Pty. Ltd
project:
01 31.05.21 RS AS CERTIFIED PROPOSED WAREHOUSE ADDITIONS FOR designed: SP
PE 08.05.21 RS ISSUED FOR TENDER NICHOLAS & ALEXANDER ARCHITECTS SOCCOBEL dca�,.
PD 01.05.21 RS ISSUED FOR CLIE NT PRESENTATION 37 Bevan Street, Albert Park, 3106 553 SOMERVILLE ROAD, SUNSHINE, VIC BRUCE YOUNG PARTNERS RS

Tel, 9696 5822 consulting structural and civil engineers date: March 20f3
PC 14,04.21 RS PRE LIMINARY ISSUE Fax, 9696 5833 dravving title: scale: 1:100 @ 81
PB 04.04.21 RS PRE LIMINARY ISSUE Email, naarch@lbigpond.net.au �
-> p,ojectw
13018
PA 08.03.21 RS PRE LIMINARY ISSUE ACN 070 432 932 GROUND FLOOR PLAN
2 Small St_ Hampton, Vic. 3188
Ph: 03 9521 8588 Fax: 03 9521 fl211 � revision no· 01
ra,· Email: byp@byp.com.au A.B.N. 78 005 39-1 758
dale- by· description:
drawing no: S02
STEELWORK MEMBER SCHEDULE
PURLIN & GIRT SETOUT NOTES MARK SIZE REMARKS

0!:-" ® ®
1. THE PURLIN/GIRT LAYOUT SHOWN ON THE STRUCTURAL
DRAWINGS IS DIAGRAMMATIC ONLY. THE PURLIN/GIRT CENTRES PORTAL FRAME REFER ELEVATION FOR DETAILS
C E F NOMINATED ON THE STRUCTURAL DRAWINGS ARE MAXIMUM PF1
AND MAY NEED TO BE REDUCED TO COMPLY WITH SUPPORT
SPACINGS REQUIRED BY ROOF SHEET MANUFACTURER AND/OR
✓-V-·'V·-✓-"✓-V-·'V·-�.
I, NOTE, BR1 & S1 TO BE LEFT OUT HERE NOTE, THESE PURLINS TO BE LEFT OUT FOR ARCHITECTURAL FINISHES ETC. 15mm BASE PLATE, 4M24 H.D. BOLTS. 450 MIN. EMBEDMENT.
� DURING INITIAL INSTALLATION OF C1 610 UB 125
( ONLY DURING INITIAL INSTALLATION DF 1, FLYBRACES AT 3m & 6m REFER ELEVATIONS

STEELWORK
&'
\..,\.._-�-___.,A,____/'-._ __...,./"....._ ___ ,,A..._ __ ..,./'...__ _j
I (- ����¥��¥;;,;�Ys�;�-
\ ERECTION DURING CONSTRUCTION
tv/4\\01 )
I I 1. REFER TO ARCHITECTURAL DOCUMENTATION FOR TYPE AND
THICKNESS OF ROOF SHEETING AND FINISHES.
25mm BASE PLATE, 4M24 H.D. BOLTS. 450 MIN.
____,,A..__ __../
j 3. THE FABRICATOR SHALL DETERMINE THE TOTAL NUMBER OF M1 200 UC 46
•\......_ "-�----�---,./'-..� ____/'-..._____A� ---�---,./'-..� ___/_
PURLIN/GIRT RUNS REQUIRED. THE TOTAL NUMBER OF EMBEDMENT.
PURLIN/GIRT RUNS REQUIRED SHALL BE BASED ON THE 25mm BASE PLATE, 4M24 H.D. BOLTS. 450 MIN.

\
WB1 WB1 M2 310 UB 40
WRITTEN INFORMATION CONTAINED ON THE STRUCTURAL AND EMBEDMENT. FLYBRACES AT j POINTS.
I I I
*
ARCHITECTURAL DOCUMENTATION. 15mm BASE PLATE, 4M24 H.D. BOLTS. 450 MIN.
M3 310 UB 40
EMBEDMENT. FLYBRACES AT j POINTS.
c"- (" <"- (" �
THE BUILDING AND SETOUT DIMENSIONS SHALL BE OBTAINED
- - - ' ' - 4. 15mm BASE PLATE, 4M24 H.D. BOLTS. 450 MIN.
FROM THE ARCHITECTURAL DRAWINGS. M4 310 UB 40
EMBEDMENT, FLYBRACES AT j POINTS.
-"- ./,/. / \ ."-.. �S1 /
- S1\
- _'-...__,_ S1
-. S1
5. THE FABRICATOR SHALL PROVIDE ALL TRIMMING ANGLES SC1 150 UC 23 HOT-DIP GALVANISED. REFER SECTION 6 ON S09
OJ
"tJ
-FB �
\ - -FB
FB 811< !

/ - -
'""i's
FB
-
F

FB
BR,
FB
REQUIRED FOR THE SUPPORT OF BOX GUTTERS. FLASHINGS
ETC. AND THE EDGE AND END SUPPORT OF ROOF AND WALL SC2 100 UC 46
TWB1 !a � SHEETING.

-
� �
I-
N
6. PURLINS SHALL BE EVENLY SPACED BETWEEN THE RIDGE AND SC3 150 PFC

*
Q'.

,/
_,
I
.o1, �
- EAVES PURLIN LOCATIONS. UNLESS NOTED OTHERWISE. THE

1/ �✓
100 UB 11 REFER TYP. BRACING DETAILS FOR END CONNECTION TYPE.
MAXIMUM END SPAN FOR ROOF SHEETING AT RIDGE, ROOF R1 16 END PLATES, 4-M16 8.8/S BOLTS. 1 FLYBRACE MID SPM
SHEETING EXPANSION JOINTS AND EAVES LOCATIONS SHALL
V S1 S1 BE 1000mm U.N.O. 200 UB 22 REFER TYP. BRACING DETAILS FOR END CONNECTION TYPE.
'
_.!
;:, I

� R2 16 END PLATES. 4-M16 8.8/S BOLTS. 1 FLYBRACE MID SPA
S1 V
c.,◊
�BA
"' / � �8- �....···� I� /
c.,◊ I 7. GIRTS SHALL BE EVENLY SPACED BETWEEN TOP AND BOTTOM
GIRT LOCATIONS, UNLESS NOTED OTHERWISE.
S1 168 x 4.8 CHS FOR END PLATES AND BOLTS REFER STRUT
CONNECTION SCHEDULE DN DRG, S10

,,/
__.....- FOR END PLATES AND BOLTS REFER STRUT

/ /
/ S2 114 x 4.8 CHS
/4- I /
8. BRIDGING LOCATIONS ARE TO BE AS SHOWN ON PLAN. / f-st:!)IEfil()N��..'9110%,518-v-·---v----....

I
"'-....__ \ '
''·
Loh),
FB FB F§__
90 x 90 x 6 EA
� �
� N N
9. PURLIN AND GIRT BRIDGING IS TO BE FIXED IN ACCORDANCE T1 REFER ELEVATION & DRG. S09 FOR DETAILS
-
/�/ \
Q'. FB

A
<O <O
WITH THE MANUFACTURER'S SPECIFICATION.
\
3 3 F E);f.f'l'.ATffA 't:T5"'REct1n,RAEll'IG

✓ A'
65 x 65 x 5 EA

I
BR1

// A '
� � CONNECTION SCHEDULE ON DRG. S1D
�24 ROD FOR CLEAT PLATES AND BOLTS REFER DETAILS ON
/ BR2 DRG. S10
GALVANISING NOTE:

I
FB FB � FB FB
., •/ V ., ' "'- I/ ;:, I /

' ALL EXPOSED EXTERNAL STEELWORK TO BE HOT

'
◊ "'-....__ / / / / /
DIP GALVANISED UNLESS NOTED OTHERWISE ON FOR CLEAT PLATES AND BOLTS REFER BRACING

I y /
THESE DRAWINGS OR AS SPECIFIED BY THE WB1 75 x 75 x 5 EA
� ! �
CONNECTION SCHEDULE ON DRG. S10

/ \
ARCHITECT/DESIGNER. FOR CLEAT PLATES ANO BOLTS REFER DETAILS ON DRG. S10.

// N WB2 �24 ROD


.. ..
CLEAT PLATE CONNECTION EACH END & TURNBUCKLE

X I X / X
FB FB FB FB Q'. . . _ r�NTRAL WITH SWL 70 kN.
V

N

rn/ DM1 NOT USED ..
<O
Q'.
\
REFER TO MECHANICAL DRGS FOR THE EXACT LOCATION OF

I ;
3 \ FB
EQUIPMENT, PENETRATIONS AND SUPPORT FRAMES. UNITS ARE TO BE DH1 NOT USED --
V /
\ <
/ ..__..__ SUPPORTED ON APPROPRIATE FRAMES SPREAD OVER A MINIMUM OF 3
fr"
R-"- --

FB

FB

FB / FB
'Q PURLINS. TYPICAL. MECHANICAL DESIGNER AND FABRICATOR ARE TO
LIAISE TO ENSURE THAT PENETRATION LOCATIONS AND PURLINS DO
DM2 NOT USED
I

NOT CLASH. I
/ / / / --TWB1 --
DH2 NOT USED
I
-------0
..
S1 � SJ 51 � s1 S1 � �'\,
_ ---- TEMPORARY ERECTION BRACING - THREADED EACH
A
...._

I/ �24 ROD
____,,


/ /
·;

END AND PROVIDE UWBB C/W NUT AND WASHER


':, � - �
FB FB FB
NOTE: THE STEEL SHOP DETAILER IS TO CO-ORDINATE WITH THE
...!' �
/ / / / SPRINKLER CONTRACTOR PRIOR TO COMMENCING SHOP DETAILS TO DOUBLE BATTENED

.A
REFER DRG. S11 FOR DETAIL
FB
ENSURE THAT THE SPRINKLER REQUIREMENTS ARE MET. TO CONFORM
� "-.. DP PURLIN

/
Q'. �
N
Q'.
WITH AS2118 SPRINKLERS

FB FB FB
/ FB

/
0 /�
LL LL LL LL EAVES TIE CLIPPED TO PANELS AT 1500 MAX CTS. 1
I/
/ a.. a.. a.. /
a.. ET1 310 UB 32
FLYBRACE MID SPAN. REFER DETAIL
H

r, � ' / ' ' / ' ,, C1 � �'\,


c.,◊
A I P1
,a/
'
/
WJ WJ WJ WJ

':, �
::E
/,,.__,,
::E FB ::E ::E
� FB REFER DETAILS FLY BRACE AS DETAILED


" /
0::
LL
0::
V 0::
LL
/
,, �
_/-,J _J � _J
FB
PURLIN SCHEDULE
�I -

/�
Q'. <( <( <( N
I- I- I- Q'.
MARK LAP
SIZE SPACING BRIDGING
0:: 0:: FB FB
-
0:: FB (u.n.o.l

//
� ,;,'<''


a.. a..
/ 2i: a.. P1 Z20015 1500 1400 2 ROWS
_, / -·r, �

/

' ' � P2 Z20019 1500 1400 2 ROWS

-
/ '
/


':, � / � -FB - -FB - FB - F
a,p; / NOTE: C - DENOTES STRAMIT C PURLIN

/
Z - DENOTES STRAMIT Z PURLIN
,// /
X

A
F§__

/
N FB N

I
N

L
<O <O <O
Q'.
3 FB FB FB FB
Q'.
3 3

- / - L·:��ii:r·%�: <
'-.,_/---'-.../"··-�'V', -----v··-��-
( S1over�� FB - FB ' I\
7'

0
\
ET1 under ) ET1 ET1 ET1 �

'
I

) '

◊ ) [
' [
l,___._/'-.....__ ..,.A.____��::·��---._/'-....._ _ ..,.A.____-,.,....
':, ../'-...._./'•.
�;;�
· _,,.......___.A•. 6
◊ ◊ ◊ WB1 17

NOTE:
NO PLANT IS TO BE
SUPPORTED OFF APPROVED WITH COH0ITION S
WAREHOUSE ROOF
BUILDING ACT
BUILCHrlG REGULATIOt-1S

BUILDING PER.MIT NO: BS-U


104&12013238610 DATT OF ISSUE: 3July2021

-,

CD

1.0 OS 0 U U 30 ,, 50 ., 10 U ., 100

Scale: 1:100 Metres

© Copyright Bruce Young Partners Pty. Ltd. 2020. This drawing shall not be �opied or modified in whole or in part without the prior written permission of Brute Young Partners Pty. Ltd
project:
01 31.05.21 RS AS CERTIFIED PROPOSED WAREHOUSE ADDITIONS FOR designed: SP
PE 08.05.21 RS ISSUED FOR TENDER NICHOLAS & ALEXANDER ARCHITECTS SOCCOBEL
PD 02.05.21 RS ISSUED FOR CLIENT PRESENTATION 37 Bevan Street, Albert Park, 3106 553 SOMERVILLE ROAD, SUNSHINE, VIC BRUCE YOUNG PARTNERS _d_c a�_,_. ---�R=s
Tel, 9696 5822 consulting structural and civil engineers _da_te_, -�M=•=rc=•�2==
PC 14.04.21 RS PRELIMINARY ISSUE
0f3
dravving title:
Fax, 9696 5833 scale: 1:100 @ 81
PB D4.04.21 RS PRELIMINARY ISSUE Email, naarch@lbigpond.net.au
.> �pco�i c_t_co_,�13�0�18-
.. e
PA 08.03.21 RS PRELIMINARY ISSUE ACN 070 432 932 ROOF FRAMING PLAN
2 Small St_ Hampton, Vic. 3188
Ph: 03 9521 8588 Fax: 03 9521 fl211 � revision no· 01
ra,· Email: byp@byp.com.au A.B.N. 78 005 39-1 758
by·
dale- description:
drawing no: S03
3 1 3
0 CD

:r
'GIRTS - G6'
( 6 ',. (6a 't..

