Maintenance
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
This document and the information in it are the property of Trane and may not be used
or reproduced in whole or in part, without the written permission of Trane. Trane reserves
the right to revise this publication at any time and to make changes to its content without
obligation to notify any person of such revision or change.
Trademarks
Trane and its logo are trademarks of Trane in the United States and other countries. All
trademarks referenced in this document are the trademarks of their respective owners.
BAS-SVX46B-EN 3
Overview
This guide provides installation, operation, and maintenance information for the following:
• Tracer™ XM30 Expansion Module
• Tracer™ XM32 Expansion Module
• Tracer™ XM70 Expansion Module
Expansion modules provide additional hardware terminations when needed for Tracer™ UC400
and Tracer™ UC600 applications. Each of the expansion modules listed above vary in the type and
capability of expansion; In some cases, additional Tracer™ PM014 DC power supply modules are
required.
The following table provides storage and operation specifications for the expansion modules.
Operating
Installation: UL 840:Category 3
Pollution: UL 840:Degree 2
Agency Compliance
4 BAS-SVX46B-EN
Overview
Configurable Connections
The following tables provide input and output connection information.
BAS-SVX46B-EN 5
Overview
Universal Input/
Configure using any combination of analog or binary inputs/analog outputs
Analog Output
10k– Type II, 10k –Type III, 2252
Thermistor
– Type II, 20k – Type IV, 100 k
The XM70 is limited to 10 combined
Resistive (Setpoint) 100–1M 0-20 mA current inputs/outputs when
powering up to two expansion
1k; 375 platinum, Balco™ or 672
RTD modules (XM30/32).
nickel
Binary output 4 Relay – SPST (form A) 24 VAC, 0.5A maximum Ranges are given per contact.
Total
19
terminations
6 BAS-SVX46B-EN
Overview
Dimensions
The following figures illustrate dimensions for the expansion modules. DIN width measurements
help determine how many modules can be installed on a DIN rail; use the following standard:
DIN Standard 43 880 standard profile, Built-in Equipment for Electrical Installations, Overall
Dimensions and Related Mounting Dimensions.
*One DIN unit = 18 mm.
4.00 in.
(101.6 mm)
ADDRESS
BAS-SVX46B-EN 7
Overview
2.38 in.
(60.45 mm)
1.93 in.
(49.02 mm)
2.82 in. (71.63 mm)
*4 DIN units
+24
VDC
IMC
1
A B
4.00 in. XM32 TRANE
(101.6 mm) IMC
BO1 BO2 BO3 BO4 TX
RX
SERVICE
ADDRESS
901 901
78
78
2 3
2 3
45 6 45 6
x10 x1
RELAYS
BO1 BO2 BO3 BO4
NO NC C NO NC C NO NC C NO NC C
2.17 in.
(55 mm) 1.73 in
8.50 in. (215.9 mm) width
(44 mm)
*12 DIN units
P1
XM70
(101.6 mm) RX
SERVICE
ADDRESS
901 901
2 3
2 3
7 8
7 8
456 456
x10 x1
8 BAS-SVX46B-EN
Power Budget Check
This section provides information about power budget consumption for the UC400, UC600, and
XM70 when using XM30 and XM32 expansions modules.
BAS-SVX46B-EN 9
Power Budget Check
10 BAS-SVX46B-EN
Installing the Expansion Modules
To mount or remove the expansion modules from a DIN rail, follow the illustrated instructions
below. If using a DIN rail from another manufacturer, follow the recommended installation
procedures that accompany it.
Important: When mounting the module in a control cabinet, provide adequate spacing between
modules to allow for ventilation and heat dissipation.
Notice:
Avoid Equipment Damage
Do not use excessive force to install the controller on the DIN rail. Excessive force could result in
damage to the enclosure.
