Download as pdf or txt
Download as pdf or txt
You are on page 1of 27

Installation & Maintenance Data IM 778-2

Group: WSHP
Part Number: 106751103
Date: June 2006

McQuay® Enfinity™
Vertical Water Source Heat Pumps
Unit Sizes 007 – 012 / R-22 Refrigerant
Unit Sizes 019 – 060 / R-410A Refrigerant

Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Unit Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-14
Transportation & Storage . . . . . . . . . . . . . . . . . . . . . . . 2 Thermostat Connections . . . . . . . . . . . . . . . . . . . . . . 16
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 Options for Mark IV/AC Units . . . . . . . . . . . . . . . . 17-21
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Field Installed Options on MicroTech Units . . . . . . . . 22
Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . 23
Cleaning & Flushing System . . . . . . . . . . . . . . . . . . . . 6 Troubleshooting WSHP. . . . . . . . . . . . . . . . . . . . . 24-25
Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Troubleshooting Refrigeration Circuit . . . . . . . . . . . . . 26
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . 9-11

©2006 McQuay International


Model Nomenclature
Note: For illustration purposes only. Not all options available with all models.
Please consult McQuay Sales Representative for specific availability.

W FCV 1 009 M E Y L T
Product Category Discharge Air
W = WSHP T = Top

Product Identifier
FCV = Floor Mounted/Standard Range Return Air
FCW = Floor Mounted/Geothermal L = Left
R = Right
Design Series
1 = A Design Future
2 = B Design (None)
3 = C Design
4 = D Design Voltage
A = 115/60/1
Nominal Capacity E = 208-230/60/1
007 = 7,000 F = 208-230/60-/3
009 = 9,000 J = 277-265/60/1
012 = 12,000 Controls K = 460/60/3
019 = 19,000 M = Mark IV L = 575/60/3
024 = 24,000 L = Microtech 2000 50 Hz
030 = 30,000 A = BACnet M = 230/50/1
036 = 36,000 N = 380/50/3
042 = 42,000
048 = 48,000
060 = 60,000

Note: Installation and maintenance must be performed only by qualified personnel who are familiar with local codes
and regulations, and are experienced with this type of equipment.

! CAUTION
Sharp edges can cause personal injury. Avoid contact with them.

Transportation & Storage


Upon receipt of the equipment, check carton for visible In the event that elevator transfer makes up-ended posi-
damage. Make a notation on the shipper’s delivery ticket tioning unavoidable, absolutely ensure that the machine is
before signing. If there is any evidence of rough handling, in the normal upright position for at least 24 hours before
immediately open the cartons to check for concealed dam- operating.
age. If any damage is found, notify the carrier within 48 Temporary storage at the job site must be indoors, com-
hours to establish your claim and request their inspection pletely sheltered from rain, snow, etc. High or low tempera-
and a report. The Warranty Claims Department should then tures naturally associated with weather patterns will not
be contacted. harm the conditioners. Excessively high temperatures,
Do not stand or transport the machines on end. For stor- 140°F (60°C) and higher, may deteriorate certain plastic
ing, each carton is marked with “up” arrows. materials and cause permanent damage.

Installation
General
1. To prevent damage, do not operate this equipment for 6. The installing contractor will find it beneficial to confer
supplementary heating and cooling during the con- with piping, sheet metal, and electrical foremen before
struction period. installing any conditioners.
2. Inspect the carton for any specific tagging numbers NOTE: Check the unit name plate for correct voltage with
indicated by the factory per a request from the installing the plans before installing the equipment. Also,
contractor. At this time the voltage, phase and capaci- make sure all electrical ground connections are
ty should be checked against the plans. made in accordance with local code.
3. Check the unit size against the plans to ensure unit 7. We recommend that the contractor cover the condi-
installation is in the correct location. tioners with plastic film to protect the machines during
finishing of the building. This is critical while spraying
4. Before installation, check the available closet dimen-
fireproofing material on bar joists, sandblasting, spray
sions versus the dimensions of the unit.
painting and plastering. If plastic film is not available,
5. Note the location and routing of water piping, conden- the shipping carton may be modified to cover the units
sate drain piping, and electrical wiring. The locations of during construction.
these items are clearly marked on submittal drawings.
Page 2 / IM 778
Unit location 5. It is recommended that the unit be located on top of a
vibration absorbing material such as rubber or carpet to
1. Locate the unit in an area that allows for easy removal of
the filter and access panels, and has enough space for reduce any vibration. See Figure 8, page 6.
service personnel to perform maintenance or repair. 6. If optional field installed controls are required (boilerless
Provide sufficient room to make water, electrical and system), space must be provided for the enclosure to
duct connections. mount around the corner from the electrical entrances.
2. The contractor should make sure that access has been Do not locate the side of the unit too close to a wall. See
provided including clearance for duct collars and fittings Figures 1 and 2.
at water and electrical connections.
3. Allow adequate room around the unit for a condensate Minimum distance requirement from return air duct
trap. collar to wall, for non-ducted units.
4. The unit can be installed “free standing” in an equipment
room; however, closet installations are more common for Model Distance
small vertical type units. Generally, the unit is located in 007 – 012 4 inches
the corner of a closet with the non-ducted return air fac- 019 – 024 5 inches
ing 90° to the door and the major access panels facing 030 – 036 6 inches
the door as in Figure 1. Alternatively, the unit can have a 042 – 048 8 inches
ducted return air with the opening facing the door and
the major access panels facing 90° to the door as in Filter access
Figure 2. Each unit is shipped with a filter bracket for side filter
removal.

Figure 1. Typical closet installation with louver door return

Heat Pump with Heat Pump with


Left-Hand Right-Hand
Return Air Return Air
Arrangement Arrangement
NOTE: Minimum distance
requirement for non-ducted
Return Opt. Controls Opt. Controls Return units. (see chart above).
Air Elec. Entrance Elec. Entrance Air

Main Access Panel Main Access Panel

Condensate Condensate
Water Supply Water Supply

Water Return Water Return

Return Air Thru Risers Return Air Thru


Louvered Door Louvered Door

Figure 2. Typical closet installation with ducted return

Heat Pump with Heat Pump with


Left-Hand Right-Hand
Return Air Return Air Return
Arrangement Arrangement Air
Return Duct &
Air Opt. Controls Grille
Opt. Controls
Duct &
Grille
Elec. Entrance Elec. Entrance
Main Access Panel Main Access Panel

Condensate Condensate
Water Supply Water Supply

Water Return Water Return

Risers

IM 778 / Page 3
Ductwork and attenuation Figure 3.

Discharge ductwork is normally used with these condi-


Trunk Duct
tioners. Return air ductwork may also be required, but will
require field installation of a return air duct collar/2" (51mm) Square Elbow
(Both Sides
filter rack kit. Internally Lined
With Acoustic
All ductwork should conform to industry standards of Insulation)
good practice as described in ASHRAE Systems Guide.
Branch Duct
The discharge duct system will normally consist of a (Internally Lined)

flexible connector at the unit, a non-insulated transition


piece to the full duct size, a short run of duct, an elbow
without vanes, and a trunk duct teeing into a branch circuit Duct
with discharge diffusers as shown in Figure 3. The transition Transition

piece must not have an angle greater than 30° or severe 2 ft. x 2 ft.
Diffuser
loss of air performance can result. Do not connect the full
Discharge
duct size to the unit without using a transition piece down Collar
to the size of the discharge collar on the unit. With metal
duct material, the sides only of the elbow and entire branch
Heat Pump
duct should be internally lined with acoustic insulation for
sound attenuation. Glass fiber duct board material is more
absorbing and may permit omission of the flexible
connector.
The ductwork should be laid out so that there is no line
of sight between the conditioner discharge and the distrib-
ution diffusers.
Ventilation air
Outside air may be required for ventilation. The temper-
Return air ducts can be brought in through a wall grille
ature of the ventilation air must be controlled so that mixture
and then to the unit. The return duct system will normally
of outside air and return air entering the conditioner does
consist of a flexible connector at the unit and a trunk duct
not exceed application limits. It is also general practice to
to the return air grille. With metal duct material, the return
close off the ventilation air system during unoccupied peri-
air duct should be internally lined with acoustic insulation
ods (night setback).
for sound attenuation. Glass fiber duct board material is
more absorbing and may permit omission of the flexible The ventilation air system is generally a separate build-
connector. ing subsystem with distribution ductwork. Introduce outside
air into each return air plenum chamber reasonably close to
Return air ductwork to the unit requires the optional
the conditioner air inlet. Do not duct outside air directly to
return air duct collar/2" (51mm) filter rack kit. See Figure 4
the conditioner inlet. Provide sufficient distance for thor-
and 5. The kit can be installed for face side or bottom filter
ough mixing of outside and return air. See “Operating limits”
removal. The flexible connector can then be attached to the
on page 8.
1" (25mm) duct collar.
Do not use sheet metal screws directly into the unit
cabinet for connection of supply or return air ductwork,
especially return air ductwork which can puncture the drain
pan or the air coil.