,=· r �
==-- --r·=-�·=n = r =--r =s-1·
r ' -, T"'�- =-·- '
r
"'"
J" APPROX ROOF LINE
r
--- '"
7
"'" '"
.
R1
"F
10# I =· J ---------------�1 ' OF EXISTING
R1 R1
..
..,,
NOTCH PANEL TO SUIT ADJACENT BUILDING
----- \��

'i � � � �
,

u u u u u
0

ft

I I I
V') � \� V') V') -, "\ V)

,,�
\_PROVIDE
l:_ \ \_PROVIDE
0
0
- tll ------�
b,;rt�-�-�
- -

-- -- --- -- TURNBUCKLE TURNBUCKLE �


.- -.. '
C:"/ - SAME SWL AS SAME SWL AS
Qc,
-··
l�RET, 0 CLIP M1 TO
7 \
ROD TO ACHIEV
TENSIONING
� ROD TO ACHIEVE
TENSIONING ' EXIS ING PANELS AT

/"·--v-- ·-v-···--v--·- -v-· --V" '"'--


0 LOC, TIONS SHOWN
0
00

\
� �

<
> EXISTING PC WALL P NELS

,,� <
TO ADJACENT BUILOII G

&) '
�---.A-._--�-/'...._ .-.A-.___-.A-.__/

�-
,//

- -
•W •'" ·'0 •... ._�.,-c·-,.- •-y•,-'*·••
-
,.�;·,·;;;,;;;_ - - - ,.
I
I
- -

DETAILER AND CONCRETER _J


ADDITIONAL -
C20019 I I
TO ENSURE WB2 CLEARS
DOOR OPENING
,GIRTS - G1 IGIRTS - G2I

NORTH ELEY ATION ELEY ATION AT GRID A

A B C E F F E D
CD B B
0
> 7 r
/_/' -v----✓ADCTfflDNAYS-NN---v---·'v- 'v·--v----v---'v--'v--'v'--'v·----✓--'v--
BARS E.F. FOR FULL
,) CN2 HEIGHT {TYPICAL AT
,__---, >-----<
/\

S07 EAST ELEVATION)
HORIZONTAL PANELS - CPS

"-
SPANDREL PANEL - CP4 SPANDREL PANEL - CP4

\/
C25024 GUTTER PURLIN C25024 GUTTER PURLIN C15014 GUTTER PURLIN C15024 GUTTER PURLIN [15014 GUTTER PURLIN

c
S1 II S1

<
(!J <9

<<
:lrrm'i"m \

II ET1 ET1 Ill =


ET1
= =
ET1 ET1
9- = � 1!f=IIJ,=i!f
j

FFFF 7if
I � -IF II 91- ;i',= =j= =j= �1 I 15
-t ;'ii
i

( -"--+++--- F8

11111 � "� 11111 , Ill I " 11111 I


S09
1111 :> u
0
Ill� <9
11111
V,oc:�111
11111
""=I
'911
FB
�---- '°,
,,,. 11111 II
Ill 11111
1 1 11111 r,.t=============u=
11111
FB
-----='l'll'-lllHl-l--�--+--++11- <I

)
0
0
0
00 t I\
\

111 11111 1 1 11111 11111 11111 11111 1 1 11111 I I \


11 1 11111 1 1 r;,1111 11111 1111,,...........,JIII 1 1 11111 1 1 II
0
0

I /
0

<
500 min .,/
11 11111 11111 1111 1 1 11111 11 �
I
I \\ II 1 1 SOO MIN

�2���==========t=l���llit=:============�b�t============:=;::i::llEM===============�tti:ll!J������tt=;-;�-;:::tt$����������������������������
REFER TO TYPICAL REFER TO TYPICAL GROUT FOR EXTENT OF
c----,1CP2r---a �_,_.,CP2r---< CP2 CP ) HORIZONTAL PANEL DETAIL HORIZONTAL PANEL DETAIL FOOTING REFER TO PANEL
( � NOTCH PANEL AS
�-� �___.A...____ __ _�/'...._ �RE!WIR_E.D---ro_ __ _�/'...._ /'-......___/'··� �/"-....._ __ _�/'...._ /'-......___/'-,._ �--__�/'...._ /'-......___/'-,._ �--__//'...._ /'-....___//'...._____,A.._____/"'-..__ /'-....___//'...._____,A.._____/"'-..____/'--......___//'...._____,A.._____/"'-..____/'--......___//'...._____,A.._____/"'-..____/"'-..� _/'---._____,A.._____/"'-..____/"'-..� _/'---_____/"'-.._____/"'-..____/"'-..� _/ ON S08 FOR LOCATING PEG ON S08 FOR GROUTING [TYP) DETAIL ON S08 {TYPI
ACCOMMODATE DETAILS ITYPI
ELECTRICAL TRAY
ANO 0/FLOW PIPE
EAST ELEY ATION WEST ELEY ATION WEST ELEVATION AT RSD

CD 0 0 1 24mm PRECAMBER
SETOUT
100mm PRECAMBER
SETOUT
14mm PRECAMBER
SETOUT
3

4
S09

;
>&
>
I
\'
I
Ex. 530 UB B2 Ex. 530 UB 82

< <
EXISTING CANOPY
TO REMAIN TAPERED HAUNCH TAPERED HAUNCH
(
> )
<
\

--

<
-�,
'
,•
-
(
1, <

u \ 10�,?RECAMB1ER UPWARDS
NIJT-H'RE[AMBER TO PORTAL PF1 TO F
�,j -
/) EXISTING COLUMN CLIPPED I BE ACHIEVED B ROLLING ONLY.
�TO NEW PRE[AST WALL _I_/ PRE-SETTING IS OT ACCEPTABLE.
TYPICAL AT G IDS B, [, 0 & E
REFER DETAIL 13 ON S09
FOR DETAILS
7
I I
I I ' :

I I
ro
~
L

C
I I I
HORIZONTAL PANELS - CPS
00

ELEY ATION AT GRID B TYPICAL PORTAL SECTION

GIRT SCHEDULE PRECAST PANEL SCHEDULE


MARK SIZE SPACING LAP BRIDGING
ASSOCIAIIOrl
(u.n.o.l MARK THICKNESS REINFORCEMENT REMARKS J.IBA B,I.IILCl:l'IG �s; I'll

(-�A
G1 C20019 1500 -- 2 ROWS ·!:r/{: MESH EACH FACE REFER TO TYPICAL PANEL DETAILS /\j 11 1')\I 1
1 )·' J' ;rll )I: 'T:
CP1 MAI .,WIRES VERTICAL - FOR ADDITIONAL REINFORCEMENT
G2 220015 1500 900 AS SHOWN 30 c9vER

CP2 .8LS18 MESH CENTRAL REFER TO TYPICAL PANEL DETAILS ·1111111 ''l''I' ·,;v.:
G3 C20019 1500 -- 2 ROWS \'---.l�'", ,, MAIN WIRES VERTICAL FOR ADDITIONAL REINFORCEMENT ·1111111··1''11',1 1['1•1 111111, l,"l', 1.0 0.5 0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0

RL918 MESH CENTRAL REFER TO TYPICAL PANEL DETAILS


-- CP3
l.'1 1il I \i['i ', 'I• l 1 r1
150
G4 C20015 1500 1 ROWS MAIN WIRES VERTICAL FOR ADDITIONAL REINFORCEMENT
1"'1
'
I','' ii - ,· \ ' \' i• . ,· \'. ' "" I' \'' )' \,
.- © Copyright Bruce Young Partners Pty. Ltd. 2020. This drawing shall not be �opied or modified in whole or in part without the prior written permission of Brute Young Partners Pty. Ltd
Scale: MOO Metres

RL918 MESH CENTRAL REFER TO TYPICAL PANEL DETAILS


GS C20024 1500 -- 2 ROWS CP4 150 MAIN WIRES HORIZONTAL FOR ADDITIONAL REINFORCEMENT I '1 1 '1 , 1'.' ·1- v ','- I'' .I 1, i I,,,.,·
' ,' •,-.•-,I project:
RL918 MESH CENTRAL REFER TO TYPICAL PANEL DETAILS
01 31.05.21 RS AS CERTIFIED PROPOSED WAREHOUSE ADDITIONS FOR
G6 C15024 1500 -- 2 ROWS CPS 180 MAIN WIRES HORIZONTAL FOR ADDITIONAL REINFORCEMENT PE 08.05.21 RS ISSUED FOR TENDER NICHOLAS & ALEXANDER ARCHITECTS SOCCOBEL
designed: SP
_dca_�_,.--�R=s
PO 02.05.21 RS ISSUED FOR CLIENT PRESENTATION 37 Bevan Street, Albert Park, 3106 553 SOMERVILLE ROAD, SUNSHINE, VIC BRUCE YOUNG PARTNERS
NOTE: C - DENOTES STRAMIT C GIRT PC 14.04.21 RS PRELIMINARY ISSUE
Tel, 9696 5822
dravving title:
consulting structural and civil engineers _da_te:_�
M=•rc=•�2=
0f=
3
Fax, 9696 5833
Z - DENOTES STRAMIT Z GIRT PB 04.04.21 RS PRELIMINARY ISSUE Email, naarch@lbigpond.net.au
scale: 1:100 @ 81
project no· 13018
PA 08.03.21 RS PRELIMINARY ISSUE ACN 070 432 932 ELEVATIONS & SECTIONS
2 Small St. Hampton, Vic. 3188
Ph: 03 9521 8588 Fax: 03 9521 fl211 revision no· Of
ra , · by·
Email: byp@byp.com.au A.B.N. 78 005 39-1 758
dale- description:
drawing no: S04
'

CONCRETE FILL
BLOCKOUT. REFER TO
FOR BASE PLATE SIZE & H.D. TYPICAL DETAILS FOR BASE PLATE SIZE & H.D. 150
BOLTS REFER TO SCHEDULE BOLTS REFER TO SCHEDULE �
ON DRG. SOJ. BOLTS CAST N20 HAIRPIN WITH 1500 LONG LEGS. ON DRG. S03. BOLTS CAST CONCRETE FILL DOOR MULLION {BEYOND}
INTO FOOTING. 20 GROUT. SHEATH HAIRPINS WITH 50 DIA x INTO FOOTING. 20 GROUT. .. BLDCKOUT. REFER TO
REFER DRG. S01 FOR GROUT .... I 300 LONG POLYSTYRENE. REFER DRG, S01 FOR GROUT TYPICAL DETAILS
PRECAST PANEL---­ ENSURE REINFORCEMENT
REQUIREMENTS. REOUIREMENTS.
{BEYOND} BAR PARALLEL TO EDGE
- FLOOR SLAB AS -FLOOR SLAB AS OF SLAB IS NO MORE THAN
--

r
REFER TO DDJ JOINT DETAIL
IP-
I ON PLAN. I ON PLAN. 40mm FROM EDGE OF SLAB
FOR FURTHER INFORMATION
I T
I EXTERNAL RAMP no MAX

.. . ..
. --::- J
-,:
-. ..
... '�
l,l!IA 16,Uil.0:IW 11,ffi'IIICEf, Pit.