Pry upward
11 BAS-SVX46B-EN
Installing the Expansion Modules
901
23
78
456
12 BAS-SVX46B-EN
Installing the Expansion Modules
BAS-SVX46B-EN 13
Installing the Expansion Modules
Figure 7. Example of a typical installation: two expansion modules and one UC600 controller
1
1 1
P1
A B
UC600 XM32 TRANE XM30
LINK MBUS IMC IMC IMC
B O1 BO2 B O3 B O4 TX BO1 BO2 BO3 BO4 TX TX
RX RX RX
LINK
SERVICE SERVICE SERVICE
ACT
SERVICE TOOL
78
2 3
2 3
2 3
2 3
2 3
7 8
7 8
7 8
2 3
2 3
7 8
7 8
456 456 456 45 6 45 6 456 456
x100 x10 x1 x10 x1 x10 x1
14 BAS-SVX46B-EN
Installing the Expansion Modules
Figure 8 illustrates an application with more than two expansion modules, which requires the use of a PM014 power
supply module. In this scenario, the UC600 only provides power and IMC communications for the first two expansion
modules.
Observe the following when using this method:
• The IMC harness/IMC terminals that connect the second expansion module to the PM014 must not transmit 24 VDC.
Remove the bottom (red) wire from the IMC cable harness.
• The PM014 can provide power for an additional 11 expansion modules.
• The UC600 provides 24 VDC power for the first two expansion modules.
• The transformer provides 24 VAC input power for the UC600 and the PM014.
Note: The above guidelines also apply when using a Tracer UC400 controller.
IMC IMC
IMC +24 +24 +24 IMC IMC +24 IMC IMC IMC
24 24 24 +24 +24
VAC VAC VAC VDC VDC VDC VDC +24 VDC
XFMR OUT MBUS OUT OUT LINK IMC VDC IMC VDC IMC
IMC IMC
1
1 1
1 1
P1
A B A B
UC600 XM32 TRANE XM30 PM014 XM32 TRANE XM30
LINK MBUS IMC IMC IMC IMC IMC
B O1 BO2 BO 3 BO4 TX BO1 BO2 BO3 BO4 TX TX BO1 BO2 BO3 BO4 TX TX
RX RX RX RX RX
LINK
SERVICE SERVICE SERVICE SERVICE SERVICE
ACT
SERVICE TOOL
0 0
ADDRESS ADDRESS ADDRESS ADDRESS ADDRESS
9
01 0
9 1 9
01 901 901 9
01 0
9 1
9 1 9 1
9
01 0
9 1
78
78
2 3
78
2 3
78
2 3
2 3
2 3
2 3
2 3
7 8
7 8
7 8
2 3
2 3
7 8
7 8
2 3
2 3
7 8
7 8
4 56 4 56 4 56 45 6 45 6 4 56 4 56 45 6 45 6 4 56 4 56
x100 x10 x1 x10 x1 x10 x1 x10 x1
x10 x1
• 24 VAC input power is provided by the transformer (for UC600 and PM014).
• The two expansion modules positioned on the left side of the PM014 receive 24 VDC power from the UC600.
• The two expansion modules (2 of 11 maximum) positioned on the right side of the PM014 are powered by
the PM014.
• The IMC cable between the expansion module and the PM014 must have the 24 VDC wire removed.
BAS-SVX46B-EN 15
Installing the Expansion Modules
Figure 9 Illustrates an application where an XM70 is used to provide power for two additional expansion modules. On this
link a total of four expansion modules can be added.
• 24 VAC input power is provided by the transformer (for UC600 and XM70)
• A maximum of two expansion modules can be powered by the UC600 24 VDC through the IMC cable.
• A maximum of two expansion modules can be powered by the XM70 through the IMC cable.
• The IMC cable between the expansion module powered by the UC600/400 DC power and the XM70 must have the 24
VDC wire removed.
• Connect the modified IMC cable between the XM30 that is powered from the UC400/UC600 and the XM70.
• The XM70 can power up to two XM30 or XM32 expansion modules.