Figure 4. Sizes 007 thru 048 Optional 2" Return Air Duct Figure 5. Size 060 Optional 2" Return Air Duct Collar
Collar Filter Rack Filter Rack

Page 4 / IM 778
Electrical Data
General
1. Verify the compatibility between the voltage and phase breaker for branch circuit overcurrent protection. See the
of the available power and that shown on the unit serial nameplate for correct ratings.
plate. Line and low voltage wiring must comply with local 3. Three phase 50 cycle units, 380/50/3, require a neutral
codes or the National Electrical Code, whichever wire for 230/50/1 power to the fan circuit.
applies.
4. Connect the thermostat/subbase wiring with the power
2. Apply correct line voltage to the unit. A 7⁄8" (22mm) hole “off ” to the unit.
and/or a 11⁄8" (29 mm) knockout is supplied on the side
of the unit. A disconnect switch near the unit is required 5. Field supplied relays installed on the input terminals
by code. Power to the unit must be sized correctly and W1, W2, Y1, Y2 or G may introduce electrical noise.
have dual element (Class RK5) fuses or an HACR circuit Never install relay coils in series with the inputs.

230 Volt Operation


All 208-230 volt single-phase and three-phase units are fac- changed. Disconnect and cap the red lead wire and inter-
tory wired for 208 volt operation. For 230 phase operation, change it with the orange lead wire on the primary of the 24
the line voltage tap on the 24 volt transformer must be volt transformer.

Fan Assembly
All fan motors are multi-speed, PSC type with integral motor and fan wheel removal without disconnecting the
mounting brackets and thermal overload protection. The ductwork. The fan housing protrudes through the cabinet
motor is isolated from the fan housing for minimum vibra- allowing adequate material for connection of flexible duct.
tion transmission. Fan motors have a terminal strip on the Each model unit is shipped from the factory for maximum
motor body for simple motor speed change without going performance and minimum sound requirements. Fan sound
back to the control box. All the fan/motor assemblies have levels and performance can be affected by external static
a removable orifice ring on the housing to accommodate pressure.

Figure 6. Sizes 007 through 012 Figure 7. Sizes 019 through 060

WHITE (COMMON)
WHITE (COMMON)
FAN BROWN (CAPACITOR)
FAN BROWN (CAPACITOR)
MOTOR MOTOR
BLACK (HIGH SPEED) SIZES 024, 030,
BLUE (HIGH SPEED) SIZE 007, 009, 012
036, 042, 060
RED (LOW SPEED)
RED (LOW SPEED)
SIZES - 019, 048

Piping
1. All units should be connected to supply and return pip- 4. Some flexible hose threaded fittings are supplied with
ing in a two-pipe reverse return configuration. A sealant compound. If not, apply Teflon tape for a tight
reverse return system is inherently self-balancing and seal.
requires only trim balancing where multiple quantities
5. Supply and return shutoff valves are required at each
of units with different flow and pressure drop charac-
conditioner. The return valve is used for balancing and
teristics exist in the same loop. Check for proper water
should have a “memory stop” so that it can always be
balance by measuring differential temperature reading
closed off but can only be reopened to the proper posi-
across the water connections. For proper water flow,
tion for the flow required.
the differential flow should be 10°F to 14°F (5°C to 8°C)
for units in cooling mode. 6. Do not connect any unit to the supply and return pip-
A direct return system may also work acceptably, ing until the water system has been cleaned and
but proper water flow balancing is more difficult to flushed completely. After the cleaning and flushing has
achieve and maintain. taken place, the initial connection should have all
valves wide open in preparation for water system flush-
2. The piping can be steel, copper or PVC.
ing.
3. Supply and return runouts usually join the unit via short
7. Condensate piping can be steel, copper or PVC. Each
lengths of high pressure flexible hose which are sound
unit includes a condensate connection.
attenuators for both unit operating noise and hydraulic
pumping noise. One end of the hose should have a 8. Units are internally trapped.
swivel fitting to facilitate removal for service. Hard pip-
ing also can be brought directly to the unit. This option
is not recommended since no vibration or noise atten-
uation can be accomplished. The hard piping must
have unions to facilitate unit removal. See Figures 8, 9,
and 10 for typical piping setup.
IM 778 / Page 5
Figure 8. Typical Vertical Unit Piping 9. Do not locate any point in the drain system above the
drain connection of any unit.
Supply Air 10. Automatic flow controlled devices must not be
Acoustical Thermal installed prior to system cleaning and flushing.
Duct Lining (10’)
11. A high point of the piping system must be vented.
Two 90° Turns 12. Check local code for the need for dielectric fittings.
(Ductwork Sized
Based on Airflow)

Note: Do not over-torque fittings. The maximum torque without damage to


Flexible Duct Collar
fittings is 30 foot pounds. If a torque wrench is not available, use as a rule
of thumb, finger-tight plus one quarter turn.
Blower Motor Access

Line Voltage Disconnect

Return Air

Isolator Pad
Ball Valve
Flexible Return Hose with with Mesurflo®
Swivel Fittings Ball Valve with
Y-Strainer
Flexible Supply Hose with Condensate
Swivel Fittings Drain

Cleaning & Flushing System


1. Prior to first operation of any conditioner, the water cir- The contractor should start main circulator with the
culating system must be cleaned and flushed of all con- pressure reducing valve open. Check vents in sequence
struction dirt and debris. to bleed off any trapped air, ensuring circulation through
If the conditioners are equipped with water shutoff all components of the system.
valves, either electric or pressure operated, the supply Power to the heat rejector unit should be off, and the
and return runouts must be connected together at each supplementary heat control set at 80°F (27°C).
conditioner location. This will prevent the introduction of While circulating water, the contractor should check
dirt into the unit. See Figure 9. and repair any leaks in the piping. Drains at the lowest
Figure 9. point(s) in the system should be opened for initial flush
and blow-down, making sure city water fill valves are set
to make up water at the same rate. Check the pressure
gauge at pump suction and manually adjust the makeup
to hold the same positive steady pressure both before
Return Runout and after opening the drain valves. Flush should contin-
ue for at least two hours, or longer if required, to see
Supply Runout clear, clean drain water.
3. Shut off supplemental heater and circulator pump and
open all drains and vents to completely drain down the
Mains system. Short circuited supply and return runouts should
now be connected to the conditioner supply and return
Flexible Hose
connections. Do not use sealers at the swivel flare con-
nections of hoses.
Runouts Initially
Connected Together 4. Trisodium phosphate was formerly recommended as a
cleaning agent during flushing. However, many states
and localities ban the introduction of phosphates into
their sewage systems. The current recommendation is to
2. Fill the system at the city water makeup connection with simply flush longer with warm 80°F (27°C) water.
all air vents open. After filling, close all air vents.