1
• 0 �
0 0 X
m m I. . 1'I I ,. •'I.. i ..,
I
-- --
>-
,_
,.
"'
V,

z -I-
w • • •
T . \ II 1111 'I l , / -:
"' =>
-
-,:
..
'
C>
0 w
I I I ' 3;0 + -+---3_0_0
-
llil, •·1-i, ,II· ·1 111,1;-, I.'"'
z �
.. \ 3-L11TM BTM
0
"'w
V,

I
/
i
------ ..
V, � ,-...--SF3 AS SCHEDULED
'
w ! ,, 'I I
,_ "'-PAD FOOTING PAD FOOTING I 'i!II I 111"1· ,I II ,I ,., !
+ +
--t--- -i- -----

0
"'
w AS SCHEDULED. AS SCHEDULED. • • • • I ·1: \ , r , I ]'. '' 'I i' ', I i 1 ''· '.
. . ' • . '. 1 .
z
.. •.
. ..

" ., • •

. .• +
• • •• • •
.. •
• • • 4
4
• • • 4

'i. FOOTING
'i. COLUMN
C

\_ 15 MPa MASS CONCRETE AS


'i. FOi ING
'i. co UMN
C

SECTION
PROVIDE POCKET FOR
REQUIRED TO FOUNDING LEVEL. DOWN PIPE
TYPICAL

REFER SCHEDULE REFER SCHEDULE

SECTION @ SECTION @ SECTION B-B


FOOTING F1 DETAIL FOOTING F3 DETAIL
�-- -. 'V'"- -, �- � FOOTING F2 DETAIL SIMILAR FOOTING F4 DETAIL SIMILAR
V ·v, • V V V ·v, V -".../- --�'V"---..,,/�---�----".../- --�'V"- --..,.../�---�----".../- --�'v"- --�---�"J V
-""
\
- . - v, - - .
' .
7
(

.. <<
'
l DOWN PIPE AS NOTED I

>
REFER BRIDGING .. . '

7
DETAIL ON DWG S07

'
--- R.C. PANEL
200
i---
PROVIDE POCKET FOR DOWN PIPE - I
I

7
150

<, rs
I' N12-200 VERTICAL & - DJACENT -
sl
�50 METAL TUBE POCKET GROUT IN DOWEL WITH 50 MPa ..
HORIZONTAL CENTRAL NDSCAPING FORMED IN PANEL MIN. NON-SHRINK GROUT.
EXTERNAL RAMP no MAX EXTERNAL RAMP no MAX '
\ I ...
( ,1----
'==-==.:;==� .!.';'==-==-I
., '

>
INTERNAL PAVEMENT

- --- * �ac--- '/ ,,· ______·· ·- _,.. ' . X


"'
J
"T ., _,..
EXTERNAL PAVEMENT
.. ...

I
-,: R20 DOWEL BAR x JOO LONG N16 PERIMETER BAR EACH

''
: ,--' -
V,

--t . :
w
."'
'
-,:
' ..
'
'600 Si -y >//
' ' •
//
< a. ONE EACH END OF PANEL SIDE OF GROUT TUBE I

<
0 -,:
l
-
>-
---
' 0
m > ,_ / EPOXY GROUT 150 INTO FOOTING ----

'> \<'
I

=t:=t:
.
' . • • • •

�� �
' ..
w
I II�

>(
.. I\'.
\
.

�,
' ' -,:.?
s �- • • • • 600
f I II

''
o ��- I .
,--STRIP FOOTING
.•
< ,_ w
I 0

- ( •. N12-600 CTS 400 ...


� N12-600 CTS 400 �+----20mm THICK GROUT FOR FULL a. J
. . �� PAD FOOTING
=.=.='..
=> '
�I
",_
I

,/ ,..,_
' 0 C>
°" TIE BARS. • • • • TIE BARS. LENGTH OF BEARING AT PAD "' I w
. AS SCHEDULED

I w -�
;;

<:
FOOTINGS AND CONTINUOUSLY
-----�----
• 'I-'
I
1, •
V,

<\
/' � " GROUT AT STRIP FOOTING
'
0 V,
• 4
, I '-- SF3 AS
....
0
? SF2 AS LOCATIONS WITH SO MPa MIN. � -,:
I\
f---- -- --- SCHEDULED SCHEDULED
, NON-SHRINK GROUT. PROVIDE

'> APPROVED LOAD BEARING SHIMS

@ L ________ _J
mER SCH�� REFER SCHEDULE AT ENDS. REFER DRG. S01 FOR
SECTION
GD
SECTION & )
<
SECTION GROUT REOUIREMENTS. ITYPICALI

(> /j TYPICAL PANEL TO FOOTING TYPICAL PAD FOOTING AT


�����������������-----=-='
INSTALL APPROVED SEALANT----
- __.A.__f..__
. A.__A.__/
AFTER SAWCUTTING SLAB.
- - -- SAWCUTTING SLAB. REFER TO SAWCUT DETAIL
DOWNPIPE LOCATIONS
REFER TO SAWCUT DETAIL DANLEY DIAMOND DOWELS INSTALLED TO --
MANUFACTURERS RECOMMENDATIONS AND
DANLEY PLATE DOWEL CRADLE SPECIFICATIONS EXCEPT AS NOTED. PROVIDE NOTE,
INSTALLED TO MANUFACTURERS NOTE, 1-N16 SUPPORT BAR WITH CHAIRS @I 600 CTS. • IT IS MOST IMPORTANT THAT NOTE:
RECOMMENDATIONS AND • IT IS MOST IMPORTANT THAT TO UNDERSIDE OF DOWEL CRADLE TO PREVENT APPROVED SEALANT ----­ R20 x 600 BARS AT 600 CRS. IN
THE SAWCUT IS LOCATED
SPECIFICATIONS EXCEPT AS NOTED. THE SAWCUT IS LOCATED MOVEMENT DURING CONSTRUCTION. CENTRALLY OVER THE DOWEL.
RECTANGULAR SLEEVES TO ALL LANDSCAPED AND PAVED AREAS
DRILL AND EPOXY GROUT DOWEL ALLOW LATERAL MOVEMENT.
CENTRALLY OVER THE DOWEL. • STOP ALL REINFORCEMENT 25mm BARS 300mm INTO EXISTING PLACE LONG SIDE HORIZONTAL. ARE TO FALL AWAY FROM BUILDING w
ENSURE REINFORCEMENT • STOP ALL REINFORCEMENT 25mm ENSURE REINFORCEMENT TO 30mm CLEAR OF JOINT. w w
-,: "'
BAR PARALLEL TO EDGE TO 30mm CLEAR OF JOINT. BAR PARALLEL TO EDGE SLAB. ALL PROJECTIONS DUE TO � z -,:
CROPPING ETC. ARE TO BE w J

---
OF SLAB IS NO MORE THAN OF SLAB IS NO MORE THAN RECTANGULAR SLEEVE
Vi �
APPLY BONDBREAKER TO JOINT 0 �
GROUND SMOOTH.

---- -
40mm FROM EDGE OF SLAB 40mm FROM EDGE OF SLAB FACE PRIOR TO SECOND POUR BASE PLATE 0

. FIRST POUR SECOND POUR EXISTING SLAB 200 45


- .
, f"I
, n Cl
\\ \\

\
NOTE, C>
X
X
L7
NOTE, TAPE ENDS OVER TO SLEEVE N12 BAR CONTINUOUS. TIE
THE CONTRACTOR SHALL CARRY OUT INTENSE HAND VIBRATION OF
CONCRETE UNDER AND AROUND THE PLATE DOWELS, TO ENSURE
THE CONTRACTOR SHALL CARRY OUT INTENSE HAND VIBRATION OF
CONCRETE UNDER AND AROUND THE DIAMOND DOWELS, TO ENSURE
TD STOP CONCRETE PENETRATION OFF N12 BAR & TOP REINF
AT EVERY SLEEVE
.
!!

COMPLETE COMPACTION OF THE CONCRETE. COMPLETE COMPACTION OF THE CONCRETE.

�[
SQUARE DOWELLED JOINT DETAIL T
x DEPTH OF CUT c 1/3 X DESIGNATED SLAB THICKNESS
DIAMOND DOWELLED JOINT DETAIL · IP SQUARE!
\\
'
PLATE DOWELLED JOINT DETAIL D.D.J. SQ.D.J. (NEW TO EXISTING) "' ·11
P.J. z
.=

TYPICAL COLUMN/MULLION
0
NOTE, PLATE JOINTS ARE TO BE SOFFCUT ON THE SAME DAY/NIGHT OF THE DANLEY DIAMOND DOWEL SPACINGS Imm) 0

SLAB POUR. THE TIMING OF SAWING IS CRITICAL, AND SHOULD COMMENCE AS � CAGE TO STEEL "
HOLDING DOWN (H.D.) BOLT CENTRES
0
SLAB THICKNESS {mm} 10mm DIAMOND DOWEL
lfil----- -
w
EARLY AS POSSIBLE BEFORE RANDOM CRACKING CAN OCCUR, BUT AFTER THE
CONCRETE HAS HARDENED SUFFICIENTLY TO PREVENT RAVELLING OR TEARING
"' FABRICATOR
0 DETAIL
OF THE SURFACE UNDER THE ACTION OF THE SAW. UP TO 150 600 w 150 UC/200 UC COLUMN
155 TO 175 600
FILLET WELD-W AT CORNER
DANLEY PLATE DOWEL SPACINGS Imm) (BOTH SIDES
180 TO 200 500 BOLT SIZE
SLAB THICKNESS Imm} 6mm PLATE DOWEL 10mm PLATE DOWEL
205 TO 225 400 COLUMN SIZE M24 H.D. BOLTS M20 H.D. BOLTS
UP TO 175 450 600
180 TO 200 JOO 500
230 AND ABOVE REFER TO DANLEY FOR GUIDANCE
lr sauAREI X y X y
205 TO 225 NIA 450 PLAN 250 UB 150 200
ELEVATION
230 AND ABOVE REFER TO DANLEY FOR GUIDANCE 310 UB, 360 UB,
TYPICAL COLUMN/MULLION 150 UC, 310 UC 200 200

SAW CUT IS TO BE FILLED


WITH AN APPROVED
SL72 MESH BTM x 800mm
WIDE TO FULL LENGTH OF
HOLDING DOWN (H.D.) BOLT DETAIL 410 UB, 460 UB 250 200
30mm DEEP SAW CUT IS TO BE FILLED - --- PROVIDE 35mm COVER TO
SEALANT. SLAB MESH IS TO SAW CUT. WITH AN APPROVED SEALANT. UPPER MOST WIRES OF TOP
SCALE, MO 530 UB 350 200
BE CUT THRU. MESH.
MINIMUM ANCHOR PLATE DETAILS MINIMUM 610 UB 450 250
xD