IMC IMC
Red wire
removed
IMC +24 +24 +24 IMC IMC +24 IMC IMC +24 +24 +24 IMC IMC +24 IMC
24 24 24 +24 24 24 +24
VAC VAC VAC VDC VDC VDC VDC VAC VAC VDC VDC VDC VDC
XFMR OUT MBUS OUT OUT LINK IMC VDC IMC XFMR OUT OUT IMC VDC IMC
IMC IMC
UI1 UI2 UI3 UI4 UI5 UI6 UI7 UI8 UI1 UI2 UI3 UI4 UI5 UI6 UI7 UI8
1
1 1 1
1 1
P1
A B P1
A B
UC600 XM32 TRANE XM30 XM70 XM32 TRANE XM30
LINK MBUS IMC IMC IMC IMC IMC IMC
B O1 BO 2 B O3 B O4 TX BO1 BO2 BO3 BO4 TX TX BO1 BO2 BO3 BO4 TX BO1 BO2 BO3 BO4 TX TX
RX RX RX RX RX RX
LINK
SERVICE SERVICE SERVICE SERVICE
SERVICE SERVICE
ACT
SERVICE TOOL
0 0
ADDRESS ADDRESS
ADDRESS ADDRESS ADDRESS ADDRESS 1 1
90 1 90 1 90 1 901 901 90 1 90 1 9 01 9 01
9 9 90 1 90 1
78
78
2 3
2 3
78
78
2 3
2 3
2 3
2 3
7 8
7 8
2 3
2 3
2 3
7 8
7 8
7 8
7 8
7 8
23
23
2 3
2 3
7 8
7 8
4 56 4 56 4 56 45 6 45 6 45 6 45 6
45 6 45 6 4 56 4 56
4 56 4 56
x100 x10 x1 x10 x1 x10 x1 x10 x1
x10 x1 x10 x1
AO1 AO2 AO3 AO4 AO5 AO6 AO1 AO2 AO3 AO4 AO5 AO6
UI9 UI10 UI11 UI12 UI13 UI14 UI9 UI10 UI11 UI12 UI13 UI14
RELAYS RELAYS
RELAYS 0.5 A MAX RELAYS 0.5 A MAX BO3 BO4 UI / AO
BO3 BO4 UI / AO BO1 BO2
BO1 BO2
BO1 BO2 BO3 BO4 NO NC C NO NC C NO NC C NO NC C
NO NC C NO NC C NO NC C NO NC C BO1 BO2 BO3 BO4 1 2 3 4
1 2 3 4
16 BAS-SVX46B-EN
Installing the Expansion Modules
Figure 10 illustrates an application with two XM70 expansion modules. When connecting multiple XM70 modules, the +24
VDC must be removed between each UC400/600 and each XM70.
• 24 VAC input power is provided by the transformer (for UC600 and each XM70 module)
• A maximum of two expansion modules can be powered by the XM70 through the IMC cable.
• The IMC cable between the two XM70 modules must have the 24 VDC wire removed.
– As an alternative, do not install the +24 VDC terminals between devices.
• The XM70 can power up to two XM30 or XM32 expansion modules.
Note: Remove the +24 VDC wire from the IMC harness or do not install the +24 VDC terminals between devices. This also
applies to remote installations.
IMC IMC
UI1 UI2 UI3 UI4 UI5 UI6 UI7 UI8 UI1 UI2 UI3 UI4 UI5 UI6 UI7 UI8 UI1 UI2 UI3 UI4 UI5 UI6 UI7 UI8
1 1 1
P1 P1 P1
2 3
2 3
7 8
7 8
7 8
7 8
7 8
7 8
7 8
23
23
23
23
4 56 4 56 4 56 45 6 45 6 45 6 45 6
x100 x10 x1 x10 x1 x10 x1
AO1 AO2 AO3 AO4 AO5 AO6 AO1 AO2 AO3 AO4 AO5 AO6 AO1 AO2 AO3 AO4 AO5 AO6
UI9 UI10 UI11 UI12 UI13 UI14 UI9 UI10 UI11 UI12 UI13 UI14 UI9 UI10 UI11 UI12 UI13 UI14
BO1 BO2 BO3 BO4 BO1 BO2 BO3 BO4 BO1 BO2 BO3 BO4
BAS-SVX46B-EN 17
Installing the Expansion Modules
Remote Mounting
Expansion modules can be mounted remotely by extending the communication and power wiring
from the IMC terminals.
Observe the following when mounting remotely:
• Maximum length of communication wiring cannot exceed 656 ft. (200 m).