Page 6 / IM 778
5. Refill the system with clean water. Test the water using es premature failure. A SystemSaver™ from McQuay
litmus paper for acidity, and treat as required to leave the should be employed to continuously re-move solids as
water slightly alkaline (pH 7.5 to 8.5). The specified per- the system operates. Contact your local representative
centage of antifreeze may also be added at this time. for further information on this device.
Use commercial grade antifreeze designed for HVAC
6. Set the loop water controller heat add setpoint to 70°F
systems only. Do not use automotive grade antifreeze.
(21°C) and the heat rejection setpoint to 85°F (29°C).
Once the system has been filled with clean water and
Supply power to all motors and start the circulating
antifreeze (if used), precautions should be taken to pro-
pumps. After full flow has been established through all
tect the system from dirty water conditions. Dirty water
components including the heat rejector (regardless of
will result in system wide degradation of performance
season) and air vented and loop temperatures stabilized,
and solids may clog valves, strainers, flow regulators,
each of the conditioners will be ready for check, test and
etc. Additionally, the heat exchanger may become
start-up, air balancing, and water balancing.
clogged which reduces compressor service life or caus-

Start-up
1. Open all valves to full open position and turn on power operation, check for warm air delivery at discharge
to the conditioner. grille. If this is a “cold building” start-up, leave unit run-
ning until return air to the unit is at least 65°F (18°C).
2. Set thermostat for “Fan Only” operation by selecting
Measure the temperature difference between enter-
“Off” at the system switch and “On” at the fan switch.
ing and leaving air and entering and leaving water. With
If “Auto” fan operation is selected, the fan will cycle
entering water of 60°F to 80°F (16°C to 27°C), leaving
with the compressor. Check for proper air delivery.
water should be 6°F to 12°F (3.3°C to 6.6°C) cooler,
3. For those units that have two-speed motors, reconnect and the air temperature rise through the machine
for low speed operation if necessary. should not exceed 35°F (19°C). If the air temperature
exceeds 35°F (19°C), then the water flow rate is inade-
4. Set thermostat to “Cool.” If the thermostat is an auto-
quate.
matic changeover type, simply set the cooling temper-
ature to the coolest position. On manual changeover 6. Check the elevation and cleanliness of the condensate
types additionally select “Cool” at the system line. If the air is too dry for sufficient dehumidification,
switch. slowly pour enough water into the condensate pan to
Again, many conditioners have time delays which ensure proper drainage.
protect the compressor(s) against short cycling. After a
7. If the conditioner does not operate, check the following
few minutes of operation, check the discharge grilles
points:
for cool air delivery. Measure the temperature differ-
a. Is supply voltage to the machine compatible?
ence between entering and leaving water. It should be
b. Is thermostat type appropriate?
approximately 11⁄2 times greater than the heating mode
c. Is thermostat wiring correct?
temperature difference. For example, if the cooling
temperature difference is 15°F (8°C), the heating tem- 8. If the conditioner operates but stops after a brief period:
perature difference should have been 10°F (5°C). a. Is there proper airflow? Check for dirty filter, incor-
Without automatic flow control valves, target a cooling rect fan rotation (3-phase fan motors only), or incor-
temperature difference of 10°F to 14°F (5°C to 8°C). rect ductwork.
Adjust the combination shutoff/balancing valve in the b. Is there proper water flow rate within temperature
return line to a water flow rate which will result in the limits? Check water balancing; backflush unit if dirt-
10˚F to 14°F (5°C to 8°C) difference. clogged.
5. Set thermostat to “Heat.” If the thermostat is the auto- 9. Check for vibrating refrigerant piping, fan wheels, etc.
matic changeover type, set system switch to the
10. Do not lubricate the fan motor during the first year of
“Auto” position and depress the heat setting to the
operation as it is pre-lubricated at the factory.
warmest selection. Some conditioners have built-in
time delays which prevent the compressor from imme- 11. Field supplied relays installed on the input terminals
diately starting. With most control schemes, the fan will W1, W2, Y1, Y2 or G may introduce electrical noise.
start immediately. After a few minutes of compressor Never install relay coils in series with the inputs.

IM 778 / Page 7
Operating Limits
Environment
This equipment is designed for indoor installation only. temperature and/or humidity, and equipment performance,
Sheltered locations such as attics, garages, etc., generally reliability, and service life may be adversely affected.
will not provide sufficient protection against extremes in

Air limits Water limits


Standard Range Geothermal Range Standard Range Geothermal Range
Units Units Units Units
Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Min. Ambient Air 50˚F/10˚C 50˚F/10˚C 40˚F/5˚C 40˚F/5˚C Min. Ent. Water ➀ ➁ 55°F/13°C 55°F/13°C 30°F/-1°C 20°F/-6°C
Normal Ambient Air 80˚F/27˚C 70˚F/21˚C 80˚F/27˚C 70˚F/21˚C Normal Ent. Water 85°F/29˚C 70˚F/21°C 77°F/25˚C 40˚F/5°C
Max. Ambient Air 100˚F/38˚C 85˚F/29˚C 100˚F/38˚C 85˚F/29˚C Max. Ent. Water ➀ ➁ 110°F/43˚C 90°F/32°C 110°F/43˚C 90°F/32°C
Min. Ent. Air ➀ ➁ 50˚F/10˚C 50˚F/10˚C 50˚F/10˚C 40˚F/5˚C
➀ At ARI flow rate.
Normal Ent. Air, 80/67˚F 70˚F 80/67˚F 70˚F
➁ Maximum and minimum values may not be combined. If one
dw/wb 27/19˚C 21˚C 27/19˚C 21˚C
value is at maximum or minimum, the other two conditions
Max. Ent. Air 100/83˚F 80˚F 100/83˚F 80˚C may not exceed the normal condition for standard units.
db/wb ➀ ➁ 38/28˚C 27˚C 38/28˚C 27˚C Extended range units may combine any two maximum or
minimum conditions, but not more than two, with all other
conditions being normal conditions.

Additional Information For Initial Start-up Only


Standard Range units FCV
Units are designed to start-up in an ambient of 50°F (10°C),
Operating voltages
with entering air at 50°F (10°C), with entering water at 70°F 115/60/1 . . . . . . . . . . . . . . . 104 volts min.; 127 volts max.
(21°C), with both air and water flow rates used in the ARI 208-230/60/1 . . . . . . . . . . . 197 volts min.; 253 volts max.
Standard 320-86 rating test, for initial start-up in winter. 265/60/1 . . . . . . . . . . . . . . . 238 volts min.; 292 volts max.
Note: This is not a normal or continuous operating con- 230/50/1 . . . . . . . . . . . . . . . 197 volts min.; 253 volts max.
dition. It is assumed that such a start-up is for the purpose 460/60/3 . . . . . . . . . . . . . . . 414 volts min.; 506 volts max.
of bringing the building space up to occupancy 380/50/3 . . . . . . . . . . . . . . . 342 volts min.; 418 volts max.
temperature. 575/60/3 . . . . . . . . . . . . . . . 515 volts min.; 632 volts max.

Geothermal range units FCW Note: Voltages listed are to show voltage range. However,
units operating with over voltage and under voltage for
Geothermal range heat pump conditioners are designed to
extended periods of time will experience premature com-
start-up in an ambient of 40°F (5°C), with entering air at
ponent failure. Three phase system unbalance should not
40°F (5°C), with entering water at 25°F (-4°C), with both air
exceed 2%.
and water at flow rates used in the ARI Standard 330-86
rating test, for initial start-up in winter.
Note: This is not a normal or continuous operating con-
dition. It is assumed that such a start-up is for the purpose
of bringing the building space up to occupancy
temperature.

Page 8 / IM 778
Typical Wiring Diagrams
Figure 10. Typical Mark IV/AC wiring diagram

Notes:
1. Unit is factory wired for 208V operation. If 230V
power supply is used, transformer must be
rewired by disconnecting the power lead from the
red transformer primary wire and connecting the
power lead to the orange transformer primary
wire. Place an insulation cap on the red trans- L1 L2 Ground
former primary wire.
2. All temperature and pressure switches are nor-
mally closed.
3. Component layout shown below is typical. Some
components may not be used on this model or
Compr
voltage. Motor
4. Mark IV/AC controller board contains a static sen-
sitive microprocessor. Proper grounding of field
service personnel should be observed or damage Heater
to controller may result.
5. Terminal block on Mark IV/AC board provides 24
060 - Blk
VAC at terminals R and C. All other outputs are 24 048 - Red Fan
VDC. 042 - Blk Motor
036 - Blk
6. Field supplied relays installed on the input ter- 030 - Blk
minals (W1, W2, Y1 or G) may interfere with
proper unit operation. Never install relay coils
in series with inputs.
7. For more information pertaining to the Mark IV/AC
controller, refer to OM120.