BOLT DIA
EMBEDMENT EDGE 01ST.
. -' - ,-- "-- - D B p T w E 700 WB, 800 WB 550 300
' ;- '
_.__
16mm 450 so 10 6 225 250 UC 350 350
20mm 450 so 12 6 300 150 SHS, 200 SHS,
300 300
THE TIMING OF SAWING IS CRITICAL, AND SHOULD COMMENCE AS EARLY AS 200 UC
POSSIBLE BEFORE RANDOM CRACKING CAN OCCUR, BUT AFTER THE CONCRETE
HAS HARDENED SUFFICIENTLY TO PREVENT RAVELLING OR TEARING OF THE 24mm 450 so 16 8 375
89 SHS, 100 SHS,
SURFACE UNDER THE ACTION OF THE SAW. THE TIMING OF SAWING IS CRITICAL, AND SHOULD COMMENCE AS EARLY AS 200 200
REFER TO CEMENT AND CONCRETE ASSOCIATION "INDUSTRIAL FLOORS AND POSSIBLE BEFORE RANDOM CRACKING CAN OCCUR, BUT AFTER THE CONCRETE 30mm 450 75 20 10 450 100 UC
PAVEMENTS" MANUAL SECTION 8.2 "SAWN JOINTS" FOR FURTHER ADVICE. HAS HARDENED SUFFICIENTLY TO PREVENT RAVELLING OR TEARING OF THE
0.2 0.1 0
SURFACE UNDER THE ACTION OF THE SAW. ALL HOLDING-DOWN BOLTS SHALL BE GRADE 4.6 IN ACCORDANCE 02 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
IN MILD WEATHER CONDITIONS {I.E. LOW TEMPERATURE, WIND AND SOLAR WITH AS1111 UNLESS NOTED OTHERWISE.
RADIATION} SAW CUTS MAY BE DELAYED UP TO 24 HOURS AFTER COMPLETION ie 1 to 2 HOURS AFTER COMPLETION OF THE FINAL SURFACE FINISH.
OF POUR. CONDITIONS OF HIGH SOLAR RADIATIONS FOLLOWED BY LOW Scale: 1:20 Metres
OVERNIGHT AIR TEMPERATURES SHOULD BE AVOIDED.
© Copyright Bruce Young Partners Pty. Ltd. 2020. This drawing shall not be �opied or modified in whole or in part without the prior written permission of Brute Young Partners Pty. Ltd
, DEPTH OF CUT • 1/3 X DESIGNATED SLAB THICKNESS project:

SAW CUT JOINT DETAIL SAW CUT JOINT DETAIL PROPOSED WAREHOUSE ADDITIONS FOR
S.C.J.
designed: SP
SOCCOBEL
S.C.J.
01 31.05.21 RS AS CERTIFIED NICHOLAS & ALEXANDER ARCHITECTS a
PD 08.05.21 RS ISSUED FOR TENDER 37 Bevan Street, Albert Park, 3106 553 SOMERVILLE ROAD, SUNSHINE, VIC BRUCE YOUNG PARTNERS �''=�='�· ---�R=s
Tel, 9696 5822
u, FOR 'CONVENTIONAL' SAWN JOINT OPTION FOR 'SOFF-CUT' SAWN JOINT OPTION PC 02.05.21 RS ISSUED FOR CLIENT PRESENTATION Fax, 9696 5833 dravving title:
consulting structural and civil engineers cc'a="c.' __,M.,a..,rcruhc.,2e,,Of""-3
scale: 1:20 @ 81
PB 24.04.21 RS PRELIMINARY ISSUE Email, naarch@lbigpond.net.au
ENSURE SAW CUTS EXTEND FOR ENSURE SAW CUTS EXTEND FOR FULL pcojecl w 13018
PA 04.04.21 RS PRELIMINARY ISSUE ACN 070 432 932 SLAB & FOOTING DETAIL 2 Small St_ Hampton, Vic. 3188
FULL LENGTH TO FACE OF WALLS LENGTH TO FACE OF WALLS - SHEET 1 Ph: 03 9521 8588 Fax: 03 9521 fl211 01
by·
revision no·
ra,· dale- description: Email: byp@byp.com.au A.B.N. 78 005 39-1 758
drawing no: S 05
500 MIN.
SLAB INFILL, F'ca40 MPa, N11 x 400 LONG DOWELS
SL81 TOP WITH 3S COVER. AT 300 MAX. CRS. DRILL
DEPTH OF SLAB TO AND EPOXY GROUT 100
MATCH EXISTING SLAB INTO EXISTING SLAB
ALL AROUND

EXISTING SLAB EXISTING SLAB

0
COMPACTED CRUSHED -�-V REINSTATE PLASTIC
ROCK BACKFILL MEMBRANE, FULLY
SHOWN HATCHED TAPE TO EXISTING
MEMBRANE ALL
AROUND

TYPICAL SLAB REINSTATEMENT DETAIL

1-N11 x 1500 LONG TOP - 1- N12 X 1500 LONG TOP

/;
OMIT IF PASSES THROUGH JOINT OMIT IF PASSES THROUGH JOINT

VERTICAL DOWNPIPE 50 LAGGING TO


WHERE REUUIRED. PIPE
300 SLAB REINFORCEMENT AS
j
(TYP) INDICATED ON PLAN.
<--- -
-PANEL

APPROVED SEALANT
+ FULL DEPTH
ABELFLEX OR FULL DEPTH ABELFLEX OR
APPROVED APPROVED EQUIVALENT
EQUIVALENT
EXTERNAL
WAREHOUSE PAVING SLAB
BLOCK OUT IN SLAB -BLOCK OUT IN SLAB
1 LAYER OF 'ABELFLEX' 1 LAYER OF 'ABELFLE X' 3N12 BARS BEAM
I I (TYPICAL!. a
REINFORCEMENT AS
DETAILED.
PIPE DIAMETER + 1100

N10 HAIRPINS x 1500mm TYPICAL SERVICES PENETRATION THROUGH TYPICAL CAULKING DETAIL
MINIMUM LONG EACH LEG
1-N12 x 1500 LONG TOP
FOOTING/EDGE THICKENING DETAIL
""�..,..
OMIT IF PASSES THROUGH
JOINT
___;,..__,_______---,,c__ "'
1-N11 x 1500 LONG TOP
�BLOCK OUT IN SLAB [OMIT IF PASSES THROUGH JOINT
1 LAYER OF 'ABELFLEX'

PROVIDE A 50mm DIAMETER


P.V.C. SLEEVE x 300mm
LONG CAST INTO CONCRETE
,___ BLOCK OUT IN SLAB _____,
1 LAYER OF 'ABELFLEX'

TYPICAL SLAB BLOCKOUT DETAILS

FOUNDATION

1-N11 x 1500 LONG BAR TOP.


OMIT IF BAR PASSES
THROUGH A JOINT. --- -�-BACKFILLED TRENCH
APPROVED WITH CONDITIONS
OR EXCAVATION
45 ° FOR CLAY
30° FOR SAND BUIILOlNG ACl
BUIILOtNG REGULATIONS
CRITICAL LINE
OF REPOSE BUILDING PE RM IT NO: 8S-U 1048/20132886/-0
DATE OF ISSUE: 3July2021
TYPICAL RE-ENTRANT CORNER DETAIL LIMITATION OF EXCAVATIONS
TYPICAL AT ALL LOADING DOCKS, DOCK
LEVELLERS AND ANY RE-ENTRANT CORNER
NEAR FOOTINGS

-,

CD

0.2 0.1 0 02 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

Scale: 1:20 Metres

© Copyright Bruce Young Partners Pty. Ltd. 2020. This drawing shall not be �opied or modified in whole or in part without the prior written permission of Brute Young Partners Pty. Ltd
project:
PROPOSED WAREHOUSE ADDITIONS FOR designed: SP
NICHOLAS & ALEXANDER ARCHITECTS SOCCOBEL
BRUCE YOUNG PARTNERS �''=�='·---�R�s
a
01 31.05.21 RS AS CERTIFIED 37 Bevan Street, Albert Park, 3106 553 SOMERVILLE ROAD, SUNSHINE, VIC
Tel, 9696 5822 consulting structural and civil engineers cc
da"""�'
_M,.,a'"rc""h'-'2"'0f"'-3
PC 08.05.21 RS ISSUED FOR TENDER Fax, 9696 5833 dravving title: scale: 1:20 @ 81
PB 01.05.21 RS ISSUED FOR CLIENT PRESENTATION Email, naarch@lbigpond.net.au
SLAB & FOOTING DETAIL pcoject w 13018
PA 24.04.21 RS PRELIMINARY ISSUE ACN 070 432 932 2 Small St_ Hampton, Vic. 3188

- SHEET 2 Ph: 03 9521 8588 Fax: 03 9521 fl211 revision no· 01


by·
ra,· Email: byp@byp.com.au A.B.N. 78 005 39-1 758
dale- description:
drawing no: S 06
� -�--200 x 16 x 200 PLATES WITH EAVES TIE AS
2 'U' BARS CAST INTO EACH SCHEDULED. NONPORITE NITOSEAL 215G - 2 LAYERS 100 X 10
PANEL. REFER TYPICAL CAST 15 x 15 x 8 EA CLEAT.
SEALANT OR EQUIVALENT. NONPORITE CELLOX-B JOINT SHOP WELDED TO
IN PLATE DETAIL J FILLER OR EQUIVALENT. COLUMN/MULLION
�----- 200 x 16 x 200 PLATES WITH
.' RC PANEL AS MEMBER AS 3 'U' BARS CAST INTO EACH
"
.. □ETAILED. SCHEDULED. PANEL. REFER TYPICAL
'.• '•• .. ,
,' ,. ,.
.>- ...
M20 BOLTS IN CAST IN Ex 1S x 10 x 140 CLIP
7
.

CAST IN PLATE DETAIL


•"

., .,

100 x 100 x 10 EA x 150 FERRULES AT CLIP SITE WELD TO STEELWORK. REFER TO TYPICAL ,,_____ MEMBER AS----­
6 CFW (SITE! TO CAST IN PLATES. LOCATIONS
1200mm MAX. CRS
l3 MIN. PER PANELi
(TYPICAL.I

J--- RC PANEL
_[: /
PANEL CLIP FOR DETAILS.

\
SCHEDULED.

ALL FERRULES TO HAVE AS DETAILED. NON FIRE RATED PANEL JOINT


N12 x 300 LONG TAILS �---150 x 12 x 350 PLATE
6 CFW (SITE) TO CAST IN PLATES.
f---:--c---:--";Ji==��-c--:----1

J .-----------;
TREMCO SEALANT OR
TYPICAL EAVES TIE EQUIVALENT TD ACHIEVE
REQUIRED FIRE RATING M20 BOLTS IN CAST-IN FERRULES
AT CLIP LOCATIONS.
L R[ PANEL
AS DETAILED.
SECTION b-b

f . · · _G
REFER TO TYPICAL FERRULE DETAIL.

1 f
TYPICAL PANEL CORNER DETAIL TO PANEL DETAIL REFER TO ELEVATIDNS FOR LOCATIONS.

TYPICAL PANEL TO STEELWORK


CLIP DETAIL
FIRE RATED PANEL JOINT
� �

100mm x 10mm 2-M20 TRUBOLTS 150 X 150 X 10 EA


GRADE 300 90 EMBEDMENT WITH N16 x 200 HOOKED
FLAT BAR 1 M20 FERRULE WITH N24 x PRECAST PANEL
600 LONG BAR. SO dia x 300 BAR CAST INTO PANEL
CAST IN FERRULE WITH
100 x 10 FL. GRADE 300
so
ASSOCIATED FITTINGS ANO LONG FOAM SLEEVE. ALL PANEL CLIPS SHALL BE MIN.
N12 CROSS BARS AND AN PANEL CLIP
N12 X 300 6 CFW !SITE) TO
FULLY WELDED IN
M20 GRADE 8.8 BOLT
LONG ACCORDANCE WITH DETAIL
UNLESS SPECIFICALLY
+ STEELWORK BOTH SIDES
REFER TO DETAILS FOR
DETAIL
FASTENER
f-- -c,.L---- COLUMN/RAKER ETC.
APPROVED BY THE ENGINEER
150 x 150 x 10 EA (LEAT
CROP BOTTOM FLANGE OF
100mm x 10mm � ET1 IF REQUIRED TO EXTEND
GRADE 300 [ 1SO x 10 EA CLEAT TO AVOID
•�--±--'l---J-�
C

FLAT BAR � PANEL JOINT


2-M20 TRUBOLTS TO 3-M20 8.8/S BOLTS TO ET1
155 EXISTING PANEL AT
TYPICAL PANEL CLIP DETAIL
2 M20 GRADE LOCATE 100mm CLEAR 200 PITCH AND
8.8 BOLTS 300 BELOW EAVES TIE 100 MIN EDGE 01STANCE WAREHOUSE PANEL BASE
90 EMBEDMENT
DETAIL AT MID SPAN
PANEL TO COLUMN CONNECTION TYPICAL EAVES TIE AT EXISTING
DETAIL -CN1 PANEL CONNECTION DETAIL - CN2 150 x 12 x 350 PLATE SITE -
(REFER TO ELEVATIONS FOR LOCATIONSI (REFER TO ELEVATIONS FOR LOCATIDNSI WELD TD CAST IN PLATES

96
81

'
N12 x 300 LONG TAIL BAR

� 200 x 16 x 200 PLATES WITH


3 'U' BARS CAST INTO
PANEL. REFER TYPICAL
l RAMSET M20 HEX FERRULE CAST IN PLATE DETAIL
OR APPROVED EQUIVALENT
No OF N16 PLATE THICKNESS /_/----v--�--........_,,,� ----v- ----v--�--........_,,,� ----v- --V--�✓--........_,,,� ----v- --V--�v-- 'V� ----v- --V--�v-- 'V� -�-\
GIRTS
PLATE DEPTH ·t·
UP TO 150 2 12
'U' BARS
( . .. ) TYPICAL PANEL / PANEL
160 - 200 2 16
210 - 300 16 .> \I TYPICAL FERRULE DETAIL CONNECTION
310 - 400 4 16
l
>
I
410 - 500 5 20 M16 FERRULES AT 900 CRS.
i
<
( 1SO x 8 EA GIRT SUPPORT
510 - 600 6 20 8 CLEAT PLATE /
610 - 100 1 20
> 6 CFW
\
110 - 800 8 20 2-M12 PURLIN BOLTS TO GIRTS
PLATE THICKNESS 't'
TYPICAL GIRT TO
N16 'U' BARS MAIN PANEL N16 'U' BARS
@l 100 CRS � REINFORCEMENT @l 100 CRS
FSBW TO PLATE FSBW TO PLATE
0

L
0

PLATE DEPTH
: BEAM DEPTH
+ 100 U.N.O.