• Twisted pair, 18 gauge wire is required for IMC communication.
• A maximum of 2 expansion modules can be powered off of a UC400/UC600.
• A maximum of 11 expansion modules can be powered with the addition of a PM014 power
supply module.
Figure 11 illustrates a basic example of remote mounting where expansion modules are locally
powered (power is supplied off of a UC400 or UC600). A maximum of two expansion modules can
be powered locally.
Additional expansion modules require the use of a PM014 power supply module (see Figure 12,
p. 19).
1
1 1
P1
A B
UC600 XM32 TRANE XM30 TRANE
LINK MBUS IMC IMC IMC
BO1 BO2 BO3 BO4 TX BO1 BO2 BO3 BO4 TX TX
RX RX RX
LINK
SERVICE SERVICE SERVICE
ACT
SERVICE TOOL
2 3
2 3
7 8
7 8
7 8
78
78
2 3
2 3
2 3
2 3
7 8
7 8
4 56 4 56 4 56 45 6 45 6 4 56 4 56
x100 x10 x1 x10 x1 x10 x1
18 BAS-SVX46B-EN
Installing the Expansion Modules
Figure 12 illustrates an advanced example of remote wiring, which includes a PM014 power supply
module. This method is required if more than two expansion modules are powered from a
UC400/600.
Do the following if using this method:
• Remove the +24 VDC wire from both the expansion module and the PM014 power supply
module.
• Run both IMC and 24 VDC.
• Remotely mounted expansion modules must have a common ground plane:
– Ensure that the ground wire is connected between remotely mounted modules.
Figure 12. Remote mounting with the use of a PM014 power supply
+24
VDC
IMC +24
VDC
IMC
1
1 1
P1
A B
UC600 XM32 TRANE
PM014 TRANE XM30
LINK MBUS IMC IMC
BO1 BO2 BO3 BO4 TX TX IMC
BO1 BO2 BO3 BO4 TX
RX RX
RX
LINK
SERVICE SERVICE
ACT SERVICE
SERVICE TOOL
ADDRESS ADDRESS
901 901 901 901 901
ADDRESS
901 901
2 3
2 3
2 3
7 8
7 8
7 8
78
78
2 3
2 3
2 3
2 3
7 8
7 8
456 456 456 45 6 45 6 456 456
x100 x10 x1 x10 x1
x10 x1
BAS-SVX46B-EN 19
Installing the Expansion Modules
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
CAUTION
Personal Injury and Equipment Damage!
After installation, verify that the 24 VAC transformer is grounded through the controller. Failure
to check could result in personal injury and/or damage to equipment.
Note: Measure voltage between chassis ground and any other ground symbol on the module
(VAC 4.0V; must comply with National Electrical Code and local electrical codes).
NOTICE:
Equipment Damage!
Complete input/output wiring before applying power to the XM32. Failure to complete this
task could cause damage to the controller or power transformer due to inadvertent
connections to power circuits.
Important: AC wiring must be in conformance with the specifications for each device and
comply with National Electrical Code and local electrical codes.
Table 7.
Maximum Wire Lengths
Type Inputs Outputs
Binary 1,000 ft (300 m) 1,000 ft (300 m)
0–20 mA 1,000 ft (300 m) 1,000 ft (300 m)
0–10 VDC 300 ft (100 m) 300 ft (100 m)
Thermistor/Resistive 300 ft (100 m) Not Applicable
• All wiring must be in accordance with the NEC and local codes.
• Use only 18–22 AWG (1.02 mm to 0.65 mm diameter), stranded, tinned-copper, shielded, twisted-pair wire.
• Analog and 24 VDC output wiring distances are dependent on the receiving unit specifications. Use shielding for analog and
24 VDC outputs.
• DO NOT run input/output wires or communication wires in the same wire bundle with AC power wires.
20 BAS-SVX46B-EN
Installing the Expansion Modules
Transformer Requirements
• AC transformer requirements: UL listed, Class 2 power transformer, 24 VAC ±10%, device max
load 26 VA. The transformer must be sized to provide adequate power to the XM70 expansion
module (26 VA) and outputs (maximum 12 VA per binary output).