CC - Compressor Contactor
HTR - Crankcase Heater (Optional)
CAP - Motor Capacitor CC

Lo Temp

Condensate
Hi Pressure
Sensor
L1

Common
Fan

Compressor

Lo Pressure

COMPONENT LAYOUT
➀ COMPRESSOR CONTACTOR Mark IV
Reversing Valve PC
➁ FAN CONTACTOR Solenoid 0 WGWY F E L U A P V R C Board
➂ TRANSFORMER 2 1 1
➃ PC BOARD
➄ AUXILIARY RELAY
➅ CIRCUIT BREAKER

IM 778 / Page 9
Figure 11. Typical MicroTech 2000 WSHP unit controller single circuit wiring diagram

Notes:
1. Unit is factory wired for 208V operation. If 230V power supply is used, 2. All temperature and pressure switches are normally closed.
transformer must be rewired by disconnecting the power lead from the
red transformer primary wire and connecting the power lead to the 3. Wires 71 and 72 used only on units with no factory installed options.
orange transformer primary wire. Place an insulation cap on the red
transformer primary wire.

Page 10 / IM 778
Figure 12. Typical BACnet® WSHP unit controller

Notes:
1. Unit is factory wired for 208V operation. If 230V power supply is used,
transformer must be rewired by disconnecting the power lead from the
red transformer primary wire and connecting the power lead to the
orange transformer primary wire. Place an insulation cap on the red
transformer primary wire.

BACnet
Controller

IM 778 / Page 11
Unit Operation
Three types of units are available: Mark IV/AC control units or units equipped with a MicroTech™ 2000 or BACnet® Water
Source Heat Pump Controller.
Mark IV/AC Control Units
The Mark IV/AC circuit board is an optional control sys- The Remote Reset feature provides the means to
tem with built-in features such as random start, compressor remotely reset automatic lockouts generated by high-pres-
time delay, night setback, load shed, shutdown, conden- sure and/or low-temperature (in heating) faults. When the
sate overflow protection, defrost cycle, brownout, and Mark IV board is in automatic lockout due to one of these
LED/fault outputs. Figure 13 shows the LED and fault out- faults, and the cause of the fault condition has been allevi-
put sequences.
ated, energizing the O-terminal for 10 seconds or more will
The unit has been designed for operation with a 24 volt
mercury bulb type wall thermostat or a microelectronic wall force the Mark IV board to clear the lockout. A unit power
thermostat selected by the manufacturer. Do not operate cycle can also be used to clear an automatic lockout if the
the unit with any other type of wall thermostat. conditions causing the fault have been alleviated.
Each unit has a printed circuit board control system. The The Fault Retry feature helps to minimize nuisance trips
low voltage output from the low voltage terminal strip can of automatic lockouts caused by high-pressure and/or low-
be either AC voltage or DC voltage to the wall thermostat. temperature (in heating) faults. This feature clears faults the
This is dependent on what terminals you use. R is A/C volt- first two times they occur within a 24-hour period and trig-
age output and F is D/C voltage output to the wall stat. gers an automatic lockout on the 3rd fault. The retry count
The 24 volt low voltage terminal strip is set up so R-G or is reset to zero every 24 hours.
F-G energizes the fan, R-Y1 or F-Y1 energizes the com-
The Mark IV/AC control circuit has built-in night setback
pressor for cooling operation, R-W1 or F-W1 energizes the
compressor and reversing valve for heating operation. The operation. A “grounded’ signal to the “U” terminal on the
reversing valve is energized in the heating mode. The circuit low voltage terminal strip puts the unit into the unoccupied
board has a fan interlock circuit to energize the fan whenev- mode for night setback operation. Fan operation terminates
er the compressor is on if the thermostat logic fails to do so. and unit control reverts to the night setback terminal on the
Remember the output to the wall stat can be AC current thermostat, W2; day heating and cooling operation is
or DC current. Terminal (R) on the wall stat can be connect- locked out. R-W2 energizes the compressor and reversing
ed to terminal (R) on the PC board for AC voltage or to ter- valve for heating operation. Night setback operation can be
minal (F) on the PC board for DC voltage. overridden for two hours by toggling the fan switch (inter-
AC current DC current mittently closing the R to O terminals) on the Deluxe Auto
R to G = fan only F to G = fan only Changeover thermostat. Day thermostat setpoints then
R to Y1 = cooling F to Y1 = cooling control the heating and cooling operation. The Mark IV/AC
R to W1 = heat F to W1 = heat control system also accommodates load shed and shut-
The Mark IV/AC control board has a lockout circuit to down operation on receipt of a “grounded” signal to the “L”
stop compressor operation if any one of its safety switches and “E” terminals, respectively, on the low voltage terminal
opens (high pressure switch and low pressure switch on strip.
unit sizes 024 through 060). If the low temperature switch
opens, the unit will go into the cooling mode for 60 seconds Figure 14.
to defrost any slush in the water-to-refrigerant heat
exchanger. After 60 seconds the compressor is locked out.
Unit Unit Unit
If the condensate sensor detects a filled drain pan, the 1 2 3
compressor operation will be suspended only in the cooling
mode. The unit is reset by opening and closing the discon- To
nect switch on the main power supply to the unit in the Additional
Units
event the unit compressor operation has been suspended Time
due to low temperature (freezestat) switch, high pressure Clock

switch, or low pressure switch on unit sizes 048 thru 060. Chassis
Ground
The unit does not have to be reset on a condensate over-
flow detection. To activate the unoccupied mode for units on the same clock schedule,
The Mark IV/AC control board fault output sends a sig- a single wire can be “daisy chained” between units and simply ground-
nal to an LED on a wall thermostat. Figure 13 shows for ed through the time clock contacts. The same system can also be done
which functions the fault output is “on” (sending a signal to to activate the load shed and unit shutdown modes by running addi-
tional wires between units to ground.
the LED).
Figure 13.
The P and C terminals of the Mark IV/AC board are used
LEDs Fault
Indication for pump restart. These terminals pass a voltage signal
Yellow Green Red Output
whenever the unit compressor is turned on. This signal is
Normal Mode Off On Off Off
detected by a pump restart relay board providing a N.O. or
High Pressure Fault Off Off Flash On
N.C. set of contacts for heat pump loop circulation pump
Low Temperature Fault* Flash Off Off On
control. When used with the Loop Water Controller, the
Condensate Overflow On Dim Off On
relay operation accommodates turning off circulation
Brownout Off Flash Off On
pumps during unoccupied periods with a safety override
Load Shed Off Off On Off
dependent, at minimum, on WSHP’s need. The P and C ter-
Unoccupied Mode On On Off Off
minals may be “daisy chained” between 200 units. See
Unit Shutdown Off Flash Off On
page 19.
*In heating mode only Field supplied relays installed on the input terminals W1,
W2, Y1, Y2 or G may introduce electrical noise. Never install
relay coils in series with the inputs.
Page 12 / IM 778
MicroTech™ 2000 WSHP Unit Controller

Each McQuay Enfinity vertical water source heat pump can An amber, on-board status LED aids in diagnostics by indi-
be equipped with a MicroTech 2000 water source heat pump cating the water source heat pump operating mode and
unit controller. The controller is microprocessor-based and is alarm conditions. If there are no current alarm conditions,
designed to communicate over a LonWorks communica- the LED will indicate the unit operating mode as shown in
tions network. The unit controller is factory programmed and the table below. If there are one or more alarm conditions
tested with all the logic required to monitor and control the present, the LED will flash to indicate an alarm condition.
unit. The controller sets the unit mode of operation, monitors
water and air temperatures, and can communicate fault con- MicroTech 2000 heat pumps are designed to be linked with
ditions to a LonWorks communications network. a centralized building automation system through a
LonWorks communications network for centralized schedul-
The MicroTech 2000 unit controllers include unit-mounted ing and management of multiple heat pumps. Wall-mounted
return air, discharge air and leaving water temperature sen- room sensors are available to control the heating and cool-
sors. Options include a tenant setpoint adjustment knob and ing operation of each MicroTech 2000 Water Source Heat
tenant override button, and the capability of substituting the Pump Unit Controller. Available room sensors include: room
return air sensor with a wall-mounted room sensor. sensor with LED status and tenant override button, room
sensor with LED status, timed-override button, and bi-metal
thermostat, room sensor with LED status, timed-override
button, and setpoint adjustment, and room sensor with LED
status, timed-override button, setpoint adjustment and bi-
Figure 15. MicroTech 2000™ WSHP unit controller
metal thermostat.