2-N16 BARS TO ·1
l CAST IN PLATE
(LADDING
BRIDGING STRUT
EX 125 x 1S x B UA CROPPE
TO SUIT ARCH. DETAIL.
6 CFW TO 100 x 8 PLATE.
2-M12 PURLIN BOLTS TO GIR
� EXTEND 300mm AS SCHEDULED
PAST PLATE BOTH I
0

G IRT AS
0

ENDS sCHEDULED -
'

-r .. '" 5
..
AS SCHEDULED
/ w '; .. AS$0Cl�tlON
ELEVATION PLAN
FLOOR SLAB
. 1•,'.• • •
/

AS □ETAILED
/ BA SUILOltfG l!ERYICEt I'll.
TYPICAL CAST-IN PLATE DETAIL ,I APPROVED WITH CONDITIONS


d "/ ='.
7

' • • ..• •
r

BUILD!r-lGACT
NOTE:
r

BOLT TO � :c
,
BUILDmG REGULATIONS
IN FERRULE

"'u u"'
NEL.
REFER TO THE ELEVATIONS FOR PANEL 0

.' ' <(


BUILDING PERMIT NO: BS-U
THICKNESS AND REINFORCEMENT. TYPICAL.
1046120132886/0 DATE OF ISSUE: 3 July 2021
BRIDGING STRUT SUPPORT SECTION d-d <i
> DETAIL
)

�._./'.__.A.�A-._.A.._./'.__.A.._/.._.A.._./'.__.A.._/.._.A.._./'.__.A.._/.._.A.._./'.__.A.._/.._.A._./"
c,
CD

© Copyright Bruce Young Partners Pty. Ltd. 2020. This drawing shall not be �opied or modified in whole or in part without the prior written permission of Brute Young Partners Pty. Ltd
project:
PROPOSED WAREHOUSE ADDITIONS FOR
01 31.05.21 RS AS CERTIFIED
designed: SP

BRUCE YOUNG PARTNERS


SOCCOBEL
PD 08.05.21 RS ISSUED FOR TENDER
NICHOLAS & ALEXANDER ARCHITECTS drawn:

consulting structural and civil engineers


RS
37 Bevan Street, Albert Park, 3106 553 SOMERVILLE ROAD, SUNSHINE, VIC
PC 02.05.21 RS ISSUED FOR CLIENT PRESENTATION
Tel, 9696 5822 date: March 20f

PB 24.04.21 RS PRELIMINARY ISSUE


Fax, 9696 5833 dravving title: scale: 1:20 @ 81
Email, naarch@lbigpond.nel.au
PA 04.04.21 RS PRELIMINARY ISSUE
0.2 0.1 0 0.2 0.4 06 0.8 1.0 1.2 1.4 1.6 1.8 2.0
PRECAST PANEL DETAILS project no· 13018
Seate: 1:20 Metres
ACN 070 432 932 2 Small St. Hampton, Vic. 3188

ra,·
- SHEET 1 Ph: 03 9521 8588 Fax: 03 9521 fl211
Email: byp@byp.com.au A.B.N. 78 005 39-1 758
revision no· Of
dale- by· description:
drawing no: S07
C L. COLUMN [ L. COLUMN
PROVIDE 200 OF NON SHRINK 60 MPa
GROUT EACH SIDE OF SHIMS WITHIN
ITYP.I ITYP.I PROVIDE APPROVED 24 HOURS OF ERECTION OF PANELS - 1-N16 CENTRAL
LOAD BEARING SHIMS ITYPl[ALI
AT ENDS. (TYPl[AL)
I
7 7
I I
CAST-IN FERRULE
FOR CLIP.
1-N16 CORNER BAR 1-N16 CORNER BAR
EACH FACE W 1TH EACH FACE W1TH
600 x 600 LEGs 600 x 600 LEGs
ITYP.I ITYP.I 1-N16 CENTRAL

<C

tE tE
0
[AST-IN FERRULE "' [AST-IN FERRULE 1-N16 [ENTRAL 0

FOR PANEL [LIP FOR PANEL [LIP
I�
600 LAP N

300 300 ITYP I


I I

+ + + +
ITYP.I ITYP.I
1-N16 CORNER BAR
CENTRAL WITH
600 x 600 LEGS ljl
� PROP POINTS. REFER TO PROP POINTS. REFER TO ITYP.I
I.

. ..l ' .l 150 MIN.


PANEL PROPPING PANEL PROPPING R20 LOCATING PEG x 300 LONG
SCHEDULE FOR MAXIMUM SCHEDULE FOR MAXIMUM 100 MIN. IN �50 METAL TUBE POCKET
SPACING OF PROPS SPACING OF PROPS - 1-N16 CENTRAL
FORMED IN PANEL AT LOCATIONS
SHOWN TOP & BTM. REFER TO
PROVIDE APPROVED LOAD ELEVATIONS
BEARING SHIMS AT ENDS
PRIOR TO FULLY GROUTING
WITH 50 MPa GROUT.
ITYPl[ALI TYPICAL UPPER HORIZONTAL WALL PANEL
N12 x 1200 LONG
EACH FACE
I ' I 1-N16 EACH FACE
ADDITIONAL REFER TO SCHEDULE FOR THICKNESS
- -�k-

ITYPl[ALI
7'-;'.'
,, ' ·- & MAIN REINFORCEMENT

I I
\
1-N16 EACH FACE 1-N16 EACH FACE

I I
1-N16 EACH FA[E 1-N16 EACH FACE

1-N16 EACH FA[E


ADDITIONAL [ L. COLUMN [ L. COLUMN

, I \ \\\\ I---
, 1-N16 EACH FACE
ADDITIONAL
PROVIDE 200 OF NON SHRINK 60 MPa
GROUT EACH SIDE OF SHIMS WITHIN

i-¥,- -,,
PROVIDE APPROVED 14 HOURS OF ERECTION OF PANELS - 1-N16 CENTRAL

-
LOAD BEARING SHIMS (TYPICAL)
1-N16 EACH FACE 1-N16 EACH FACE


AT ENDS. !TYPICALI
ljl ljl I 1,1 I ljl I I
CAST-IN FERRULE

i- i- 1...1 FOR CLIP.

200 MIN. ,, I.
' ' '
150 MIN.
• R20 LOCATING PEG
x 300 LONG IN �50
METAL TUBE POCKET
200 MIN. ,, I.
' ' I'
150 MIN.
• R20 LOCATING PEG
x JOO LONG IN �50
METAL TUBE POCKET
1-N16 CENTRAL
PROVIDE APPROVED LOAD - 400 FORMED IN PANEL. PROVIDE APPROVED LOAD - 400 FORMED IN PANEL.
BEARING SHIMS AT ENOS REFER ELEVATIONS BEARING SHIMS AT ENOS REFER ELEVATIONS
(TYP.) (TYP.J <C
PRIOR TO FULLY GROUTING FOR LOCATIONS. PRIOR TO FULLY GROUTING FOR LO[ATIONS.
1/
0
WITH 50 MPa GROUT. WITH 50 MPa GROUT. 1-N16 CENTRAL 0

< 600 LAP N
AL 1

�-�/".�-����/'-.·�-/'-_���---A__-�,,A.·�_/''--���---A__-�,,A.·�-/'---A�--/'·..__�,,A.·�--/"----·A�_/'-..__�,,A.·�----/"----·A�_/'-..__�,,A.·�----/"----·A�_/'-..._,,/'-....�--/"----·A�_:: �-.A...--�--A�_/'-..._,,/'.....--/'-.....--A�_/'-..._,,/'.....--�-,,.A...�_/'-..._,,.A...--�-,,.A...-__..A...__,,.A...--�-,,) ITYP.I -1-M10 FERRULE MID SPAN


I I
TYPICAL VERTICAL WALL PANEL TYPICAL VERTICAL WALL PANEL 1-N16 CORNER BAR
REFER TYPICAL DETAIL

REFER TO SCHEDULE FOR THICKNESS WITH PENETRATION CENTRAL WITH


600 x 600 LEG s (+)
& MAIN REINFORCEMENT REFER TO SCHEDULE FOR THICKNESS ITYP.I
& MAIN REINFORCEMENT
200 MIN.
' ' I I. ,,I. 150 MIN. - 1-N16 CENTRAL

PROVIDE APPROVED LOAD -


BEARING SHIMS AT ENDS
PRIOR TO FULLY GROUTING
WITH 50 MPa GROUT.
(TYPICAL) TYPICAL BOTTOM HORIZONTAL WALL PANEL
REFER TO SCHEDULE FOR THICKNESS
& MAIN REINFORCEMENT

600 LAP - 1-N16 EACH FACE


ITYP.I

[AST IN PLATE FOR


1-N16 CORNER BAR
EACH FACE WITH
600 x 600 LEGS
+- - -
- - - - - - - - -
MAIN WIRES HORIZONTAL - --
WELDED CONNECTION
ITYPICALI
ITYP.J PROP POINT
0 0
1-N16 EACH FACE 0
� � 1-N16 EACH FACE

,
,./-"s_/--·--.......,,,----�--·-··v··-·· -
- 1-N16 EACH FACE
"s_/
----�--
f- 1 - N16 EACH FACE ADDITIONAL BARS \
\ BOTTOM TO SPANDREL PANELS U.N.O. I

\.__ "--�--/'.____/'._,"'.__�&
1

TYPICAL SPANDREL PANEL

®
REFER TO SCHEDULE FOR THICKNESS '
& MAIN REINFORCEMENT I

APPROVED WITH CONDITIONS


BUILDING ACJ
="
C
BUILDING REGULATIONS

BU.IILDING Pf RMIT NO: BS--\J


'1048/20132,&8610 DATE Of ISSUE: 3 July 2021

02U O 02 04 06 U U l2 l4 U U 2•

Scale: 1:20 Metres

© Copyright Bruce Young Partners Pty. Ltd. 2020. This drawing shall not be �opied or modified in whole or in part without the prior written permission of Brute Young Partners Pty. Ltd
project:
PROPOSED WAREHOUSE ADDITIONS FOR designed: SP
NICHOLAS & ALEXANDER ARCHITECTS SOCCOBEL _c �_,_. ---�R=s
01 31.05.1 RS AS CERTIFIED 37 Bevan Street, Albert Park, 3106 553 SOMERVILLE ROAD, SUNSHINE, VIC BRUCE YOUNG PARTNERS _d a
Tel, 9696 5822 consulting structural and civil engineers _da_te_, -�M=•=
rc=•�2==
0f3
PC 08.05.2 RS ISSUED FOR TENDER Fax, 9696 5833 dravving title: scale: 1:20 @ 81
PB 01.05.13 RS ISSUED FOR CLIENT PRESENTATION Email, naarch@lbigpond.net.au
PRECAST PANEL DETAILS pcoject w 13018
PA 14.04.13 RS PRELIMINARY ISSUE ACN 070 432 932 2 Small St_ Hampton, Vic. 3188

- SHEET 2 Ph: 03 9521 8588 Fax: 03 9521 fl211 revision no· 01


ra,· Email: byp@byp.com.au A.B.N. 78 005 39-1 758
dale- by· description:
drawing no: S 08
0 150x10 STRAP PLATE
8 CFW TO RAFTER
0 APPROVED WITH CONDITIONS
AISO(IAHON
1MSA BlUILIJlt(G SERVICES I'll.