• CE-compliant installations: The transformer must be CE marked and SELV compliant per IEC
standards.
Notice:
Avoid Equipment Damage!
Sharing 24 VAC power between controllers could cause equipment damage.
A separate transformer is recommended for each controller. The line input to the transformer must
be equipped with a circuit breaker sized to manage the maximum transformer line current.
If a single transformer is shared by multiple XM70/UC600 devices:
• The transformer must have sufficient capacity.
• Polarity must be maintained for every XM70/UC600 device powered by the transformer.
Important: If polarity is inadvertently reversed between controllers that are powered by the
same transformer, a difference of 24 VAC will occur between the grounds of each
controller. The following symptoms could result:
BAS-SVX46B-EN 21
Installing the Expansion Modules
24 VAC
transformer
Connect secondary
transformer wires
here
P1
XM70
IMC
BO1 BO2 BO3 BO4 TX
RX
SERVICE
ADDRESS
901 901
2 3
2 3
7 8
7 8
456 456
x10 x1
22 BAS-SVX46B-EN
Installing the Expansion Modules
BAS-SVX46B-EN 23
Expansion Module Operation
After applying power to the expansion modules, the transmitting (TX) and receiving (RX) LEDs
blink when communication occurs between devices. The following table describes LED activity and
indicators.
LED has been pressed and remains on until Sequence on power-up: One short
Solid green
powered down blink upon power-up or during memory
test; will remain green if memory test
fails. When the service LED is pressed,
Service
the module will continue to use its normal
LED not illuminated Normal operation node number for communication.
However, it will communicate node 0 if
possible (this does not affect operation).
BAS-SVX46B-EN 24
Expansion Module Operation
Troubleshooting
This section describes possible solutions for communication and status errors that may occur after
the modules have been configured (“Configuring the Expansion Modules,” p. 23).
Note: By clicking the Discover Modules button, you can locate addresses of modules without
defining them.
Communication
Problem:
Points that are referencing expansion modules are in fault or not controlling.
Solution: Verify communication with expansion modules.
1. Verify that the expansion modules are powered.
2. Visually verify that all modules are communicating (both the TX and RX lights are blinking).
3. In Tracer TU, navigate to the Utilities/Controller/Controller Status screen.
4. In the Expansion Module Status section, confirm that all modules are communicating. After
clicking Send to Device, if errors appear in the Errors column see “Status Errors” below.
Status Errors
Error messages that appear in the Expansion Module Status section are explained here.
BAS-SVX46B-EN 25
Expansion Module Operation
26 BAS-SVX46B-EN
Commissioning and Troubleshooting in a Powered State
This section provides instructions for testing the expansion module points after establishing a
connection and applying power. The step numbers or method numbers in each figure correspond
to the information in each table. Refer to Table 2, Table 3 and Table 4, p. 6 for a list of device
connections.
The following equipment is required in order to test inputs and outputs:
• Digital multimeter (DMM)
• Small flat-bladed screwdriver
27 BAS-SVX46B-EN
Commissioning and Troubleshooting in a Powered State
Resistive Inputs
Measured Voltage Across a Thermistor Input Measured Voltage Across a Thermistor Input
4 4
Voltage Measured Across Input–Vdc
3.5 3.5
3 3
2.5 2.5
2 2
1.5 1.5
1 1
0.5 0.5
0 0
0 50 100 150 200 -40 -20 0 20 40 60 80 100
Charts show
measurements 2
across thermistor
input (Fahrenheit
1.5
and Celsius) and
resistive input.
1
0.5
0
0 2 4 6 8 10 12 14 16 18 20
28 BAS-SVX46B-EN
Commissioning and Troubleshooting in a Powered State
Voltage Inputs
BAS-SVX46B-EN 29
Commissioning and Troubleshooting in a Powered State
3.5
2.5
1.5
0.5
0
0 2 4 6 8 10 12 14 16 18 20
30 BAS-SVX46B-EN
Commissioning and Troubleshooting in a Powered State
BAS-SVX46B-EN 31
Voltage Analog Output
32 BAS-SVX46B-EN
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad
portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.