Figure 16. MicroTech 2000 Unit Controller LED Indication


Status LED State Mode
On Continually Occupied, Occupied Load
Shed
On 1⁄2 sec., Off 5 1⁄2 sec. Unoccupied
On 5 1⁄2 sec., Off 1⁄2 sec. Tenant Override, Override
Load Shed
Flashing Alarm Condition

Figure 17. MicroTech 2000™ WSHP unit control box

Each unit controller orchestrates the following unit


operations:

● Enable heating and cooling to maintain setpoint based on


a room sensor.
● Enable fan and compressor operation.
● Monitor all safety controls.
● Monitor discharge air temperature.
● Monitor leaving water temperature.
● Relay status of all vital unit functions.
● Support optional control outputs.

IM 778 / Page 13
BACnet® WSHP Unit Controller
McQuay Enfinity vertical water source heat pumps are Each BACnet-compliant controller has the following operat-
available with a factory mounted and tested Alerton BACnet ing features:
unit controller as a special. The unit controller is factory pro-
● Start-up – The unit will not operate until all the inputs
grammed and tested with all the logic required to control the
and safety controls are checked for normal conditions.
unit, and is designed to communicate over a BACnet MS/TP
communications network to an Alerton BACtalk building ● Fan operation – Fan operation can be customized in
software to run continuously during occupied mode, or to
automation system (BAS). The controller operates the com- cycle ON or OFF appropriately on a call for heating and
pressor, fan, and reversing valve as required to maintain the cooling.
space temperature within the current setpoints. Data
● Cooling mode – On a call for cooling, the compressor
regarding equipment status, water and air temperatures, and fan start immediately. Compressor run-time is cal-
and fault conditions can be monitored by an Alerton BACtalk culated as a percent of full cycle time (17 minutes) using
BAS. Setpoints and other system preferences may be proportional-integral control to maximize efficiency.
changed remotely using an Alerton BACtalk workstation or ● Heating mode – On a call for heating, the compressor
Alerton service tool software. and fan start immediately, and compressor run-time is
calculated as a percent of full cycle time (17 minutes)
The controller makes operational data and commands using proportional-integral control to maximize
efficiency.
available on the Alerton BACtalk network using BACnet
objects and properties. Each heat pump controller connects ● Short Cycle Protection and Random Start – A start
delay of 180 seconds plus the compressor’s MAC
to the BACtalk network using a BACnet MS/TP LAN, which
address in seconds prevents short-cycling and simulta-
is a simple twisted-pair communications connection that neous start-up. A minimum 2-minute on time and 5-
operates at up to 76.8 Kbps. DIP switches on the controller minute off time for the compressor further ensures short-
enable the MS/TP MAC address to be set in the range 0- cycle protection.
127. A status LED on the unit indicates communication ● Occupied Mode – A simple software control signal from
activity on the MS/TP LAN. the building automation system or a wall-mounted unit
puts the unit into occupied mode. The unit controls com-
pressor and fan operation to maintain occupied set-
Figure 18. BACnet® WSHP unit controller
points. High and low limits for occupied setpoints are
software configurable.
● Unoccupied Mode – A simple software control signal
from the building automation system or a wall-mounted
unit puts the unit into unoccupied mode for night setback
operation. The unit controls compressor and fan opera-
tion to maintain unoccupied heating and cooling set-
points, which are also software configurable.
● After-hours Override Mode – A simple software control
signal from the building automation system or a wall-
mounted unit can initiate after-hours heating or cooling
in half-hour increments. Maximum override time is soft-
ware configurable up to 9.5 hours. This feature can also
be disabled in software.
● Reversing valve delay – When the compressor turns
off after heating mode, the reversing valve remains ener-
gized for 60 seconds before it returns to the normal cool-
Each BACnet-compliant unit includes discharge air and ing position to eliminate swishing. The reversing valve
leaving water temperature sensors, as well as all safety energizes 10 seconds before the compressor.
sensors, signals, and switches. Wall-mounted room sen- ● Load Shed – Load shedding can be orchestrated by the
sors are available from Alerton to control heating and cool- building automation system using the occupied/unoccu-
ing operation. Available sensors include tamper-resistant pied command in software.
stainless steel wall sensors with optional push-button for ● Brownout Protection – An onboard sensor measures
status override; wall-mounted sensors with tenant setpoint input voltage and suspends compressor and fan opera-
tion if the supply voltage drops below 82% of the normal
adjustment lever and timed-override button; wall-mounted
line voltage for a minimum of 10 seconds, creating an
sensors with LED status, timed-override button, tenant set- alarm available in software. The alarm automatically
point adjustment buttons, password-protected field service resets when the supply voltage returns to above 90% of
access to operational data, and optional humidity sensor; normal.
and wall-mounted sensors with LCD and programmable
operation.

Page 14 / IM 778
BACnet® WSHP Unit Controller
● Condensate Overflow Protection – A liquid sensor at temperature is within setpoints. The controller also mon-
the top of the drain pan senses a high water level. Upon itors leaving water temperature. If the leaving water tem-
sensing water, cooling operation is suspended, while perature is outside software-configurable setpoints, com-
heating operation is allowed. The controller creates an pressor operation is suspended and high or low water
alarm available in software. The alarm automatically temperature alarms occur. The alarm automatically
resets when the water level returns to normal. resets when the water temperature returns to within 6
deg. F of the setpoint.
● Safety Control – The unit monitors refrigerant pressure
and generates separate high-pressure and low-pressure ● Unit Self-test Mode – While the unit is in occupied
alarms available in software. While either alarm is active, mode, a self-test can be initiated via software. Upon initi-
compressor operation is suspended. In a refrigerant low- ation of the test, compressor operation is suspended for
temperature condition, an alarm occurs and the unit a minimum of five minutes, cooling attained temperatures
operates in cooling mode for 60 seconds to defrost the are cleared, and attained temperature alarms are
heat exchanger, after which compressor operation is cleared. The unit then switches to full heat for four min-
suspended. These alarms can be reset in software or by utes and then records the attained supply air tempera-
cycling power to the controller. ture. Compressor operation is then suspended for five
minutes. The unit then switches to full cooling for four
● Attained Temperature and Water Temperature minutes and the attained supply air temperature is
Alarms – Attained temperature, water temperature recorded. Attained temperature alarms are set if the
alarms with software-adjustable setpoints are available attained temperatures failed to reach alarm setpoints
in software. The controller samples supply air and during heating or cooling.
records attained temperatures for heating and cooling. If
after two hours of operation, the attained temperature
does not meet the software-configurable setpoint for
heating or cooling as appropriate, a software alarm
occurs. The alarm automatically resets when the attained

IM 778 / Page 15
Thermostat Connection Diagrams
Mark IV/AC Units – Unit Sizes 007-060
7-Day Programmable Electronic Thermostat (P/N 107095901)
WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit1)

C W1 Y1 W2 Y2 G O W2 G W1 Y1 F E L U A P V R C
Thermostat Terminals

Includes Thermostat and Wall Plate.

Refer to the installation, operation &


application guide (LIA217) for thermo-
stat 107095901 installation details
R

Non-Programmable Electronic Thermostat (P/N 668054201)


WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit1)
Override (Optional)
O W2 G W1 Y1 F E L U A P V R C
O
C W1 Y1 W2 Y2 G
Thermostat Terminals

Includes Thermostat and Wall Plate.

Refer to the installation, operation &


application guide (LIA204-4) for ther-
mostat 668054201 installation details
R

Optional Remote Sensor (P/N 667740201)


1. Remove cover from remote sensor housing.
2. Select an appropriate location for mounting the remote
sensor.
3. Mount remote sensor unit using hardware provided. Thermostat

4. Install two strand shielded wire between remote sensor


and thermostat. Shielded wire must be used. Remote Sensor
Do not run remote sensor wire in conduit with other wires.
• Wire 1 should run between the S1 terminal on the ther- S1 S2
mostat and the S1 terminal on the remote sensor

• Wire 2 should run between the S2 terminal on the ther- S1 S2


mostat and the S2 terminal on the remote sensor Wire 2

• Connect the shielding of the wire to the S2 terminal on Wire 1


the thermostat Cut R12 from
circuit board
5. Disable the main sensor (R12) on the thermostat by
cutting it from the circuit board.