6-MJO 8.8/S BOLTS

150x10 CAP PLATE 1-M24 8.8/S ERECTION BUILDING ACT


FSBW TO FLANGES BOLTS FOR FABRICATION BUILDING REGULATIONS
8 CFW TO WEB
REFER ELEVATIONS
BUILOlNG PERMIT NO: BS--U 104812-0 132886!0
00 500 DATf OF ISSUE: 3 July 2-021
-
----
--
-
- --=--� -=-- = -=--=--=-----=-----=- - ,- -

LJ_,-����F�==::=i=1 r·
'/

.
PURLIN AS NOTED

·f..--
I
)
_
_/

- _ l : �
G
-,,_

/
/ <(

\
STRUT AS DETAILED -----.I--II.-.U..L\aba"""""'

<
//\ 2; / .----- --"..-


✓ REFER TO ARCH

==
!REFER PLAN FOR LOCATION iL__0_1_',
o/
-\._)�I

[==- - ---- > & � ',


DETAILS FOR 75x10 FL
AND BRA9Nullµ-Af¼ ON RAKER, END PLATE TRUT SI AS SCHED.
---<>
0 ' FLASHING & SEALING 6 CFW TO SC1
DRAWING S101 \ ' 4
AND BOLTS. REFER
/\ & 'U' BENT PLATE
I\ L__0_1_',

>
!

>�
MEMBER SCHEDULE .llll-�i-..':::l:--END PLATE ON FAR
STRUT S1 AS NOTED RAFTER AS NOTED
'.... _/'_:,/ ON ELEVATION ON ELEVATION , '
P' SIDE TO BE CLEAR
g._ ..
·�_A.___.A__ __,/
1-M10 8.81S OF ERECTION BOLTS
REFER S10 FOR
- ERECTION BOLTS \
DETAILS m

UB HAUNCH FLYBRACE TO �____.A�___../"--_____..A.�--�----·A�___../"--_____..A.�--�----·A�___../"--_____..A.�__/


/ ' \&
(
::;-;
!REFER TO ELEVATIONS) CONNECT TO BOTTOM
'-,
,....--✓
01 \
6 FW HAUNCH TO RAFTER, FLANGE OF HAUNCH
DETAIL DETAIL -
GD &/
1o1v
I/ '!
WELD JOO AT ENDS THEN
MISS 150, HIT 150 !STAGGERED)
FOR CONNECTION DETAILS
REFER TO SECTION 1 ON
(·--v----✓-....,
, + >----+----+ REFER DETAIL 6 FOR \
'

\ 100xJO y{FFENER PLATE THIS SHEET 10 CLEAT PLATE


I
' . >
( CONNECTION
4
1WR4 STDES. FSBW TO 100x15 END PLATE 6 CFW TO Ml ,
FLANGES AND DOUBLER FSBW TO FLANGES, I 1-M10 8.8/S BOLTS DETAILS

> �<.
I <.
PLATE, 6 CFW TO WEB 6 CFW TO WEB
4-M14 8.8/S BOLTS
'-...__
·- TO SCJ
HI"--+---- EXISTING ADJOINING
BOTTOM
<l
�12 CLEAT PLATE

90x15 DOUBLER PLATE


- ' 6 CFWTO COL
l-M10 8.81S BOLTS
PANEL
<,
\
___,,,, EXISTING PC WALL
EACH SIDE OF COLUMN WEB ( OF ADJOINING
+--�•,�- +-
-
6 CFW TO FLANGES AND WEB \ BUILDING )
'---..___A._/__)

DETAIL DETAIL SECTION SECTION

0 l.
10 CAP PLATE
6 CFW
10 PLATE STIFFENER
FSBW TO FLANGES
1,,�
8 CFW TO WEB '
··-

EXISTING ADJACENT 150x150x10 EA PURLIN AS NOTED M1 AS


BUILDING xJOO LONG PURLIN AS NOTED SCHEDULED
- 1-M10 TRUBOLTS
AT 100 PITCH
REFER TYPICAL
RAKER TO PANEL
��-
I

4
ON EACH LEG OETAIL FOR CLIP AND
CLIP PANEL TO COLUMN :
V) ++c -�

>I
90 EMBEDMENT
0
10 BASE PLATE FERRULE DETAILS lr--r--{)fF
AT LOCATIONS SHOWN
0
RAKER, END PLATE STRUT S1 AS SCHED. TRUT S1 AS SCHED.
ON ELEVATIONS. REFER � AND BOLTS. REFER
6 CFW \
PRECAST DETAILS FOR �'I,
REFER TO DWG S10 F� ) RAKER AS
� MEMBER SCHEDULE
CLIP AND FERRULE -'-""'--'- '---END PLATE ON FAR SCHEDULED

-.
RAFTER DETAILS �(
SIDE TO BE CLEAR

\
DETAILS 1-M10 8.8/S ----...,/ _.A___A.___/',__/- T1 AS
OF ERECTION BOLTS 6 CFW STUB COLUMN 75x8 FLAT
ERECTION BOLTS SCHEDULED
REFER TYPICAL GIRT SC1 TO MULLION ALL
�I 10 PLATE STIFFENER PURLIN CLEAT
,_ ·, TO PANEL DETAIL ON AROUND !TYPICAL) (
/
FSBW TO FLANGES 6 CFW TO COL

Y
FLY BRACE AS
LOCATED ON ' //--
---v--
--
DWG S09
8 CFW TO WEB 1-M11 4.6/S
ELEVATIONS.
11 'U' BASE PLATE
6 CFW TO SC1 SECTION SECTION ....::;: PURLIN BOLTS

>&
) �
' , 10 NON-SHRINK
,
,'
t---+i!;=,=e\J ) GROUT

PRECAST PANEL
I �
SECTION SECTION SECTION
' 1-M10 8.8/S TRUBOLTS
GD
<l
·�- __A.___.A.
AT 150 PITCH
90 EMBEDMENT

EXISTING ADJOINING
DETAIL PANEL

SECTION

F
B
CIP AS SCHEDULED
ON S01 Ml AS SCHEDULED FLASHING TO PORTAL RAFTER AS
ARCH DETAILS DETAILED ON ELEVATIONS.
\ TYPICAL

,,,·�,1,======,,,
<
10 CLEAT PLATE
6 CFW TO ET1 GIRT AS SCHEDULED
1-M20 8.8/S BOLTS GIRT AS SCHEDULED i;-!l,-_·-,
150x11 PLATE
TO WBI
6 CFW TO OH! TOES

100x100x6 SHS EXISTING CANOPY


DM1 - --0
< > t
6 CFW TO EXISTING COLUMN & COLUMN
CIP AT TOP AND MID MEIGHT.
BOTH SIDES 65x65x6 EA FIXED TO
EACH WALL GIRT WITH M11 � ADDITIONAL GT GIRT � ADDITIONAL G1 GIRT
NOTE, CIP AND CLIPS TO BE PURLIN BOLT FOR TRANSITION OF FOR TRANSITION OF
HOT-DIP GALVANISED & COLD TO PROVIDE SUPPORT FOR SHEETING SHEETING
GAL AFTER WELDING FLASHING. 10 CLEAT PLATE WITH
FLASHING TO ARCH 1-M10 8.8/5 BOLTS
DETAILS IN 75 LONG VERTICALLY

SECTION SECTION DETAIL DETAIL SLOTTED HOLES

MULLION M1 AS OETAILED.

INTERNAL MULLION M1 TO
PORTAL RAFTER
CONNECTION DETAIL
02U O 02 04 06 U U l2 l4 U 1.8 2.0

Scale: 1:20 Metres

© Copyright Bruce Young Partners Pty. Ltd. 2020. This drawing shall not be �opied or modified in whole or in part without the prior written permission of Brute Young Partners Pty. Ltd
project:
PROPOSED WAREHOUSE ADDITIONS FOR designed: SP
01 31.05.21 RS AS CERTIFIED NICHOLAS & ALEXANDER ARCHITECTS SOCCOBEL
BRUCE YOUNG PARTNERS =''=�='�· ---�R�s
a
PD 08.05.21 RS ISSUED FOR TENDER 37 Bevan Street, Albert Park, 3106 553 SOMERVILLE ROAD, SUNSHINE, VIC
Tel, 9696 5822 consulting structural and civil engineers cc8'cc"c.' __,M,.a.,rca,h.,2e,,Of,,,_3
PC 01.05.21 RS ISSUED FOR CLIENT PRESENTATION Fax, 9696 5833 dravving title: scale: 1:20 @ 81
PB 14.04.21 RS PRELIMINARY ISSUE Email, naarch@lbigpond.net.au
STEEL FRAMING DETAILS 2 Small St. Hampton, Vic. 3188
pcoject w 13018
PA 04.04.21 RS PRELIMINARY ISSUE ACN 070 432 932
- SHEET 1 Ph: 03 9521 8588 Fax: 03 9521 fl211 revision no· 01
ra,· Email: byp@byp.com.au A.B.N. 78 005 39-1 758
dale- by· description:
drawing no: S 09
BRACING CONNECTION SCHEDULE {MINIMUM

-_
REQUIRED!
RAKER AS SCHED. RAKER AS SCHED. RAKER AS SCHED. RAKER AS SCHED.
BRACE SIZE BOLTS GUSSET PL. WELDING
E48xx ELECTRODES
END PLATE AND BOLTS END PLATE AND BOLTS JIN STRAIGHT LINE! GRADE 250
AS SCHEDULED AS SCHEDULED CATEGORY SP
ci ci MINIMUM TOTAL
w ci w ci x"' x SIZE
WELD LENGTH lmml
�I
WEB CLEAT. REFER WEB CLEAT. REFER et: WEB CLEAT. REFER �WEB CLEAT. REFER
I
w w z z
et: w r STRUT AS SCHED.
<(
STRUT AS SCHED.
I
"'
,'

~
,'

~
MEMBER SCHEDULE w MEMBER SCHEDULE V,
MEMBER SCHEDULE w MEMBER SCHEDULE :,: :,:
V, V, V, V, 0
0
0
0 75 x 75 x 5 EA 1-M10 8.8/S 75 x 10 PLATE 6 CFW 100
"' "'
�I
V, V, a' a'

I
NOTE, STRUT MAY BE >- NOTE, STRUT MAY BE 75 x 75 x 6 EA 3-M10 8.8/S 100 x 10 PLATE 6 CFW 230
"' ANGLED IF REQ'D TO "'>-
=:,
ANGLED IF REQ'D TO
>-
"'
=:, 75 x 75 x 8 EA 3-M10 8.8/S 130 x 10 PLATE 6 CFW 290

-
e
>-
V,
SUIT CORNER MULLION V,
SUIT CORNER MULLION >-
V, 75 x 75 x 10 EA 4-M20 8.8/S 150 x 10 PLATE 6 CFW 340
CLEAT PLATE CLEAT PLATE AND
u..J
AS SCHEDULED SINGLE ROW OF BOLTS ...J 90 x 90 x 6 EA 1-M14 8.8/5 130 x 10 PLATE 8 CFW 210
AS SCHEDULED z 90 x 90 x 8 EA 3-M24 8.8/S 130 x 12 PLATE 8 CFW 270
PFC RAKER AT CORNER MULLION PFC RAKER AT MULLION UB RAKER AT CORNER MULLION UB RAKER AT MULLION <( 90 x 90 x 10 EA 4-M24 8.8/S 150 x 12 PLATE 8 CFW 310
...J
<(
100 x 100 x 6 EA 3-M14 8.8/S 130 x 10 PLATE 8 CFW 140
END WALL RAKERS WITH NO ROOF BRACING u..J
100 x 100 x 8 EA 3-M14 8.8/5 150 x 11 PLATE 8 CFW 300
CLEAT AND BOLTS 100 x 100 x 10 EA 4-M24 8.8/S 180 x 12 PLATE 8 CFW 360
AS SCHEDULED 100 x 100 x 12 EA 5-M14 8.8/S 180 x 16 PLATE 8 CFW 440
150 MAX. 150 MAX. 150 MAX. 250 MAX. 125 x 125 x 8 EA 4-M24 8.8/S 180 x 12 PLATE 8 CFW 390
125 x 125 x 10 EA 5-M24 8.8/S 180 x 16 PLATE 8 CFW 460
60 MAX. 60 MAX. 60 MAX 60 MAX.
"-' r 100 X 75 X 6 UA 3-M10 8.8/S 130 x 10 PLATE 8 CFW 210
END PLATE. REFER NOTCH FLANGE OF END PLATE. REFER NOTCH FLANGE OF END PLATE. REFER NOTCH FLANGE OF END PLATE. REFER ...J "'
ci l!J =:, 100 x 75 x 8 UA 3-M14 8.8/S 130 x 12 PLATE 8 CFW 160
MEMBER SCHEDULE MULLION IF REQ'D FOR MEMBER SCHEDULE MULLION IF REQ'D FOR MEMBER SCHEDULE MULLION IF REQ'D FOR MEMBER SCHEDULE w Z�-
BRACE INSTALLATION BRACE INSTALLATION BRACE INSTALLATION w <( r w 100 x 75 x 10 UA
>-
"' 3-M14 8.8/S 150 x 11 PLATE 8 CFW 310
END PLATE. REFER 10 PLATE WEB 10 PLATE WEB END PLATE. REFER 10 PLATE WEB 10 PLATE WEB V, 1-M10 8.8/S ...J D 7
MEMBER SCHEDULE STIFFENER, 6 CFW STIFFENER, 6 CFW MEMBER SCHEDULE STIFFENER, 6 CFW STIFFENER, 6 CFW "'
V,
BOLT w
<( >- z
::) W 0
"' 125 x 75 x 6 UA 3-M14 8.8/S 130 x 10 PLATE 8 CFW 240
z
d �....J
125 X 75 X 8 UA 3-M14 8.8/S 150 x 12 PLATE 8 CFW 300
:,: WALL BRACING
"'
=:, u..J z
zo 125 x 75 x 10 UA 4-M24 8.8/S 180 x 12 PLATE 8 CFW 360
RAKER AS SCHED. RAKER AS SCHED. RA ER AS SCHED. RAKER A SCHED.
w CROSSING :::, 125 x 75 x 12 UA 5-M24 8.8/S 180 x 16 PLATE 8 CFW 440
FFL FFL
CLEAT AND BOLTS 16 DIA. ROD 1-M10 8.8/S 75 x 10 PLATE 6 CFW 200
c::,
" AS SCHEDULED CLEAT AND BOLTS CLEAT AND BOLTS D 20 DIA. ROD 1-M10 8.8/S 75 x 10 PLATE 6 CFW 100
ci ci ci -1 ,i, AS SCHEDULED ci I AS SCHEDULED ci
�-
, Gr<" R-"' 24 DIA.ROD 1-M10 8.8/S 75 x 10 PLATE 6 CFW 200

I� I�
w w

I "' I "' I
w w
I I et: ' 'Q
I
w 61' w 90 x 90 x 10 EA WITH 16 END [LEAT PLATE AND SINGLE ROW
5:,v"- NOTE - GUSSET PLATE LENGTH TO BE KEPT TO A MINIMUM.
"o "' "'
V,
1'oo 1'oo PLATE, 6 CFW TO COLUMN ANO OF BOLTS AS SCHEDULED.
-10 ,t
I I I 1;"'
V, V, V,
61'

I�"'
61'
I I
V, V,

"' I "' I
61'
NOTE, STRUT MAY NOTE, STRUT MAY
-10 NOTE, STRUT MAY NOTE, STRUT MAY
-10 -10
BASE PLATE AND EXTENDED [LEAT TO BE WELDED TO - PROVIDE FSBW WHERE MINIMUM LENGTH CAN'T BE ACHIEVED.
I ,,;�- ,.,,
t; t; �- t; TO ENSURE BRACING, NUT AND COLUMN AND BASE PLATE AND
I
BE ANGLED IF "' BE ANGLED IF BE ANGLED IF BE ANGLED IF <'o
WASHER ARE CLEAR OF FLOOR EXTENDED TO ENSURE BOLTS
REQ'D TO SUIT >- REQ'D TO SUIT SLOTTED HOLE TO >-
V, SLOTTED HOLE TO REQ'D TO SUIT >-
<Y REQ'D TO SUIT >- SLOTTED HOLE TO y<"-1� >-
V, SLOTTED HOLE TO
STRUT CONNECTION SCHEDULE
V, V, V,
CORNER MULLION CORNER MULLION SUIT UNIVERSAL WIND SUIT UNIVERSAL WIND CORNER MULLION 'V CORNER MULLION SUIT UNIVERSAL WIND -9 SUIT UNIVERSAL WIND ARE CLEAR OF FLOOR {MINIMUM
BRACING BRACKET BRACING BRACKET BRACING BRACKET BRACING BRACKET REQUIRED!

PFC RAKER AT CORNER MULLION PFC RAKER AT CORNER MULLION PFC RAKER AT MULLION UB RAKER AT CORNER MULLION UB RAKER AT CORNER MULLION UB RAKER AT MULLION TYPICAL WALL BRACING DETAILS STRUT SIZE BOLTS END PLATE WELDING
GRADE 150 E48xx ELECTRODES

END WALL RAKERS WITH ROOF BRACING CLEAT SLOTTED INTO CLEAT SLOTTED INTO
076 to 0114
0139 to 0168
4-M16 8.8/S BOLTS
4-M20 8.8/S BOLTS
10 PLATE
12 PLATE
6 CFW
6 CFW
STRUT AND BOLTS STRUT AND BOLTS 0119 4-M24 8.8/S BOLTS 12 PLATE 6 CFW
AS SCHEDULED AS SCHEDULED 0273 4-M24 8.8/S BOLTS 16 PLATE 6 CFW

& &
ci ci
CLEAT AND BOLTS SLOTTED HOLE TO CLEAT AND BOLTS SLOTTED HOLE TO w w STIFFENERS MAY BE OFFSET CLEAT AND BOLTS REFER RIDGE STRUT

&
et: et:
AS SCHEDULED SUIT UNIVERSAL AS SCHEDULED SUIT UNIVERSAL w w FROM COLUMN FLANGES AS AS SCHEDULED CONNECTION SCHEDULE

�"�-
V, V,

&
WIND BRACING WIND BRACING -11,; -11,; SHOWN IF REQUIRED FOR
"' "' � "' "' �
'Q 'Q
D
NOTE: STEEL SHOP DETAILER TO CO-ORDINATE WITH
V, V,
R-
"'
-11,; BRACKET BRACKET �<"6 1i'(f �<"61' 1i'(f INSTALLATION OF STRUT w
r

& & I�
>- >-

�I I� I�
ci ci 'Q
ci -11,; ci w

I�
R-"' f1 "'
�<""'1'
1' =:, V,
SPRINKLER CONTRACTOR PRIOR TO COMMENCING
-tv
'Q
�<""'1' -10 "'{0
"
�<:J

�-
&'v / R-"' R-"'{f SHOP DETAILS TO ENSURE REQUIREMENTS ARE MET.
"'{0
� I

�I I� "'{0
I� S> ...._,;:sf1
�·
'Q 'Q
"' "'
x, .....
�f1
ALLOW FOR AS2118 SPRINKLERS.
'
<f',/
' « x'>
CLEAT AND BOLTS CLEAT AND BOLTS �<:J
x
x'>
,,_ V
� I !

�I I� I�
=:, =:, =:, =:,
AS SCHEDULED AS SCHEDULED
½/,
/.
':S
,v
� I RAFTER AS SCHED. RAFTER AS SCHED. ':S NOTE,
ALL BRACING AND COLUMN/RAFTER INTERSECTIONS
ARE TO BE LOCATED SO AS TO INTERSECT OR BE
RAFTER AS SC D. RAFTER AS SCH D. RAFTER S SCHED. 10 PLATE PLACED AS CLOSE AS PRACTICABLE DUE TO
ci' ci STIFFENER, CONSTRUCTION CONSTRAINTS.
w
r, 10 PLATE WEB w 10 PLATE WEB CHS STUB TO BE 6 CFW SLOTTED HOLE TO 10 PLATE WEB

"'<i'
END PLATE AND BOLTS END PLATE AND BOLTS WHERE STRUT SIZES W' STIFFENER, 6 CFW et: STIFFENER, 6 CFW WEB STIFFENERS ONE SIZE DOWN SUIT UNIVERSAL STIFFENER, 6 CFW
V,
AS SCHEDULED AS SCHEDULED VARY, ENSURE BOLT V, OVER COLUMN FROM NOMINATED MAX. MAX. WINO BRACING
100 MIN. 100 MIN. HOLES SUIT LARGER 60 MAX. V,
60 MAX. STRUT DIAMETER OFFSET OFFSET BRACKET 60 MAX. FSBW
>-• >-
DIAMETER STRUT =:,•
er:::
>-
V,
115 MAX, "'
=:,
>-
115 MAX. WEB STIFFENERS 150 MAX. CLEAT PLATE
V,
OVER COLUMN SLOT LENGTH
100 MIN. 100 MIN. +
+
PORTAL RAFTER AT COLUMN PORTAL RAFTER AT COLUMN PORTAL RAFTER AT STRUTS PORTAL RAFTER AT STRUTS PORTAL RAFTER OVER COLUMN STRUT STUB OPTION RAFTER STIFFENER VARIATION STRUT AT BOLTED RIDGE +
+I
MAY BE USED WHEN THERE IS MAY BE USED WHEN THERE IS VERTICAL CLEATS AS SHOWN MAY ONLY +
PORTAL RAFTER WITH ROOF BRACING ON ONE SIDE INSUFFICIENT CLEARANCE BETWEEN
RAFTER WEB STIFFENERS
INSUFFICIENT CLEARANCE BETWEEN
RAFTER WEB STIFFENERS
BE USED WHEN THERE IS NO POSSIBILITY
OF USING STRUT END PLATES +
STRUT AS SCHED.

6mm SEAL PLATE BOTH


++ SIDES OF CLEAT PLATE,
6 CFW ALL AROUND
SLOTTED HOLE TO CLEAT AND BOLTS CLEAT PLATE WITH 55 MAX. 55 MAX.

&
SUIT UNIVERSAL AS SCHEDULED SINGLE ROW OF BOLTS

�"�-
WIND BRACING AS SCHEDULED
R-"' BRACKET 6 CFW

�I �I
ci 'Q
ci
f1 "'
�<:J
1'oo
61' R-"'
& RIDGE STRUT CONNECTION SCHEDULE
�I �I
'Q

1i'
"'
CLEAT AND BOLTS CLEAT AND BOLTS -10 CLEAT AND BOLTS -- SPRINKLER RANGE PIPE w
w SPRINKLER RANGE PIPE w
. w
STRUT SIZE SLOT LENGTH CLEAT PLATE BOLTS
�I �I
=:,
/. X AS SCHEDULED AS SCHEDULED AS SCHEDULED zz
"' - "'
zz
"'
x
<'v.
x /4 0
,' "'"' 0 "'
,::
RAFTER AS SCHED. RAFTER AS SCHED. RA TER AS SCHED. " " " ' ' ' " '
7
w
- 7
Ow 0114, 0139 100mm 10 PLATE, 6 CFW 1-M10 8,8/S
1:,:1 w 1:,:1 w 0168 100mm 12 PLATE, 6 CFW 1-M24 8.8/S
--
<7
I,I PURLIN AS NOTED •7 I I PURLIN AS NOTED
0119 150mm 16 PLATE, 8 CFW 3-M24 8.8/S
RAFTER 0173 200mm 20 PLATE, 8 CFW 3-M30 8.8/S
10 PLATE WEB ROD
-
/I
..... .....