Page 16 / IM 778
Options on Mark IV/AC Units
Auxiliary Relay (P/N 106059701)
WSHP Mark IV/AC Board Low Voltage Terminal Strip The auxiliary relay is designed to interface external equip-
ment with the Mark IV/AC board. The auxiliary relay
O W2 G W1 Y1 F E L U A P V R C
has been provided with the components necessary
to protect from electrical damage that may occur to the
Operation: In this example the Mark IV/AC board when using standard off-the-self relays.
auxiliary relay contacts can be The auxiliary relay can be used to provide fault signals,
used to indicate a fault condi- 1
tion. With the auxiliary relay
Orange unit operation signals, or to provide a means for remote
connected as shown, the nor- 2 Yellow equipment to control the Mark IV/AC board. The orange,
mally open contacts will close yellow, and white connections are short flying leads
during a fault condition. 3 White
pre-attached to the board. The diagrams shown are some
Auxiliary Relay connection examples.

WSHP Mark IV/AC Board Low Voltage Terminal Strip


WSHP Mark IV/AC Board Low Voltage Terminal Strip
O W2 G W1 Y1 F E L U A P V R C
O W2 G W1 Y1 F E L U A P V R C

Operation: In this example


the auxiliary relay contacts 1 Orange Operation: In this example the
can be used to signal WSHP 1 Orange auxiliary relay is used to interface
2 Yellow
fan operation to another other control devices to the Mark
device. In this example when White Yellow IV/AC board. Using the Orange (-)
the thermostat energizes the
3 2
and White (+) wires, and 24vac or
“G” terminal the auxiliary relay Auxiliary Relay
normally open contacts will 3 White 24vdc, another device could be
close. used to start and stop the WSHP
Auxiliary Relay heating sequence.

IM 778 / Page 17
Multiple Unit Control (up to 3 units) (P/N 056794201)
This multiple unit control board is an accessory used when or “Y1” terminals (i.e. Boilerless System Kit).
you need to control up to 3-units from a single thermostat. The multiple unit control board provides the components
The board is typically mounted in the unit control box clos- necessary to protect the Mark IV/AC board from electrical
est to the thermostat. A maximum of 2 boards may be used damage that may occur when using standard off-the-shelf
together if up to 6-units must be connected and controlled relays.
from a single thermostat.
Do not use the unoccupied (U-terminal) feature with the
This version of the board uses VAC relays and should not multiple unit control board.
be used in combination with any other accessories or
equipment that require VDC connections to the “G”, “W1”,
WSHP Mark IV/AC Board Low Voltage Terminal Strip
O W2 G W1 Y1 F E L U A P V R C
R
Y
TB3
G
W
Multiple Unit WSHP Mark IV/AC Board Low Voltage Terminal Strip
Control Panel
O W2 G W1 Y1 F E L U A P V R C
R
Y
TB2
G
W
WSHP Mark IV/AC Board Low Voltage Terminal Strip
O W2 G W1 Y1 F E L U A P V R C
R
Y
TB1
TB4 G
G W Y R C W
G
Thermostat Terminals
C W1 Y1 W2 Y2
R

Multiple Unit Control (up to 2 units) (P/N 106059801)


This multiple unit control board is an accessory used when or equipment that require VAC connections to the “G”,
you need to control up to 2-units from a single thermostat. “W1”, or “Y1” terminals (i.e. Boilerless System Kit). Do not
The board is typically mounted in the unit control box clos- use the unoccupied (U-terminal) feature with the multiple
est to the thermostat. The “G”, “W”, “Y”, “C”, and “L” con- unit control board.
nections are short flying leads pre-attached to the board. A The multiple unit control board provides the components
maximum of 3 boards may be used together if up to 4-units necessary to protect the Mark IV/AC board from electrical
must be connected and controlled from a single thermostat. damage that may occur when using standard off-the-shelf
This version of the board uses VDC relays and should not be relays.
used in combination with any other accessories
g p
O W2 G W1 Y1 F E L U A P V R C

R
Multiple Unit Y
Control
Panel G
W
G W Y C L
L WSHP Mark IV/AC Board Low Voltage Terminal Strip
O W2 G W1 Y1 F E L U A P V R C
G
Thermostat Terminals
C W1 Y1 W2 Y2
R

Page 18 / IM 778
Motorized Valve & Relay for Unit Sizes 007 thru 060
Wired as shown below the motorized valve will open on a Note: The wiring shown below can only be used when the “P” ter-
call for compressor operation. Valves for unit sizes 007 to minal is not being used as a pump restart signal to other equip-
019 are 1⁄ 2" while unit sizes 024 to 060 are 3 ⁄4". Other ther- ment. If the “P” terminal must be used as a pump restart signal to
mostat combinations may be used. Valve and auxiliary other equipment, then wire the auxiliary relay’s yellow wire to
“Y1”, white wire to “W1”, and orange wire to “C”, then the valve
relay(s) are purchased separately. will open on a call for occupied heating or cooling from the
thermostat.

Connector

Valve 36" (915 mm)


Lead Length Black to 6

6
3 White to 1
1

Conduit Pins, Plug


Female
Anti-Short
Bushing

P/N 060977401 - 1/2" Motorized Valve Kit


P/N 060977301 - 3/4" Motorized Valve Kit
P/N 859004354 - Valve Relay Kit

WSHP Mark IV/AC Board Low Voltage Terminal Strip

O W2 G W1 Y1 F E L U A P V R C
Time Clock
(by others)

1 Orange
Daisy-chain to
2 Yellow additional Mark IV/AC
board “U” terminals
3 White
Auxiliary Relay
GN
BL

6 3 1

IM 778 / Page 19
Boilerless System Kit (BSK) – P/N 062522204 for sizes 007 - 060
The BSK option for use with the Mark IV/AC control board
provides the capability to control a remote duct heater. The
duct heater must be provided with a low voltage control
circuit that only requires a set of dry contacts for operation.
The contacts shown on the Boilerless System board (termi-
nals 1, 2, and 3) are used to control the remote duct heater,
the N.O. contacts will close on a call for duct heater heat.
POT1 provides a means to manually adjust the water tem-
perature setpoint (adjustment range is 43oF to 60oF). The
Normal/Override switch provides a means to manually force
electric heat to always be used in place of heat pump heat
when in the override position (default position is normal -
heat pump heat).
When the water temperature drops below the value of
POT1, then the duct heater will be used instead of heat
pump heat on a call for heat from the low voltage thermostat
(not included).

The BSK field installed kits include the sheet metal enclo-
sure with cover, wire harness, boilerless system board, aux-
iliary relay, and water temperature sensor. When used, one
BSK is required for each unit. To use the BSK kit you attach
9.66 the sheet metal enclosure to the unit as shown, route the 4-
(245 mm)
(007 – 042) wire harness through knockouts and connect to the Mark
14.50 IV/AC board, mount and connect and insulate the water tem-
(368 mm) perature sensor on the water supply line, and then connect
(048 – 060)
the duct heater control contacts to the duct heater control
circuit.
If night setback (U-terminal) is used, the duct heater will
respond to the occupied W1 thermostat signal. The load
shed input (L-terminal) cannot be used for other control
functions when being used with the BSK.
1.75 The BSK is a DC voltage device, when the BSK is used the
6.5 (165 mm) (007 – 042) (44.5 mm) thermostat must be wired for VDC operation.
4.12 (105 mm) (048 – 060)
When the water temperature drops below the value of
POT1, then the duct heater will be used instead of heat
pump heat on a call for heat
Wire Ends to be Field from the low voltage thermo-
Connected to the stat (not included).
Mark IV/AC Board
RD

43 Ohm

Water
OR

4-pin Temperature
Plug Sensor
OR RD
5
BR

WH

WH
4

WH BK
3

GR GR
RD

Boilerless
2

Signal to remote
System duct heater
Board
1

control circuit
OR

1 Orange
Normal

Override

2 Yellow
Pot 1
3 White
Auxiliary Relay
WH

YE

Page 20 / IM 778
Pump Restart Relay Kit P/N 061419001

Used as an option with the Mark IV/AC board, the pump will change state causing a contact closure between termi-
restart relay kit provides a means to alert the loop water nal 58 and 64 signaling the loop water control (LWC) panel
controller that water flow is required by a WSHP so that the to restart the loop pump if Off.
system pump can be started. This option is typically used in The pump restart relay kit is typically mounted within one
installations where the pump may be shut off when there is WSHP or within the LWC panel, whichever is more conve-
no need for water flow (i.e. temperature OK, etc.). Typically nient, diagrams are provided below for each location. To
only one pump restart relay kit is required per installation as install the relay, remove the cover on the double-faced tape
up to 200 Mark IV/AC boards can be “daisy-chained” provided on the relay and attach the relay either to the
together. inside of the LWC panel (adjacent to circuit breaker CB1
The Mark IV/AC “P” terminal is used to determine WSHP and terminal block TB3) or in the WSHP control box (in a
compressor operation. Wired as shown below, when com- convenient location), then wire as shown below.
pressor operation is required, the Mark IV/AC “P” terminal

Wiring Pump Restart Relay when Installed within the LWC Panel
WSHP Mark IV/AC Board Low Voltage Terminal Strip
O W2 G W1 Y1 F E L U A P V R C

Daisy chain to other Mark


IV/AC board “P” and “C”
terminals
7
Pump
Restart 6
Relay
5 64 Loop
4 58 Water
Controller
3 Terminals

2
1 65

Wiring Pump Restart Relay when Installed within a WSHP Control Box

WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit 1)


O W2 G W1 Y1 F E L U A P V R C

Daisy chain to other Mark


IV/AC board “P” and “C”
terminals
7
Pump
Restart 6
Relay
5 64 Loop
4 58 Water
Controller
3 Terminals

IM 778 / Page 21
Field Installed Options on MicroTech 2000 Units
MicroTech 2000 units can provide up to 4-outputs, that can 4) Motorized Water Valve
be configured for any of the following output control These outputs provide control for a motorized water
signals: valve that can be used to stop or divert flow away from
1) Scheduled Output the WSHP when compressor operation is not needed.
When using a Network Master Panel (NMP) these out- The output will be energized when compressor operation
puts can be assigned to one of 32 available schedules. is required.
The output will energize when the assigned schedule is If more than one of the above control signals is required on
occupied and de-energize when unoccupied. These out- a single WSHP, the MicroTech 2000 Auxiliary Module Kit
puts could be used to control lights, etc. (107239001) must be used and these additional output con-
2) Auxiliary Heat (Skin Heat) trol signals will be connected to the Auxiliary board. The
When using a Loop Water Controller (LWC) the Auxiliary board is provided in all 2-circuit units. 1-circuit
MicroTech 2000 receives loop water temperature infor- units can provide up to 4-outputs while 2-circuit units only
mation from the LWC and will use the Auxiliary Heat out- have 3-outputs available. The 4th control signal output
put for heating when loop water temperature is inappro- shown in the diagrams below is not available on 2-circuit
priate for heat pump heating. These outputs provide a units.
signal that can be used to control a remote electric If the Auxiliary board is added in the field to provide addi-
heater. The output will energize on a call for electric heat tional outputs it will need to be mounted within the WSHP
and de-energize when not required. control box so that J1 on the Auxiliary board can be con-
3) Fresh Air Damper nected to J6 on the MicroTech 2000 board without exceed-
These outputs provide a signal that can be used to con- ing a maximum wire length of 10".
trol a remote fresh air damper. The output will energize Also, each output is by default configured to “none” and
when the unit fan is energized and de-energize when the must be field set to one of the four signal types listed above
unit fan is de-energized. using the Monitor software, cable, and a PC communicat-
ing to the unit through an MCG panel.

1st Control Signal Output 2nd Control Signal Output

Terminals Located on
Microtech 2000 Auxiliary Board
J6
(by others)
Terminal Boards
(Located externally on the WSHP chassis)
4 3 2 1
1 2 3 4 5 6 7 E L U P C
24VAC
IMPORTANT: 24VAC 24VAC
To use onboard 24VAC, change Pilot Duty Relay Pilot Duty Relay
the jumper PF1 on the (by others) (by others)
MicroTech 2000 controller from
factory default pins 1 and 2 to
pins 2 and 3.

Use contacts as needed for option

3rd Control Signal Output 4th Control Signal Output

Terminals Located on Terminals Located on


Microtech 2000 Auxiliary Board (by others) Microtech 2000 Auxiliary Board
J7 J10
(by others)
4 3 2 1 4 3 2 1

24VAC 24VAC
24VAC
24VAC Pilot Duty Relay
Pilot Duty Relay (by others)
(by others)

Use contacts as needed for option


Use contacts as needed for option

Page 22 / IM 778
Mark IV/AC Sequence of Operation Read Outputs

Check Timers
14-Position Terminal Strip
Ye s Hi
Pres. Sw ?
Pin Designation Description No
1 C Transformer ground (Ovac) Ye s
2 R Transformer supply (24vac) Brown Out ?
3 V -DC power connection No
4 P Pump request output Ye s
LowTempSw?
5 A Alarm fault output No
6 U Unoccupied input
Ye s
7 L Load shed input Lo Shed?
8 E Remote shutdown input No
9 F +DC power connection Ye s
N SB?
10 Y1 Occupied cooling mode input
No
11 W1 Occupied heating mode input
12 G Fan only input Ye s
Cond.Overflow?
13 W2 Unoccupied heating mode input No
14 O` Tenant override input Ye s
R-W1?
No
LED Status and Fault Output Status Ye s
R-Y1?
Board Status LED’s Fault Output No
Mode Yellow Green Red Terminal A
Occupied Off On Off Energized
Stop Comp.
Unoccupied On On Of Energized
Load Shed Off Off On Energized Flash Red LED
Condensate Overflow On Dim Off De-Energized
High/Low Pressure Fault Off Off Flash De-Energized
Low Temperature Fault* Flash Off Off De-Energized Stop Comp.
Brownout Off Flash Off De-Energized
Emergency Shutdown Off Flash Off De-Energized Stop Fan

*in heating mode only Flash Green LED


Note: The fault output is energized when no faults exist. The fault ouput is
de-energized during faults and when unit power is off.
Stop Comp.

General Use and Information Htg Mode?


No

The Mark IV/AC control board is provided with three drive terminals, R(24vac), Ye s
F(24vdc), and C(Ovac) that can be used by the end user to drive the thermostat Flash Yellow LED
inputs (G, Y1, W1, and W2) and control inputs (U, L, E, and O). Any combination of
a single board drive terminal (R, F, or C) may be used to operate the Mark IV/AC
board’s control or thermostat inputs. However, only one drive terminal (R, F, or C)
Stop Comp.
can be connected to any individual input terminal or damage will occur. Some of the
control inputs are used within the Water Source Heat Pump and not accessible to
the end user. For example, HP, LT, and COF are not available for use by the end user. Turn On Red LED

Typically the Mark IV/AC board’s R(24vac) terminal is used to drive the board’s ther-
mostat inputs and control inputs by connecting it to the R terminal of an industry No
R-W2?
standard thermostat. The control outputs of the standard thermostat are then con-
Ye s
nected to the Mark IV/AC board thermostat inputs and control inputs as needed.
Any remaining board input(s) may be operated by additional thermostat outputs or Start Comp.
remote relays (dry contacts only).

All Mark IV/AC board inputs must be operated by dry contacts powered by the con- No
trol board’s power terminals. No solid state devices (Triacs) may be used to operate Cooling Mode
Mark IV/AC board inputs. No outside power source may be used to operate Mark
IV/AC board inputs. Turn On Yellow LED

Stop Comp.
Using Drive Using Drive Using Drive
Terminal R (24vac) Terminal F (24vdc) Terminal C (ground)
De-engergized Energized D-energized Energized De-energized Energized Reversing Valve On
Place the Meters
Red (+) Lead on Place the Meters Place the Meters Place the Meters
Time Delay
Input to be on Black (-) Lead Black (-) Lead Black (-) Lead
on C on V on R
checked Start Comp.
U, L, E, Y1, W1, 10 to 22 to 30 to 10 to 22 to
Ovdc
G. W2. P 14vac 26vac 33vdc 14vac 26vac

Start Comp.

IM 778 / Page 23
Troubleshooting Water Source Heat Pump
DANGER
Field wiring must comply with local and national fire, safety, and electrical codes, and voltage to the system must be within the limits
shown in the job-specific drawings and unit electrical data plate(s).
All power supply to unit must be disconnected when making field connections. Rigorously adhere to lockout and tagout procedures.
Improper wiring or procedure can cause electric, personal injury or death.