END PLATE AND BOLTS END PLATE AND BOLTS END PLATE AND BOLTS ()
STIFFENERS, BRACING
AS SCHEDULED AS SCHEDULED 6 CFW AS SCHEDULED STRUT AS SCHED. STRUT AS SCHED. ANGLE BRACE
AND BOLTS AS
SCHEDULED
100 MAX. VERTICAL 115 MAX. STRUT AS END PLATE
CENTRES BETWEEN SCHEDULED AND BOLTS AS
ROD BRACING SCHEDULED
100 MIN.

PORTAL RAFTER AT COLUMN PORTAL RAFTER AT COLUMN PORTAL RAFTER AT STRUTS PORTAL RAFTER AT STRUTS ROOF BRACING CROSSING TYPICAL STRUT ENO PLATE ELEVATION OF STRUT TO RAFTER ELEY ATION OF ROOF BRACING TO RAFTER
MAY BE USED WHEN OTHER END OF ROD
IS FIXED AND UNABLE TO BE TENSIONED

PORTAL RAFTER WITH ROOF BRACING ON BOTH SIDES


ASIOCIAIION
STRUT, END PLATE
w w w w AND BOLTS AS t.!BA, BIJ!Ul!NG �S M.
. w . w . w . w
zz zz zz zz
-« SCHEDULED
:,:
0 <(
"' -
:,:"'
0 <(
<( -
0 "'
:,: "'
<( -
:,:
0 "'
<(
"' APPROVE0WITH CONDITIONS
ow Ow Ow Ow
"ft -7
w "fl-
-7
w "fl- - -
-7
w "fl-
-7
w
I I PURLIN AS NOTED 1 I PURLIN AS NOTED I I PURLIN AS NOTED 1 I PURLIN AS NOTED BUILDING ACT
'[10015 TRIMMER
;j'IXED TO EACH
--ifri�T1ll�=-_
=�=� =�=�=
_ �=�=-==j
BUILDING REGULATIONS
�---+
�URLIN (TYPICAL! BUILDING PERMIT llO: BS-U 1048/2013288610
"11AKER, END PLATE STRUT AS SCHED. RAKER, ENO PLATE STRUT AS SCHED. RAKER, END PLATE STRUT AS SCHED. RAKER, END PLATE STRUT AS SCHED. DATE OF ISSUE: 3July2021
"'AND BOLTS. REFER AND BOLTS. REFER AND BOLTS. REFER AND BOLTS. REFER
-'tiEMBER SCHEDULE MEMBER SCHEDULE MEMBER SCHEDULE MEMBER SCHEDULE 2-M20 8.8/S
� STRUT AS ERECTION BOLTS
~ END PLATE ON FAR END PLATE ON FAR END PLATE ON FAR END PLATE ON FAR END PLATE STRUT, END PLATE
,;2-M10 8.8/S SIDE TO BE CLEAR 1-M10 8.8/S SIDE TO BE CLEAR 1-M10 8.8/S SIDE TO BE CLEAR 1-M20 8.8/S SIDE TO BE CLEAR SCHEDULED AND BOLTS AS AND BOLTS AS END PLATE ON FAR END PLATE ON FAR 2-M20 8.8/5
8'RECTION BOLTS OF ERECTION BOLTS ERECTION BOLTS OF ERECTION BOLTS ERECTION BOLTS OF ERECTION BOLTS ERECTION BOLTS OF ERECTION BOLTS SCHEDULED SCHEDULED SIDE TO BE CLEAR SIDE TO BE CLEAR ERECTION BOLTS
OF ERECTION BOLTS OF ERECTION BOLTS

PFC RAKER UB RAKER UB RAKER UB RAKER STRUT TO MULLION STRUT TO SHALLOW RAFTER STRUT TO DEEP RAFTER
ALL BRACE COMBINATIONS ANGLE/ROD BRACING ANGLE/ANGLE BRACING ROD/ROD BRACING
0 100 MIN.
�,--+�-- RAKER AND STRUT END PLATE ELEY ATIONS

n
CLEAT AND BOLTS D STRUT AS
w
AS SCHEDULED C)c,,-,1
SCHEDULED

"'
V,
V, 100 MIN. 100 MIN.
0.2 0.1 0 02 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
>-
RAKER RAKER
� I
V, Scale: 1:20 Metres
CLEAT AND BOLTS
AS SCHEDULED

w
CAST IN PLATE ____, © Copyright Bruce Young Partners Pty. Ltd. 202 . This drawing shall not be �opied or modified in whole or in part without the prior written permission of Brute Young Partners Pty. Ltd
project:
1-----, CHED. �

--= + 6 CFW {SITE WELD!


F'7,,=-4-���i3o,;;,F,�4 RAKER TD CAST IN PROPOSED WAREHOUSE ADDITIONS FOR designed: SP
'i. PRECAST PANEL 0 PLATE {TYPICALI NICHOLAS & ALEXANDER ARCHITECTS SOCCOBEL _c �_,_. ---�R=s
01 31.05.21 RS AS CERTIFIED 37 Bevan Street, Albert Park, 3106 553 SOMERVILLE ROAD, SUNSHINE, VIC BRUCE YOUNG PARTNERS _d a
6 CFW !SITE WELDI MIN. 1-M20 TRUBOLTS, Tel : 9696 5822 consulting structural and civil engineers _da_te_, -�M=•=
rc=•�2==
0f3
90 EMBEDMENT. PC 08.05.21 RS ISSUED FOR TENDER Fax: 9696 5833 dravving title:
PRECAST CAST-IN PLATE END PLATE AS STRUT END PLATE scale: 1:20 @ 81
PANEL AS SCHEDULED SCHEDULED TO CAST IN PLATE FOR ERECTION PB 01.05.21 RS ISSUED FOR CLIENT PRESENTATION Email, naarch@lbigpond.net.au
PURPOSES ONLY pcoject w 13018
PA 24.04.21 RS PRELIMINARY ISSUE ACN 070 432 932 TYPICAL BRACING DETAILS
2 Small St_ Hampton, Vic. 3188

STRUT/RAKER AT PRECAST PANEL SECTION A-A ra , · by·


Ph: 03 9521 8588 Fax: 03 9521 fl211
Email: byp@byp.com.au A.B.N. 78 005 39-1 758
revision no· 01
dale- description:
drawing no: S 10
PURLIN LAP BOLTS
NOTE, 1-M12 4.6/S PURLIN BOLT
� FLY BRACE AS IN TOP WEB HOLE & 1-M12 4.6/S LAPPED AS NOTED LAPPED AS NOTED PURLIN CLEAT TOP OF
LOCATED ON AS SCHEDULED STEEL BEAM
ELEVATIONS PURLIN BOLT IN LOWER FLANGE
ITYP. AT BOTH ENOS OF LAP) 6 CFW TO BEAM
PURLIN LAP PURLIN CLEAT PURLIN LAP PURLIN LAP PURLIN [LEAT PURLIN LAP PURLIN CLEAT PURLIN [LEAT
B [LEAT PLATE '
BOLTS REFER SCHEDULE BOLTS BOLTS REFER SCHEDULE BOLTS REFER SCHEDULE REFER SCHEDULE
2-M11 4.6/S
PURLIN BOLTS "
6 CFW TO ANGLE '
1-M16 TRUBOLT TO PANEL
,____j\____j\____J,

I PURLIN AS NOTED PURLIN AS NOTED PURLIN AS NOTED


. + +

50 X 50 X 5 EA AT 45 ° 50 X 50 X 5 EA AT 45 ° PURLIN CLEAT SCHEDULE


1-M12 8.8/S PURLIN 1-M12 B.B/S PURLIN
50x50x5 EA AT 45 °
FLYBRACE BOLT 6 CLEAT PLATE --- 1-M12 8.8/S PURLIN BOLT EACH END BOLT EACH END DISTANCE 'D' CLEAT SIZE
so X so X 5 EA AT 45 ° NOTE, THIS IS AN 6 CFW TO RAFTER BOLT EACH END 50 X 50 X 5 EA AT 45° (TYPICAL) (TYPICAL)
8 CLEAT PLATE ---; 1-M12 8.B/S PURLIN ADDITIONAL BOLT TO 1-M12 8.8/S PURLIN LESS THAN 10 15x8 FLAT
6 CFW TO COLUMN PURLIN LAP BOLTS !TYPICAL) 6 CLEAT PLATE ---J, 6 CLEAT PLATE 6 [LEAT PLATE
BOLT TO COLUMN BOLT EACH END 6 CFW TO RAKER 6 CFW TO RAKER
6 CFW TO RAFTER ITYPICALI 10 TO 90 15x10 FLAT
PRECAST PANEL COLUMN TYPICAL PURLIN BOLTING DETAILS COLUMN OR RAFTER HAUNCH GREATER THAN 90 75x75x5 EA
1'10
RAFTER WITH HAUNCH UB RAKER PFC RAKER
NOTE: FLYBRACE BOLT TYPICAL PURLIN CLEAT DETAIL
IS AN ADDITIONAL BOLT
TO PURLIN LAP BOLTS TYPICAL ROOF & WALL FLY BRACE DETAILS

-50x50x5 EA WITH -50x50x5 EA WITH


6 END PLATES 6 END PLATES
1-M11 PURLIN BOLTS 1-M12 PURLIN BOLTS
300 1000 EACH END EACH END

'
1000 --
-
---·- ·- � ....--
-- ,;·
...
I---·- ·-
·

.;-----
...
7

--
_l-::::·.-= · __-_-- ,·-,-- �������--=-....-:-,------
- --- .........
--
- -- --
-- - -BRIDGING STRUT -
----- --
-I
. :-,--·

=--- -- -- - ....
__
-
-BRIDGING STRUT -

,7

,'
DOUBLE PURLIN RIDGE PURLIN

TYPICAL PURLIN & GIRT CONNECTIONS


PURLINS & GIRTS ARE TO BE CONNECTED TO THE FRAME BY
Bmm CLEAT PLATES, 6mm C.F.W. & 1-M11 4,6/S PURLIN BOLTS
SHEETING SPLICE DETAIL ALL IN ACCORDANCE WITH THE MANUFACTURER'S STANDARD
SPECIFICATIONS AND DETAILS UNLESS NOTED OTHERWISE

l.fflA llill!LOll(G IB!Wla:S m.


APPROVEDWITH CONDITIOHS
BUILDING ACT
BUILDING REGULATIONS
BUILDING PE RJ.IIT NO: BS-U 1048120·132&8610
DATE OF ISSUE: 3 July 2021

C
00

02U O 02 04 06 U U 12 14 U U 2•

Scale: 1:20 Metres

© Copyright Bruce Young Partners Pty. Ltd. 2020. This drawing shall not be �opied or modified in whole or in part without the prior written permission of Brute Young Partners Pty. Ltd
project:
PROPOSED WAREHOUSE ADDITIONS FOR designed: SP
NICHOLAS & ALEXANDER ARCHITECTS SOCCOBEL _c �_,_. ---�R=s
01 31.05.21 RS AS CERTIFIED 37 Bevan Street, Albert Park, 3106 553 SOMERVILLE ROAD, SUNSHINE, VIC BRUCE YOUNG PARTNERS _d a
Tel, 9696 5822 consulting structural and civil engineers _da_te_, -�M=•=
rc=•�2==
0f3
PC 08.05.21 RS ISSUED FOR TENDER Fax, 9696 5833 dravving title: scale: 1:20 @ 81
PB 02.05,21 RS ISSUED FOR CLIENT PRESENTATION Email, naarch@lbigpond.net.au
ROLLER SHUTTER DOOR & pcoject w 13018
PA 14.04.21 RS PRELIMINARY ISSUE ACN 070 431 931 2 Small St_ Hampton, Vic. 3188

FLY BRACING DETAILS Ph: 03 9521 8588 Fax: 03 9521 fl211 revision no· 01
ra,· Email: byp@byp.com.au A.B.N. 78 005 39-1 758
by·
dale- description:
drawing no: S 11