Low Voltage, check power Fuse may be blown, circuit Wires may be loose or broken. Unit Control, check thermostat
supply voltage breaker is open Replace or retighten wires for correct wiring or bad thermostat

Check wiring - loose or broken


and check for bad Check capacitor
connection
Neither Fan, nor Check wiring - loose or broken
Compressor Runs and check for bad
Check relays and contacts,
also capacitor and wiring connection

Hi pressure lockout -
A. Cool mode, check water flow
Check high pressure switch B. Heating mode, check air flow
and low temperature switch to C. Check reversing valve for
see if unit is cycling on the safety Compressor runs Fan operates, proper valve position
in short cycle Compressor does not
Unit
Check to see if the reversing Check compressor overload
valve is not hung up and is make sure it is closed
operating correctly

Check compressor to ground,


Check condensate overflow or for internal short to ground.
switch in cool mode of operation

Compressor winding may be


open. Check continuity with
Compressor attempts to start ohm meter
Insufficient cooling or heating
but does not

Check compressor wiring for Check thermostat for improper


defective wiring or loose location
connection

Check for defective compressor Check for proper air flow. Filter
internal windings with ohm meter could be dirty

Check for bad compressor Check blower assembly for


capacitor dirt or bad fan motor capacity

Check for lock rotor amp draw Check for low refrigerant charge

Check amp draw on blower


assembly

Page 24 / IM 778
Troubleshooting
The in and outs of R410A ! WARNING
Refrigerant 410A is a non-ozone depleting blend of two Recycle/recovery equipment must be designated for
refrigerants HFC-125 and HFC-32 in a fifty percent mixture. R-410A. R-410A pressure is greater than R-22.
Refrigerant 410A exhibits higher operating pressure and Improper equipment can cause severe injury or death.
refrigeration capacity than R-22. R-410A refrigerant is
intended for use in new air conditioning application that has
Make certain that the recycle or recovery equipment used
traditionally been serviced by HCFC-22 or R-22. Due to
higher capacity and pressure of R-410A, it is not recom- is designed for R-410A. The pressure of R-410A refrigerant
mended as a retrofit to existing R-22 systems. is approximately 60 percent greater than that of R-22.
Pressure gauges require a range up to 800 PSIG high side
Although R-410A is non-flammable at ambient temper- and 250 PSIG low side. Recovery cylinders require a 400
ature and atmospheric pressure, it can become com- PSIG rating – do not put R-410A in a 300 PSIG rated
bustible under pressure when mixed with air. (NOTE: R- cylinder.
410A should not be mixed with air under pressure for
leak testing. Pressure mixtures of dry nitrogen and R-410A (NOTE: because a water source heat pump operates under
can be used for leak testing.) a wide range of water and air temperatures, the values
printed below are to be taken as suggested pressure and
temperatures.) All McQuay water source heat pumps are
Lubrication designed for commercial use. The units are designed for
the cooling mode of operation and fail safe to cooling. The
R410A should be used only with polyolester (POE) oil. The
reversing valve is energized for the heating mode of
HFC refrigerant components in R-410A will not be compat-
operation.
ible with mineral oil or alkylbenzene lubricants. R-410A sys-
tems will be charged with the OEM recommended lubri-
cant, ready for use with R-410A. Superheat Head Pressure Water Delta T
8 to 14 degrees 335-355 PSIG 10° to 12°
Charging
Due to the zeotropic nature of R-410A, it should be charged All information above is based on ISO standard 13256-1
as a liquid. In situations where vapor is normally charged and are tested at these conditions.
into a system, a valve should be installed in the charging
line to flash the liquid to vapor while charging.

General Maintenance
1. Normal maintenance on all conditioners is generally lim- 4. Record performance measurements of volts, amps, and
ited to filter changes. Motors used with WSHP unit size water temperature differences (both heating and cooling).
007 through 060 are provided with permanently lubricat- A comparison of logged data with start-up and other
ed motors and require no oiling even though oil caps may annual data is useful as an indicator of general equipment
be provided. condition.
2. Filter changes are required at regular intervals. The time 5. Periodic lockouts almost always are caused by air or
period between changes will depend upon the project water problems. The lockout (shutdown) of the condition-
requirements. Some applications such as motels pro- er is a normal protective result. Check for dirt in the water
duce a lot of lint from carpeting and linen changes, and system, water flow rates, water temperatures, airflow
will require more frequent filter changes. Check filters at rates (may be a dirty filter), and air temperatures. If the
60-day intervals for the first year until experience is lockout occurs in the morning following a return from
acquired. If light cannot be seen through the filter when night setback, entering air below machine limits may be
held up to sunlight or a bright light, it should be changed. the cause.
A more critical standard may be desirable.
3. The condensate drain pan should be checked annually
and cleaned and flushed as required.

IM 778 / Page 25
Troubleshooting Refrigeration Circuit
Air Water Safety
Head Suction Compressor Super Temp (loops) Temp Lock
Symptom Pressure Pressure Amp Draw Heat Subcooling Differential Differential Out
Charge
Undercharge System Low Low Low High Low Low Low Low Pressure
(Possible Leak)
Normal
Overcharge System High High High Normal High Normal High Pressure
Low
Low Air Flow Heating High High High High Low High Low High Pressure
Normal
Low Air Flow Cooling Low Low Low Low High High Low Low Temp
Normal
Low Low
Low Water Flow Heating Normal Normal Low Low High Low High Low Temp
Low Water Flow Cooling High High High High Low Low High High Pressure
High Air Flow Heating Low Low Low Low High Low Low Low Temp
High Air Flow Cooling Low High Normal High Low Low Normal High Pressure
High Water Flow Heating Normal Low Normal High Normal Normal Low High Pressure
High Water Flow Cooling Low Low Low Low High Normal Low Low Temp
TXV Restricted High Low Normal High High Low Low
Low

Cooling Mode Heating Mode

Return Air Return Air


Thermal Co-Axial Heat Thermal Co-Axial Heat
Expansion Valve Exchanger Expansion Valve Exchanger
Coil – Coil –
Air to Air to
Refrigerant Refrigerant
Heat Heat Water In
Water In Exchanger
Exchanger
Water Out Water Out
Sensing Sensing
Bulb Bulb
and and
Capillary Capillary
Tube Tube
Compressor Compressor

Blower Blower

Reversing Valve Reversing Valve

Conditioned Air Conditioned Air


(Cooling) (Heating)

Cooling Refrigeration Cycle Heating Refrigeration Cycle


When the wall thermostat is calling for COOLING, the When the wall thermostat is calling for HEATING, the
reversing valve directs the flow of the refrigerant, a hot gas, reversing valve directs the flow of the refrigerant, a hot gas,
leaving the compressor, to the water-to-refrigerant heat leaving the compressor, to the air-to-refrigerant heat
exchanger. Here the heat is removed by the water and the exchanger coil. Here the heat is removed by the air passing
hot gas condenses to become a liquid. The liquid then over the surfaces of the coil and the hot gas condenses to
flows through a thermal expansion metering system to the become a liquid. The liquid then flows through a capillary
air-to-refrigerant heat exchanger coil. The liquid then evap- thermal expansion metering system to the water-to-refriger-
orates becoming a gas, at the same time absorbing heat ant heat exchanger. The liquid then evaporates becoming a
and cooling the air passing over the surfaces of the coil. gas, at the same time absorbing heat and cooling the water.
The refrigerant then flows as a low pressure gas through The refrigerant then flows as a low pressure gas through the
the reversing valve and back to the suction side of the reversing valve and back to the suction side of the com-
compressor to complete the cycle. pressor to complete the cycle.

Page 26 / IM 778
McQuay Training and Development

Now that you have made an investment in modern, efficient McQuay equipment, its care should be a
high priority. For training information on all McQuay HVAC products, please visit us at www.mcquay.com
and click on training, or call 540-248-9646 and ask for the Training Department.

Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form
933-43285Y. To find your local McQuay Representative, go to www.mcquay.com.

This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.mcquay.com.

Products Manufactured in an ISO Certified Facility.

©2006 McQuay International • 800.432.1342 • www.mcquay.com IM 778-2 (Rev 6/06)

You might also like